Permit ✓, -,,- CITY O F TIGARD GARD ELECTRICAL PERMIT
PERMIT #: ELC2006 -00157
�i DEVELOPMENT SERVICES DATE ISSUED: 2/27/2006
13125 SW Hall Blvd., Tigard, OR 97223 503-639- 4171 PARCEL: 2S102DA -00200
SITE ADDRESS: 08720 SW BURNHAM ST ZONING: CBD
SUBDIVISION: LOT : JURISDICTION: TIG
Project Description: Install generator. Job No. 63670
RESIDENTIAL UNIT TEMP SRVC /FEEDERS MISCELLANEOUS
1000 SF OR LESS: 0 - 200 amp: PUMP /IRRIGATION:
EACH ADD'L 500SF: 201 - 400 amp: SIGN /OUT LINE LTG:
LIMITED ENERGY: 401 - 600 amp: SIGNAL/PANEL:
MANF HM/ SVC/ FDR: 601 +amps - 1000 volts: MINOR LABEL (10):
SERVICE /FEEDER BRANCH CIRCUITS ADD'L INSPECTIONS
0 - 200 amp: W /SERVICE OR FEEDER: 50 PER INSPECTION:
201 - 400 amp: 3 1st W/O SRVC OR FDR: PER HOUR:
401 - 600 amp: EA ADD'L BRNCH CIRC: IN PLANT:
601 - 1000 amp: PLAN REVIEW SECTION
1000+ amp /volt: > =4 RES UNITS: > 600 VOLT NOMINAL:
Reconnect only: SVC /FDR >= 225 AMPS: CLASS AREA/SPEC OCC:
Owner: Contractor:
CITY OF TIGARD FRAHLER ELECTRIC CO
13125 SW HALL 11860 SW GREEN BURG RD
TIGARD, OR 97223 TIGARD, OR 97223
Phone: 503 - 639 -4171 Contact #: FAX 503 - 639 -4673
PRI 503 - 639 -4627
FEES
Description Date Amount Reg #: LIC 37410
[ELPRMT] ELC Permit 2/27/2006 $653.05 SUP 18165
[TAX] 8% State Surcharge 2/27/2006 $52.24 ELE 34 -13C
Total $705.29 REQUIRED ITEMS AND REPORTS
This Permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other applicable laws.
All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is
suspended for more than 180 days. ATTENTION: Oregon law requires you to follow rules adopted by the Oregon Utility Notification Center. Those
rules are fot in OA -0 -0010 through OAR 952 - 001 -0100. You may obtain copies of or direct questions To OUNC at
503 -246 699 or 1 -800 2 -2 4. _ --
Issue By: G� Q�JV�_ Permittee Sign 'ture: ,,A��� 0 ' `. ( a r ^
— OWNER INSTALLATION ONLY
The installation is being made on property I own which is not intended for sale, lease, or rent.
OWNER'S SIGNATURE: DATE:
..„--, CONTRACTOR INSTALLATION ONLY
SIGNATURE OF SUPR. ELECT: ,4-! /' ,► *'t ' .(U DATE:
{
LICENSE NO: / K/l
Call 503 - 639 -4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
•
Elec'tricafi Permit Application vE® ' - .,- F ..fOR OI�rICL USF ON
City of Tigard D Received ' eB Pemut 41 i •
EL 0 -00157
13125 SW Hall Blvd.. Tigard, OR 97223 p Plan Review
Phone: 503.639.4171 Fax: 503.598.19(QAY 2 5 2006 °� DateBy� Other Pe mit:
Inspection Line: 503.639.4175 4"11411 i " D ate •
ReadyBy: Juris: El See Page 2 for
Internet: www. ci.tigard.or.us CITY OF TIGARD Notified/Method: Supplemental Information
B ILDINC DIVISION . _
R
-_ . ,PL•AN °, EVIEW � �,,- -
.
❑ New construction ® Addition/alteration/replacement Please check all that apply: •
❑ Demolition ❑Other: ❑ Service over 225 amps,. comm'l 0 Hazardous location
❑ Service over 320 amps — rating ❑ Buildng over 10,000 sq. IL,
CATEGORY of " CONSTRUCT %ON : of 1 -and 2- family dwellings 4 or more new residential
❑ 1- and 2- family dwelling ® Commercial/industrial ❑ Accessory building ID System over 600 volts nominal units in one structure
['Building over three stories ['Feeders, 400 amps or more
❑ Multi- family ❑ Master builder ❑ Other:
❑ Occupant load ov ['Manufactured structures or
a 99 persons
- , ' , ' .: ;JOB SITE INFORMATION AND LOCATION - - - ❑Egress/lighting RV park
❑Health -care facility ❑Other:
Job no.: 63670 Job site address: 8720 SW BURNHAM Submit 2 sets ofplans with any of the above.
City /State/ZIP: TIGARD, OR 97223 The above are not applicable to temporary construction service.
Suite/bldg. /apt. no.: Project name: CITY OF TIGARD /IT 'BLDG D esaip tMn " `FEE" "=SCH ;. FM ;, i .. Tot to
Cross street/directions to job site: New residential single- or multi- family dwelling unit.
Includes attached garage.
1,000 sq. fl. or less 145.15 4
Subdivision: Lot no.: Ea. add'l 500 sq. ft. or portion 33.40 1
Limited energy, residential 75.00 2
Tax map/parcel no.:
Limited energy, non - residential 75.00 2 • .: : ::` DESCRIPTION
y . � „ - ':OF.'1WORK ,. •
^,- ... Each manufactured or modular
dwelling, service and/or feeder 90.90 2
INSTALL GENERATOR PLAN REVIEW Services or feeders installation, alteration, and/or relocation
200 amps or less 80.30 2
• v MI `PROPERTY DOWNER . - -- ` ` ' - � ® ':TENANT > , - _ 201 amps to 400 amps 106 85
401 amps to 600 amps 160.60 2
Name: 601 amps to 1,000 amps 240.60 2
Address:_ Over 1,000 amps or volts 454.65 2
Reconnect only 66.85 2
City /State/ZIP: Temporary services or feeders installation, alteration, and/or
relocation
Phone: ( ) Fax: ( ) s
200 amps or less 66.85 1
Owner installation: This installation is being made on property that I own which is not 201 amps to 400 amps 100.30 2
intended for sale, lease, rent, or exchange, according to ORS 447, 449, 670, and 701. 401 amps to 600 amps 133.75 2
Owner signature: Date: Branch circuits — new, alteration, or extension, per panel
',1 ' ' • - = ' -' i O - ::CONTACT - PERSON • A Fee for brands circuits with
service or feeder fee, each 6.65 2
Business name: FRAHLER ELECTRIC COMPANY branch circuit
B. Fee for brands circuits
Contact name: 11860 SW GREENBURG ROAD without service or feeder fee,
46.85 2
each branch circuit
Address: TIGARD, OR 97223 Each add'l branch circuit 6.65 2
City /State/ZIP: Miscellaneous (service or feeder not included)
Pump or irrigation circle 53.40 2
Phone: ( ) Fax: : ( ) 53.40 2
Sign or outline lighting
E -mail: Signal circuit(s) or limited -
''.j ., - - ' :CONTRACTOR 11'''' ' ` - `` -. ..- . energy panel, alteration, or
extension. Des cribe: Page 2 2
Business name: FRAHLER ELECTRIC COMPANY
Address: 11860 SW GREENBURG ROAD Each additional inspection over allowable in any of the above
Per inspection 62.50
City /State/ZIP: TIGARD, OR 97223 Investigation per hour (1 hr min) 62.50
Phone: ( 503) 639 -4627 Fax: ( 503 639 -4673 Industrial plant per hour 73.75
EL••ECTRICAI: • PERMIT 'FEES"
CCB Lic.: 37410 Electrical Lic.: 34 -13C Suprv. Lic.: 18165 Subtotal
Suprv. Electrician signature, recd: y �,Gii Plan review (25% of permit fee) 163.26
Print name: R. W. FRAHLER � Date: 05/23/06 State surcharge (8% of permit fee)
TOTAL PERMIT FEE 163.26
Authorized signature: This permit application expires If a permit is not obtained within 180
days after it has been accepted as complete
Print name: Date: ° Fee methodology set by Tri- County Building Industry SaMoe Board
" Number of inspections oar oennit allowed.
CITY OF TIGARD ELC2006-00167
BUILDING DIVISION PERMIT #: 2/27/2006
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639-4171 4,0
Inspection Requests (24 Hrs.): (503) 639-4175 —ill- 11.
7/21/2006 7:01AM 78
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
00720 SW BURNHAM ST
SITE ADDRESS: CLASS OF WORK:
SUBDIVISION: CITY OF TIGARD LOT #: TYPE OF USE:
PROJECT NAME: Niche, IT department. Install generator. Job No. 63670
DESCRIPTION:
CITY OF TIGARD,
OWNER: FRAHLER ELECTRIC CO PHONE #: 603-63627
CONTRACTOR: PHONE #:
7/21/2006
Inspection Request Scheduled For: Date: Pour Time:
Cof:JA# I rmsgtfaifiapeription 99griTd qgV§t090 Mes
Corrections/Comments/Instructions: nr\
v
R (AO. % vp Rnta s fob -
6-0,43 Neis
-4 PASS n PARTIAL APPROVAL 0 CANCEL n NO ACCESS
' 111 IL CALL FOR INSPECTION ADDITIONAL FEES ASSESSED
—
Inspector: C.,--kt ws6 Date: 11 Phone #: (503) 718- 214
t ,
Halton Power Start -up
Customer: CITY OF TIGARD, IT DEPT. Work order #0550698 Hour 2
Location:8720 SW BURNHAM ST. Serial # JNPS02127 ,Mode D100P1
Contact: ROBERT MURCHISON Engine Rating 100KW
Phone #:503- 639 -4171 IDate 1 7/13/06 Generator Rating 100KW
Inspection OK Not OK OK Not OK
Lube oil level X TransfeP switch
Lube oil leaks X Manual transfer /check debris X
Crankcase breathers open X Verify Phase Rotation X
Coolant level & test protection X Verify Volt. Match gen /utility X
Coolant leaks X Program /Cal Trans.Switch X
Air cleaners & piping X Perform Transfer Test X
Air inlet restriction X Engine Panel /Controls X
Exhaust silencer & piping X Breaker function (Shunt Trip) N/A
Exhaust back press. (max 27 1120) N/A Remote Start/Stop X
Fuel tank & piping X Remote annunciate operation X
Fuel pressure X Check safety functions X
Mounting bolts X Engine E -STOP X
Isolators adjustment X High Water Temp. X
Alignment (3500 required) N/A Low Oil Pressure X
Vibration Test (If Required) N/A Engine Overspeed X
Governor linkage (mechanical) X _Adjust dynamics and load control X
Engine parameters (printout) N/A Engine load test X
ECMP+ (cooldown timer) X Special Test (Block Loading) N/A
Battery Charger X cke water heaters X
Ja t w e�
�,�a,:.;s & e4,,i,a.�i:?r'�. -� >.sr ,•. ,a+.:;.,, .. �;��� �� {.�_a'^;�*Frt�a�N, sad'; '� �o �
07 �F!dt��.5��"=.. _..:Ct7 a ttOn .. _ f ' t'J' 6 � x.., ' ' a q „R itNi tt�T @ fix °.: 4 x 1+
Oil filters 2 0 , , ,z j p` ,, . ,
Oil brand & rating 15-40 Gallons
Primary fuel filters 1 i .- ' a -,z,
Secondary fuel filters 1;°' + e
Air filters 2 , ; rr. �. . "; 7.
Belts fan 2 ;, -a� : ,,is,p, :�„ : 4
Belts alternator ` :z.„ ,
Coolant type ELC Gallons U . -_''� A
Batteries 1 ' .
... , •.•�.• � °ru.� rte•. .,;.r.�a.,.ka��. , .�.; > "K�,"� .,::�
•, '! ="f �.. ,� -Y.. >o2 _A..-,3 C�., a:.pi ,.p.�. a..;.Y;i;.c1:d t p•.t1vT.Vitl.. S - ¢T
4"`P4.`x^ -'> .. �3.. : ^,P3� §7�:. 't^ s �:'.. ?M, �ait�,a�.:d.:� .
r.?3.. ��'^�e'��i.`:c`�� .. _ . _ � '. &� '���:• ... ��..�x,r5:;.�_ ._ ._..,._.. asa:;:'a........ _���' - �.,:.�.. r�.�` = �._ � •,. r
Location of load bank for testing: OUTSIDE
Load bank cable quantity, size & length: SUITE CASE
Any special requirement to service this location: CAN PULL UP TO.
Comments: MISSING 120 OHM RESISTOR FOR ANNUNCIATOR, HAD AC C. BRING ONE TO
SITE. PLEXY GLASS WINDOW WAS PARTIALLY POPPED OUT, SPENT TIME RE- INSTALLING.
Technician Signature Date Customer Signature Date
ADAM DINGMAN 7/13/06
HALTON DIESEL GENERATOR SET TEST REPORT
Customer & Location: CITY OF TIGARD IT BUILD
Engine Generator
Manufacturer: CAT Manufacturer: CAT
Model: D100P1 Rating:100KW Model: 2330/1500 Rating: 100KW
Serial No: JNPS02127 Ar: Serial NoYB51047 *U855544 Ar:
Package Serial: Test Date: 7/13/06 W /O: 0550698 Hours: 2
Generator En ' ine
Volts Amps L.O. L.O. Fuel Water AMB
Time % K.W. A BC A B C HZ PF Temp Press Press Temp Temp
12:00 100 100 240 240 240 244 244 244 60 1.0 190 88 OK 182 70
12:15 100 100 240 240 240 244 244 244 60 1.0 190 88 OK 182 70
12:30 100 100 240 240 240 244 244 244 60 1.0 190 88 OK 182 70
12:45 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
1:00 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
1:15 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
1:30 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
1:45 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
2:00 100 100 240 240 240 244 244 244 60 1.0 200 88 OK 183 70
Remarks: START UP.
Generator Main Breaker Transfer Switch Additional Misc. Info
Model: ABBS5N Model: ZENITH ZTGD/ 400AMP
Rating: 400AMP/ SET TO .80 Serial: TSB01187
Tested by: Adam Dingman Certified, True and Accurate this date: Witnessed and Accepted by:
7/13/06
c:lmsoficelfieldsrvlgenrator.doc 7/14/2006 SM
007,
, x3
1 2 A: Frequency
63.5D 124.0 � �, =r -r - , �_, , _.., ... r..r r ,. .. - ' — Datablock
Name =A: Frequency A: AC
i _ Date = 7/13/2006 7/13/2006
6100 123.0 ( ` Time = 2:34:20 PM 2:34:20 PM
- : Y Scale = 500 mHz /Div 1 V /Div
- • YAt50%= 61.50 Hz 120.0V
62.50 122.0 --- -� _.- _..-- .,-- .- -.- -1- .. -_ - -. -- - .. - - - -- - -- _.- -. - - - -- ▪ X Scale = 30 s /Div 30 s /Div
- - - X At 0% = 00:00:00 00:00:00
62.00 121.0 • : X Size = 62 (62) 62 (62)
_ Maximum = 62.79 H2 120.0V
. ' I - Minimum = 60.37 Hz 119.5V
61.50 Hz 120.0V _ 4 I. I ?; ' i -4 1 1 1 4 1 4 1 1: 1 1 4 4 1 1 ` 4 7, 4 4 4: 1 4 1 1 1 1 1' 1 Cursor Values
X1: 00:00:15
1 X 2 : 00:00:46
61.00 119.0 d X : 00:0a31
Y1: 60.51 Hz
` - Y2: 61.41 Hz
60.50 110.0 _ - - --- -- - _._
. r - - — _ -- _--- - -_._. dY: 0.90 Hz
60.00 117.0 •
I ) j
59 .50 116.0 - u-�-l. + ' l l...- .1..Ll.1- J1 -L1... - 1..:.. .....l...1.- l.J.......L -L..l- _.LI .7,..1._- LI- LL......l..LI_l-
00:00:00 30 s /Div
" ..
00 7v x
1 2 A: Frequency
65.00 140.0 - TiT • tT "^lT l 7 T ,- l i IT' Tt l l f r� -� • T 1 TTr ^T'L Tr'• Datablock
Name =A Frequency A: AC
I Date = 7/1 3/2006 7/13/2006
64.00 135.0 - f Time = 2:36:01 PM 2:36:01 PM
Y Scale = 1 Hz /Div 5 V /Div
63.00 130.0 - _ YAt50% =61.00 Hz 120.0V
• -� - � —� - --
_ X Scale = 30 s /Div 30 s /Div
X At 0 = 00 00 00 00:00:00
62.00 125.0 - X Size = 63 (63) 63 [63]
- �}(' l .. Maximum = 6289 Hz 135.7 V
I = Minimum = 58.13 Hz 107.1 V
61.00Hz 120.0V 'Zi` ~ i 1 1, I I i 4 1 1 1 1 ' 1 1 1 1 1 I; 1 ; I: 1 1 I t '. 1 1 1: - Cursor Values
r xi: 00:00:16
X 2 : 00:00:47
60.00 115.0 T _ d X : 00:00:31
ii 1'. \ - Y 1 : 59.31 Hz
- - _ ` - r = Y 2 : 59.70 Hz
59.00 110.0 - � ' - - - - -'. _..___ - - -, - -- -- - -- _._ _. .._.. d Y : 0.39 Hz
_
58.00 105.0
00:00:00 30 t/Div
{
CITY OF TIGARD
BUILDING DIVISION PERMIT #: ELC2006- 00157
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 2
Phone: (503) 639 -4171 , % iv ✓d11�u�i��I 111
Inspection Requests (24 Hrs.): (503) 639 -4175 ...! `__..
INSPECTION WORKSHEET FOR DATE: 7/18/2006 TIME: 7:03AM PAGE: 39
SITE ADDRESS: 08720 SW BURNHAM ST CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME: CITY OF TIGARD
DESCRIPTION: Niche, IT department. Install generator. Job No. 63670
OWNER: CITY OF TIGARD, PHONE #:
CONTRACTOR: FRAHLER ELECTRIC CO PHONE #: 503 - 639 -462i
Inspection Request Scheduled For: Date: 7/18/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
199 Electrical final 033236 -01 603- 201 -2626 N
0 33 1 \2 -O I �� Q4 '1 k Z I I O z
Corrections /Comments /Instructions: U
PASS APARTIAL APPROVAL ❑ CANCEL n NO ACCESS
n FAIL n CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: G 1 .Ck v� LE Date: Phone #: (503) 718- 2 I i /V
. ,
CITY OF TIGARD , .. . .
BUILDING DIVISION PERMIT #: ELC2006-00157
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 2127/2006
Phone: (503) 639-4171 Alk
,. 7tfivitiil-•
Inspection Requests (24 Hrs.): (503) 639-4175 .„_.3.11 IL.
INSPECTION WORKSHEET FOR DATE: 6/30/2006 TIME: 7:01AM PAGE: 55
SITE ADDRESS: 08720 SW BURNHAM ST CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME: CITY OF TIGARD
DESCRIPTION: Niche, IT department. Install generator. Job No. 63G70
CITY OF TIGARD,
OWNER: PHONE #:
CONTRACTOR:
FRAHLER ELECTRIC CO PHONE #: 503-639-4627
Inspection Request Scheduled For: Date: 6/30/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
1'15 Electrical service 032492-01 503-639-4627 N
Corrections/Comments/Instructions:
IA PS R .NYE- - b R.00.)11 0 0
_• re ,-. L i .: ., 1 s Ili — C - 4--- t. k -•
P‘O■P'N
C-0 9 . (0.2-21 •
I PASS 0 PARTIAL APPROVAL D CANCEL El NO ACCESS
N FAIL CALL FOR INSPECTION n ADDITIONAL FEES ASSESSED
Inspector: .---0 \k/Va N 061 L 0 Phone #: (503) 718- 2q417 ,
r --.--
,
CITY OF TIGARD
I BUILDING DIVISION .• A PERMIT #: ELC2006-00 IP
I 13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 2127/2006
Phone: (503) 639-4171 , , 41 " 11° , Olt
Inspection Requests (24 Hrs.): (503) 639-4175 ,,,,,...to --a
INSPECTION WORKSHEET FOR DATE: 5/19/2006 TIME: 7:01AM PAGE: 43
SITE ADDRESS: 00720 SW BURNHAlvi ST CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME: CITY OF TIGARD
DESCRIPTION: Niche, IT department Install generator. Job No, 0670
OWNER: CITY OF TIGARD, PHONE #:
CONTRACTOR: FRAHLER ELECTRIC CO PHONE #: 503-639-4627
Inspection Request Scheduled For: Date: 5/19/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
125 Wall cover 030188-02 503-639-4627 Y
Corrections /Comments/ Instructions:
0 ? 20.) ■ p p■wz,s, PLh1.D kvifft)1/43 Fedi
E t\) Tt (kG fes) .
0 V- C.zsMI GACS - So .51 Vt SiVe
- .
--.._.______
PASS X PARTIAL APPROVAL 0 CANCEL - pi NO ACCESS
FAIL El CALL FOR INSPECTION fl ADDITIONAL FEES ASSESSED
Inspector: C-T 1\9) N0e) LE ---- Date: 5-- 19i0b Phone #: (503) 718- 214,
CITY OF TIGARD ..„
\?. . . 1. .
BUILDING DIVISION PERMIT #: ELC2006-00167
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 7J27/200$
Phone: (503) 639-4171 . . ' Ac
. 4, 4 01 1 1 i 1 0iP
Inspection Requests (24 Hrs.): (503) 639-4175 1j, 67
,,,,,,.. -....
INSPECTION WORKSHEET FOR DATE: 5/1912006 TIME: 7:01,01 PAGE: 44
SITE ADDRESS: 08720 SW BURNHAIVI ST CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME: CITY OF TIGARD
DESCRIPTION: Niche, IT department. Install generator. Job No. 63670
OWNER: CITY OF TIGARD, PHONE #:
CONTRACTOR: FRAHLER ELECTRIC CO PHONE #: 503-639-4627
Inspection Request Scheduled For: Date: 511912006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
105 Underground/slab cover 030188-01 603-639.4527 Y
,
Corrections/Comments/Instructions:
(A
creoess . 0.16 I:No.1
ASS I PARTIAL APPROVAL fl CANCEL n NO ACCESS
I I FAIL I I CALL FOR INSPECTION fl ADDITIONAL FEES ASSESSED
Inspector: GI\ ( 0 (.% CE Date: 51 I c t 0 6 Phone #: (503) 718-