Loading...
Correspondence ,. - April 17, 2008 \I 0 Allison May Riverside Homes, Inc. 1925 NW Amberglen Pkwy. Ste. 200 Beaverton, Oregon, 97006 RE: New Single Family Residence Building Permit: MST2008 -00026 Construction Type: VB Address: 12717 SW Da Vinci Ln. Occupancy Type: R -3 Area: 3474 Sq. Ft. Stories: 3 The plan review was performed under the 2005 Oregon Residential Specialty Code. The review of the submitted plans will be completed when the following information is provided. Please provide two copies of revised plan sheets to reflect the accurate elevations as shown on the site plan provided. Provide two copies of revised engineering that reflect the change in the height of the structure at some points as much as 4.5 feet, as this affects the lateral design calculations. If any changes are made to the shear walls, provide two copies of plan sheets affected. ..3'." Provide two copies of a cut section showing the post and beam with the accurate elevation shown. Provide a detail of how the post bracing will meet code, or the design of such. Provide a detail of any cripple walls and designate the locations on the plan. The floor framing pages provided are incomplete. Provide two sets of manufactured r framing depicting the floor joist size, spacing, and all floor beams to be used. 6. Provide two copies of the lower floor plan showing the required smoke detector. There is no detail for slab edge insulation, neither is there enough information on the lower floor plan to clarify how the energy code will be met at the lower level floor. Provide two revised plan sheets showing how this will be accomplished. Provide a comprehensive foundation plan showing vents, holdowns, and the retaining wall design called out at the location it will be used on the plan. Provide two copies of plan sheets showing these changes. �� Provide two copies of plan sheets revised to show vehicular barrier. ...lke Revise the rear elevation to show the door leading out from the main level to the c■ ered patio. Provide two copies of plan page. 0 The house should be designed and engineered for the lot on which it will be built. . ' emove all references to verifying the height of retaining walls in field, and provide two copies of sheets with accurate retaining wall heights called out at the locations at which they are necessary. The plan should be designed to meet the 2005 ORSC. Remove any references on all At . to other non - applicable codes. Provide geotechnical verification of the 2000 pound soil bearing value used in the design • f the retaining walls, or provide two copies of a revised design using the allowable soil bearing value of 1500 pounds per square foot. May 1, 2008 Allison May Riverside Homes 1925 N.W. AmberGlen Parkway, Suite 200 Beaverton, OR 97006 Re: Structural Engineering Review Comments on Bella Vista Lots 18 & 28 Riverside Homes Plan #3569- B -03 -OR City of Tigard Building Permit #MST2008 -00026 & MST2008- 00027, CSA Job #003 -4R. The following items are in response to the City of Tigard Structural Engineering Review Comments on Bella Vista Lots 18 & 28, Riverside Homes Plan #3569- B- 03 -OR, City of Tigard Building Permit #MST2008 -00026 & MST2008- 00027, CSA Job #003 -4R. Item 2. Provide two copies of revised engineering that reflect the change in the height of the structure at some points as much as 4.5 ft, as this affects the lateral design calculations. If any changes are made to the shearwalls, provide two copies of plan sheets affected. CSA Response: The lateral analysis originally analyzed the lower floor wall lines as full height walls for the entire house plan. Therefore the lower walls are not affected by the elevation change. The only lower wall lines that are affected by the elevation change are the lower front wall lines C & D since their height now exceeds 9'. Since the entire main floor load of wall line C was conservatively placed into lower wall lines C & D (page 24/57 of calcs), the lower front wall lines C & D also remain unchanged. The shearwalls and holdowns therefore do not change due to the elevation change. Enclosed also is a comparison between the old and new elevation drawings. Item 9. Provide a detail of any cripple walls and designate the locations on the plan. CSA Response: Reference ponywall detail HD5 /S4. Item 13. Provide geotechnical verification of the 2000 psf soil bearing value used in the design of the retaining walls, or provide two copies of a revised design using the allowable soil bearing value of 1500 psf. CSA Response: Enclosed is a geotechnical report #02 -7801 by GeoPacific Engineering, dated 6/15/05, & on page 3 verifying that the 2000psf allowable soil bearing value is adequate. CC, m ,1 Q \kc '.►n Sub . oA. 41 Jer• All other items in the backcheck will be addressed by Magaro Architecture. Sincerely, CSA Consulting Engineers, LLC Chris Blaumer, P.E. Design Engineer C5A Consultnq E nglneers, LLC 2895 Beavercreek Rd. • Oregon City, OR 97045 (503) 228 -3848 FAX (503) 228 -0475 cs CONSUL 17NG� ENGINEERING EXCELLENCE March 17, 2008 I : R r E. Lid 4 4R MAR 2 5 LUU8 7 Z008 Riverside Homes CITY Of rlOA ID 1925 NW Amber Glen Pkwy #200 BUILDING DIVISION Beaverton, OR 97006 Re: Authorization for use of engineering, Plan 3569- 00- B- L- 03 -03 -OR Bella Vista, Lot 18 CSA Job #003 -4R CSA Consulting Engineers authorizes Riverside Homes to use all applicable engineering designs and calculations we have performed for the subject plan in order to obtain permits for the referenced lots. This use is authorized with the following conditions. 1. The plans being submitted have not been modified from the plans for which the engineering was done. 2. The structural codes and design criteria under which the engineering was done is consistent with the codes and criteria currently used by the permitting agency. CSA Consulting Engineers can take no responsibility to insure that these conditions are met unless we review the specific plan submitted for permits and all applicable engineering. If we can be of further help please do not hesitate to call. Cordially, PRO CSA Consulting Engineers, LLC '' . �� � e rr . 4, 1 ®;, ,. IN Dwight D. Mason, P.E. e 12 2 13 ° � '� Structural Manager colfr i■AN L 12.3 - 2895 Beavercreek Rd. • Oregon City, OR 97045 (503) 228 -3848 FAX (503) 228 -0475