Plans Fan Powered Terminal Unit Schedule Size CFM Static Pressure NC Levels Fan Electric Heat Coil ,Tag Model Unit Inlet Outlet Max Min Inlet Down Min Rad. Dis sFM ESP , Hn CFM KW , EAT LAT Volts/Ph. Steps VAV -02 DTQS 06 16 16.5x14.5 2000 500 1.00 0.25 0.10 42 29 2.000 0.25 0.75 2,000 6.0 . 66 76 277/1 1 VAV -05 .DTQS 06 16 16.5x14.5 2000 700 1.00 0.25 0.10 42 29 2.000 0.25 0.75 2,000 7.5 _ 65 77 277/1 1 Notes: 1. Room NC level shown includes attenuation transfer functions obtained from tables in ARI Standard 885. 2. Sound data shall be obtained from tests conducted in accordance with ARI Standard 880 -98. 3. Selections based upon Titus as Manufacturer. OffilmiNeph 4. Dimensions are for base product only. Check submittal drawings for exact dimensions. 5 . Size units are given in inches, flow units are cubic feet per minute, pressure units are inches of water, and temperature units are degrees fahrenheit. trt C S G 0 ^{� D O rn 7 Z Printed: 0/11/2005 : 8:27:18AM Version : Page 1 TITUS TEAMS Fan Powered Terminal Unit Selection Project: Tag: VAV -02 Project Location: Altitude: 1.0 Feet File: LEE LOEBE.tw User. Room: Selection Size Primary CFM Heating Static Max NC Levels Quantity Model Unit Inlet Outlet Max. Min. CFM Inlet Down Min. Rad. Disch. 1 DTQS 06 16 16.5x14.5 2,000 500 2,000 1.00 0.25 0.10 42 29 Notes: 1. For parallel boxes, inlet static pressure includes downstream pressure drop. 2. See below for PWL calculations used to obtain Max NC rating. 3. Outlet size is approximate and does not include coil dimensions. See submittal drawings for exact dimensions. E lectric Heating Coil Performance Fan Performance KW Max KW CFM EAT BoxIAT Volts / Ph. Steps CFM DnstrmESP Hp 6.0 11.5 2,000 66.3 75.7 277 /1 1 2,000 0.25 0.75 Other Information Accessories Fan Curve Max. Prim. CFM : 2,780 Lining: SteriLoc Design CFM: 2,000 Heat Coil: Electric Safety Factor. 28% Attenuator: No Unit LxWxH: 47 x 48 x 21 in. Filter. Yes Controls: DDC Motor: Standard Selected : True Acoustic Summary Radiated Sound PWL Discharge Sound PWL Sound Description 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC Fan +Primary Sound 76 70 67 69 62 50 77 69 69 67 66 64 Fan Only Sound 72 70 67 69 62 50 74 67 67 65 64 64 * Total Attenuation Per. ARI 885 18 19 20 26 31 36 29 30 41 51 52 39 * Room Sound Level 58 51 47 43 31 14 42 48 39 28 16 14 25 29 Notes: 1. Room sound levels shown include attenuation based on transfer function file: Catalog 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -98. 3. Sound power levels are in decibels, re 10 watts. 4. Dash ( -) in space indicates sound and NC value is less than 10. 5. Dimensions are for base product only. Check submittal drawings for exact dimensions . 6. Size units are given in inches, flow units are cubic feet per minute, pressure units are inches of water, and temperature units are degrees fahrenheit. The results of this program are only an aid to the designer, and are not a substitute for professional design services. Titus accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. — Printed: 10/112005 : 8:26:33AM Version: TITUS TEAMS Fan Powered Terminal Unit Selection Project: Tag: VAV -05 Project Location: Altitude: 1.0 Feet File: LEE LOEBE.tw User: Room: Selection Size Primary CFM Heating Static Max NC Levels Quantity Model Unit Inlet Outlet Max. Min. CFM Inlet Down Min. Rad. Disch. 1 DTQS 06 16 16.5x14.5 2,000 700 2,000 1.00 0.25 0.10 42 29 Notes: 1. For parallel boxes. inlet static pressure includes downstream pressure drop. 2. See below for PWL calculations used to obtain Max NC rating. 3. Outlet size is approximate and does not include coil dimensions. See submittal drawings for exact dimensions. Electric Heating Coil Performance Fan Performance KW Max KW CFM EAT BoxLAT Volts / Ph. Steps CFM DnstrmESP HP 7.5 11.5 2,000 64.8 76.6 277/1 1 2,000 0.25 0.75 Other Information Accessories Fan Curve Max. Prim. CFM : 2,780 Lining: SteriLoc Design CFM: 2,000 Heat Coil: Electric Safety Factor. 28% Attenuator: N/A Unit LxWxH: 47 x 48 x 21 in. Filter: Yes Controls: DDC Motor: Standard Selected : True Acoustic Summary Radiated Sound PWL Discharge Sound PWL Sound Description 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC Fan +Primary Sound 76 70 67 69 62 50 77 69 69 67 66 64 Fan Only Sound 72 70 67 69 62 50 • 74 67 67 65 64 64 Total Attenuation Per. ARI 885 18 19 20 26 31 36 29 30 41 51 52 39 Room Sound Level 58 51 47 43 31 14 42 48 39 28 16 14 25 29 Notes: 1. Room sound levels shown include attenuation based on transfer function file: Catalog 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -98. 3. Sound power levels are in decibels, re 10^ -12 watts. 4. Dash ( -) in space indicates sound and NC value is less than 10. 5. Dimensions are for base product only. Check submittal drawings for exact dimensions . 6. Size units are given in inches, flow units are cubic feet per minute, pressure units are inches of water, and temperature units are degrees fahrenheit. The results of this program are only an aid to the designer, and are not a substitute for professional design services. Titus accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Printed: 10/112005 : 8:27:06AM Version: ' Tit Submittal DTQS -1.0 11 -19 -04 ti -F . The Leader In Air Management DTQS Fan Powered Terminal, Series Flow Direct Digital Control, Pressure Independent N + 2� 1/4 K— � -J r-12 3 3/8 ilill �TT, 0 ,. A i r, 1 0„ _ D }; u I . Y Y II II II it u ,11_(1 u u is u u u - u u 1111 - I o00 I n.n f I - , Primary Air Inlet » ;: r- -- - -ri:� w with Multipoint ; ; ; :1:;: Center Averaging F II II I • Sensor 11 111 c OD L L ii ii 1 �� WI Induced / n n a ■ 41 1 + II Air Inlet -_' 2 111111....111111....1.1 I 2 l 114 `H Left hand unit, top view shown. All dimensions are in inches. • Right hand units are built as a mirror image. Inlets, discharge, and control enclosure are opposite of the drawing above. Unit Size Inlet Size A B C D E F G H, J K ^ 'L. N , :',.. - W: , '• , Filter Size 6 6 5 7 /e 2 7 /8 8 6 7 7 /3 2 7 /e 2, 3 10 7 9 4 7 /3 12 8 11 7 /3 4 7 /3 8 6 8 3 /15 13 7 7/e 14 1 /2 14 3'/2 17 11 4 40 7 /e 2 7/e 36 1/e 19 x 17 10 7 9 7 /e 4 7 /e 4 12 8 11% 4 7 /e 14 10 13 7 /3 6 7 /8 10 . 7 9 7 /8 4 7 /3 12 8 11 7 / e 4 7 /8 5 14 10 13 7 /3 6 7 /e 16 11 15 7 /3 6 7 /e 7 r 2 ' n z + 1 ' 7 4 7 /a 48 27 x 20 12 8 10 /, 21 11 /e 17 ! 16 / 9 / 20 /e 14 != 2 /Z 46 h O 14 10 13 7 /3 6 7 1e 16 11 15 7 / 3 6 7 1e 14 10 13 7 /8 6 7 6, 7 16 11 15 7 / 3 6 7 /e Motor Amperage Ratings Accessories (Optional) Unit Motor 120/1/60 208/240/1/60 277/1/60 Check [' if provided. Size hp FLA FLA FLA Induced Air Filter, 1" thick, disposable 2 1 /3 4.0 t8 1.3 construction type. 3 1 / 4 7.0 3.0 2.4 0 Fan disconnect switch (not available on units 4 'h 9.8 4.1 2.9 with optional electric coils.) _ 5 I h 10.0 4.3 3.3 6 3 /4 13.4 7.2 5.4 ❑ Fibre Free Liner ❑ UltraLoc Liner 7 1 N/A 9.0 6.5 SteriLoc Uner ❑ W Fiberglass Liner FLA = Full Load Amperage, as tested in accordance with UL 1995 Hanger Brackets ❑ 1" EnviroLoc Uner All fan motors are single phase, same voltage as electric coil (when ❑ an unit fusing supplied), with exception that 277 V motors are used with 480V, 3 ❑ Cam Latch for Access Door phase coils (4 wire wye). ❑ V J • DTQS -2.0 11 -19 -04 Accessories (Optional) ❑ Hot Water Coil Section . 0 0 0.0 o • 1/Y copper tubes . • Aluminum ripple fins, 10 per inch — T i - 4 Tr?�' 7 • Connections: Male solder, 5/8" for • ; 1 n both 1-row and 2 -row. Left hand or , } u u . • right hand connections. i i iii • Galvanized steel casing - " ' 4 ' ; �; 1 • Flanged duct connection. I _ • Coil is installed on discharge of I i i i - - - 4 unit. 1.n i ' • i rt r T. • 1 , 1 I ❑1 Row II • I II ❑ 2Row . • iu I J� i R • I i n I - 7 d j I II I d 1 11 , 1•1 A , n , II u t - r - ,_11 T, u U 1 "Typ. 9 M S Unit Size M (1 row) M (2 row) R S 2, 3, 4 1 1 1 / 4 17 15 5, 6, 7 1 1 '1 25 17 1 / 2 R and S are inside dimensions. Electric Coil Section ❑ Optional SCR Controlled Electric Heater ❑ Optional Lynergy Controlled Electric Heater Stand • Single side access to low voltage, high voltage, and electric heater controls. t • Automatic reset thermal cutouts, one o 0 0 ll 6 1 /4 _ o • 0 o per element _ } - g ir 7r �- • 4 • Single point electrical connection for • �TT I. „ ∎ � �� entire unit , }. u $ Heater Rack . • Positive pressure flow switch II Access Cover • • Flanged duct connection ' - r11ys o a ; II II • Cog is installed at discharge of unit. • Transformer • =_- � 1"Typ. II Options 0.0 l ,I.� & I� r - I Fuse Block " " u'u 0. Disconnect switch, door ". ;; ; ; : R interlock type 1 El Manual reset cutout 11 ii d , u u 0 0 ❑ Dust tight construction " " u ; ❑ Mercury contactors r u �- i Supply Voltage LI ❑ 208V, 1 ph, 60Hz Pik 4 S— T ❑ 240V, 1 ph, 60Hz ❑ 277V, 1 ph, 60Hz Unit Size U R S T ❑ 208V, 3 ph, 60Hz ❑ 480V, 3 ph, 60Hz (4 wire wye only) 2, 3, 4 3'/ 14 11 2' /a 5, 6, 7 9'/ 16'1 14'/2 3'/e R and S are inside dimensions.