CITY OF TIGARD
OREGON
May 23, 1995
Kathy Lorinc
12435 SW 121st Ave
Tigard OR 97223
RE: Board and Care Facility located at 12435 SW 121st Ave
Thank you for your response to my letter dated March 21, 1995. You have
addressed all items except the installation of the sprinkler system. Pursuant
to your request, we will issue a Temporary Certificate of Occupancy for 30 days
from this date to complete the installation of the sprinkler system.
Since
I
David Scott, .
Building Official
c: TVFR
File
George Steele
Enclosure: Temp Cart of Occ
a \mst93_)601 \emp.occ
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
March 21, 1995 CIW OF TIGAR®
OREGON
Mr. and Mrs. Joseph Lornic
12435 SW 121st Avenue
Tigard, OR 97223
RE: Board and Care Facility located at 12435 SW 121st Avenue
Dear Mr. and Mrs. Lornic:
This letter is to follow -up my visit to your facility on March 14, 1995. That
visit and our review of City records has revealed that the last two permits
(BUP 92 -0355 and MST 93 -0601) and Certificates of Occupancy were issued in error,
and that several code violations exist in your facility. Sections 303(e) and
308(f) gives the Building Official authority to suspend or revoke permits and
Certificates of Occupancy when issued in error or when it is determined that the
building is in violation of any of the provisions of the code.
I do not wish to suspend or revoke your Certificates of Occupancy. Based upon
my review, there are reasonable steps you may employ to achieve compliance at
your facility. Tigard will correct its files accordingly.
To make your facility compliant as an SR2 occupancy for 15 residents, the
following must be done:
1. The evacuation capability for the facility must be determined using
the attached Appendix F from the National Fire Protection
Association's "Life Safety Code Handbook," attached. You must
achieve a slow rating.
2. The group of 5 bedrooms in the rear must have no more than 5
residents.
3. The group of 3 bedrooms adjacent to the middle living area must have
no more than 5 residents and a 3' -0" wide swinging exit door must be
installed at the existing sliding door.
4. The group of 4 bedrooms at the front must have no more than 5
residents.
5. The two storage rooms at the basement and the furnace room adjacent
to the kitchen must be enclosed within a one -hour occupancy
separation, or these rooms shall be provided with sprinklers and
self - closing smoke tight doors.
6. The kitchen shall be provided with sprinkler protection above the
cooking appliances.
7. The chain lock at the front door must be removed so that the door is
operable from the inside without any special knowledge or effort.
8. The locks on the exterior gate across the driveway must be removed
since this is in the exit path.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Mr. and Mrs. Lornic
March 21, 1995
Page 2
To make your facility compliant as an SR3 occupany for 15 residents, the
following must be done:
1. The evacuation capability for the facility must be determined using
the attached Appendix F from the National Fire Protection
Association's "Life Safety Code Handbook," attached. You must
achieve a prompt rating.
2. The two storage rooms at the basement and the furnace room adjacent
to the kitchen must be enclosed within a one -hour occupancy
separation, or these rooms shall be provided with sprinklers and
self - closing smoke tight doors.
3. The kitchen shall be provided with sprinkler protection above the
cooking appliances.
4. The chain lock at the front door must be removed so that the door is
operable from the inside without any special knowledge or effort.
5. The locks on the exterior gate across the driveway must be removed
since this is in the exit path.
Please determine your course of action so we may proceed to resolve this matter.
Thank you for your cooperation.
Sincer ly,
David Scott, P. .
Building Official
DS:wh
c: TVFR
file (�
H. 1 OC 417C.i
v.
March 21, 1995
Mr and Mrs Joseph Lorinc
12435 SW 121st Avenue
Tigard OR 97223
RE: Board and Care Facility located at 12435 SW 121st Avenue
Dear Mr and Mrs Lorinc:
This letter is to follow -up my visit to your facility on March 14, 1995. That
visit and our review of City records has revealed that the last two permits (BUP
92 -0355 and MST 93 -0601) and Certificates of Occupancy were issued in error, and
that several code violations exist in your facility. Sections 303(e) and 308(f)
gives the Building Official authority to suspend or revoke permits and
Certificates of Occupancy when issued in error or when it is determined that the
building is in violation of any of the provisions of the code.
I do not wish to suspend or revoke your Certificates of Occupancy. Based upon
my review, there are reasonable steps you may employ to achieve compliance at
your facility. Tigard will correct its files accordingly.
To make your facility compliant as an SR2 occupancy for 15 residents, the
following must be done:
1. The evacuation capability for the facility must be determined using
the attached Appendix F from the National Fire Protection
Association's "Life Safety Code Handbook," attached. You must
achieve a slow rating.
2. The group of 5 bedrooms in the rear must have no more than 5
residents.
3. The group of 3 bedrooms adjacent to the middle living area must have
no more than 5 residents and a 3' -0" wide swinging exit door must be
installed at the existing sliding door.
4. The group of 4 bedrooms at the front must have no more than 5
residents.
5. The two storage rooms at the basement and the furnace room adjacent
to the kitchen must be enclosed within a one -hour occupancy
separation, or these rooms shall be provided with sprinklers and
self - closing smoke tight doors.
6. The kitchen shall be provided with sprinkler protection above the
cooking appliances.
7. The chain lock at the front door must be removed so that the door is
operable from the inside without any special knowledge or effort.
8. The locks on the exterior gate across the driveway must be removed
since this is in the exit path.
To make your facility compliant as an SR3 occupancy for 15 residents, the
following must be done:
1. The evacuation capability for the facility must be determined using
the attached Appendix F from the National Fire Protection
Association's "Life Safety Handbook," attached. You must achieve a
prompt rating.
2. The two storage rooms at the basement and the furnace room adjacent
to the kitchen must be enclosed within a one -hour occupancy
separation, or these rooms shall be provided with sprinklers and
self - closing smoke tight doors.
3. The kitchen shall be provided with sprinkler protection above the
cooking appliances.
4. The chain lock at the front door must be removed so that the door is
operable from the inside without any special knowledge or effort.
5. The locks on the exterior gate across the driveway must be removed
since this is in the exit path.
Please determine your course of action so we may proceed to resolve this matter.
Thank you for your cooperation.
Sincerely,
David Scott, P.E.
Building Official
c: TVFR
File