Correspondence FIE COpr May 22, 2006 /iiiiiii�,i CITY OF TIGARD OREGON Canterbury Place LLC Dave Gutschmidt 11625 SE 5 Street Bellevue, WA 98005 RE: FIRE ALARM SYSTEM /SPRINKLER WA'1ER FLOW ALARM Project Information - TWO STORY 6 PLEX CARRIAGE CONDOMINIUMS — BUILDING #2 Building Permit: BUP2006 -00149 Occupancy Type: R -1 Address: /0 Es 10- 794- Eanterbury Lane Construction Type: V -1 hour —Sprinklered Area: 2 Story, 7,748 Sq Ft Tenant Name: Canterbury Woods Hazard: Light Residential The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief. All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, TVFR99 -01 5. Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. 1109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 6. The annunciation of all zones and device identification shall be on electrically supervised initiating circuits to the main fire alarm control panel. Alarm, supervisory and trouble signals shall be annunciated in the main control panel and in any required remote annunciator panels by means of an audible signal and a visual display. Such annunciation shall indicate the building, floor, zone or other designated area from which the alarm or trouble signal originated. For the purpose of annunciation, zoning shall be in accordance with the following: 1. When the fire- protective signaling system serves more than one building, each building shall be considered as a separate zone. 2. Each floor of a building shall be considered as a separate zone. 3. Each section of floor of a building that is separated by area separation walls or by horizontal exits shall be considered as a separate zone. 4. Annunciation shall be further divided into zones where deemed necessary by the authority having jurisdiction. 5. Identification of the type of alarm, initiating devices such as manual, automatic, sprinkler water flow, sprinkler supervisory switches, etc.. shall be separately indicated on electrically supervised initiating circuits to the main fire alarm control unit. TVFR99 -01, section 1007.3.3.7 7. When required by chief, fire alarm systems shall be monitored by an approved central, proprietary or remote station service or a local alarm which gives audible and visual signals at a constantly attended location. TVFR99 -01, section 1007.3.3.6.1 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout . all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull -/ / al He e , Senior Plans Examiner