Correspondence April 4, 2008
Gertz Construction Company Inc.
19200 SW 46 Ave.
Tualatin OR, 97062 -8770
RE: Lot # 4
Project Information
Building Permit: MST2008 -00018 Construction Type: \ B
•
Address: 13836 SW Halcyon Terrace Occupancy Type: R -3
Area: 3048 Sq. Ft. Stories: 2
The plan review was performed under the 2005 Oregon Residential Specialty Code. The review
of the submitted plans will be completed when the following information is provided.
1. Please revise plans and or truss details - K- girder is designed as a two point bearing
truss , reactions of 7997 #(left) and 6305 #(right). Plans appear to have been detailed
with a three point bearing truss and a majority of the loading transferring down to
beam M -9 to M -10, M -8. Two copies are needed.
2. In addition to said above, please re- evaluate footings and beams K- girder transfers
to, and submit two revisions if necessary.
3. When responding, provide an itemized letter stating in what way each issue has been
addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
Brandon Shaw
Plans Examiner
BrandonS@tigard-or.gov
Phone: 503.718.2425
Fax: 503.624.3681
Brandon Shaw
From: Ken Gertz [Ken @Gertzco.comj
Sent: Wednesday, April 09, 2008 10:58 AM
To: Brandon Shaw
Subject: Re: MST 2008 00018 - Lot 4 Edgewood
Attachments: k GIRD 3PNT BEARING.pdf
Brandon,
Thanks for the update. It came in the mail yesterday, as luck would have it.
I have elected to keep the 3 point truss so we don't have to change anything else on the
plan.
I assume you got the Tree plan and all the new Plot Plans that match, as well as all the
other stuff you need for the other plans. You should be close to being able to issue permits
on all but lot 5, of which I still owe the corrections.
I hope to start Lots 3 and 2 and one other next week if that works with you.
If there is anything else you need please let me know, and I will get it handled for you.
Thanks
Ken Gertz
Brandon Shaw wrote:
> A plan review letter was sent out 4Apri108 by mail, but here's a copy.
> Brandon Shaw
> Plans Examiner
> Tigard OR, 97223
> 503 - 718 -2425
> Original Message
> From: Ken Gertz [mailto:Ken @Gertzco.com]
> Sent: Tuesday, April 08, 2008 8:28 AM
> To: Brandon Shaw
> Subject: MST 2008 00018
> Brandon,
> I haven't seen a correction list for Lot 4 Gertz Homes at Edgewood.
> Is it all cool with no corrections other than the plot plan?
> Ken Gertz
1
Brandon Shaw
From: jeff [Jeff @markstewart.com]
Sent: Wednesday, April 09, 2008 1:46 PM
To: Brandon Shaw
Cc: 'Ken Gertz'
Subject: MST2008 -00018
Attachments: m -9 beam calc.pdf; cardinal lot 4 revis beam under girder.pdf
Hello Brandon,
Here's a new m -9 beam calc that reflects the truss company's load from the new 3point girder the
truss company designed. The new load is less than what was on the original calc; therefore the
beam got smaller (5 1/8 "X12" glb) & is flush. Could please redline that change? Ken Gertz will
provide the new truss drawings. Please let me know if there's anything else you need. Thanks.
Jeff Gerherg