Loading...
Correspondence t June 27, 2008 Teken Construction Tim Hickmen 4348 SE Rosewood St. Hillsboro, OR 97223 RE: 2 -story kitchen and bonus room addition. Project Information Building Permit: MST2008 -00081 Construction Type: VB Address: 13170 SW Howard Occupancy Type: R -3 Area: 635 Sq. Ft. Stories: 2 The plan review was performed under the 2005 Oregon Residential Specialty Code. The review of the submitted plans will be completed when the following information is provided. 1. Manufactured trusses were not present with the plans. Please provide two copies, to include the hangers called out for the connection from the existing trusses to the carrier truss. 2. Engineering packet has calculated a 3 1/8" X 9" X 7' -6" Glulam, plans do not show such beam, please indicate location on plans. 3. Engineering packet has the "Beam under girder truss" as a 5 1/8" X 9" X 5' Glulam. Plan shows three arrows at such location but total span for middle section (rec. room) is 7' on the inside. Please clarify. 4. When responding, provide two copies and an itemized letter stating in what way each issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brandon Shaw Plans Examiner BrandonS @tigard - or.gov Phone: 503.718.2425 Fax: 503.624.3681 F- nt • MILLER CONSULTING July 1,2008 ENGINEERS Mr. Kerry VanderZanden Partin and Hill Architects and Planners 209 NE Lincoln Hillsboro, OR 97124 Subject: Willis Addition 13170 SW Howard Dr., Tigard MCE Project Number: 080444 Building Permit #: MST2008 -00081 Dear Mr. VanderZanden: The following is a plan check response.for the structural items on the City of Tigard plan check submitted by Brandon Shaw. 1.) "Engineering packet has calculated -a 31/8" x 9" x 7 ' -6" glulam; plans do not show such a beam. Please indicate location on plans." MCE Response: The 3 1/8" x 9" glulam from the calculations has been replaced by a 5 1/8" x 9 glulam on the plans. This is a larger beam that is required and is acceptable. 2.) "Engineering packet has the 'beam under girder:truss' as a 5 -1/8" x 9" x 5' glulam. Plan shows -three arrows - at such location but total span for middle section (recreation room) is 7' on the inside. Please clarify. MCE Response: The point load for the girder truss lands on the beam over the opening to the closet. The span in this location is:5' -0 ". The span over the opening to the recreation room does not have the girder truss point load on it. The calculation for this beam is done as the "Beam into Addition" on sheet7. This . beam has been upsized to a 5 1/8" x 9" as stated above. If you have any questions, please feel free to contact our office. /:c% Pr Respectfully, i- _ /- 7 977PE Miller Consulting Engi e rs, Inc. ' " • J (3 � (/ S, t .iiA� h�c e issa McFe on, . "" Associate w i2_370 9570 SW Barbur Blvd., Suite 100 Portland, Oregon 97219 -5412 Phone (503) 246 -1250 Fax (503) 246 -1395 www.mlllerengrs.00m American Consulting a Engineers Council