Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 August 22, 2007 • • RE: THOMASVILLE TIGARD Project Information Building Permit: BUP2007 -00405 Construction Type: VB Address: 6650 SW Bonita Dr. Occupancy Type: B Area: 16931 Sq. Ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. 1) All improvements made to the building shall be inspected prior to covering. 2) Make approved set of plans available for all inspections. FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key- operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. (Sec. 1008.1.8.3) All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. (Sec. 1008.1.8) Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. (Sec. 1011.1) Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. (Sec. 1006.3) FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. (Sec. 1006.2) Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 Portable fire extinguishers shall be installed in new and existing Group A, B, E, F, H, I, M, R -1, R -2, R -4, and S occupancies. (OFC Sec. 906) Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf shall be conspicuously posted by the owner in that part of each story in which they apply, using durable metal signs, and it shall be unlawful to remove or deface such notices. The occupant of the building shall be responsible for keeping the actual load below the allowable limits. (1603.3 OSSC) American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy (109.1 OSSC) Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. _'e •etfull tea, -! �, I an Nelson Senior Plans Examiner City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 August 16, 2007 'I • • RE: THOMASVILLE FURNITURE T I GARD Project Information Building Permit: BUP2007 -00405 Construction Type: VB Address: 6650 SW Bonita Dr. Occupancy Type: M Area: 16931 Sq. Ft. Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. The following conditions will be required prior to issuance; • Table 29 -A in The 2007 Oregon Structural Building Code requires two restrooms for both male and female with 13,961 Sq. Ft. of mercantile area. (200 Sq. Ft. per occupant) American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Respectfull , /16, Or iiit4 Nelson .Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 ' S PERMITS TODAY i x Vizi) August 3, 2007 AUG O Attention Building Permit Technicians J��' ?007 CITY OF TIGARD BUILDING DIVISION a p I Ur j 1 r a 13125 SW Hall Blvd. r , Tigard, OR 97223 V s i�� ? Re: Plan submittal for Tenant Improvement of retail store in an existing space "THOMASVILLE FURNITURE" located at 6650 SW Bonita Rd., Tigard, OR 97224 Dear Building Permit Technicians: Please find attached for Plan review 2 sets of plans. We have enclosed the Energy Calcs, Structural Calcs, Permit Applications and a check of $1,899.88 for the plan review fees. Per our conversation with Barbara in your department, our plan review fees are $1,899.88 based on the valuation. The job valuation for this project is $509,000.00, breakdown as follows: Architectural: $ 300,000.00 Mechanical: $ 65,000.00 Electrical: $ 110,000.00 Plumbing: $ 8,500.00 Sprinkler: $ 13,500.00 Fire Alarm: $ 12,000.00 Const. Type: V B Fully Sprinklered Occup. Type: M- Retail Occup. Load: 495 If it is at all possible could we please have a receipt for our plan review fees and any approval/corrections faxed to us at 626/ 792 -5777. Please call us if you have any questions. Sincerely, Carla Street TOTAL SQUARE FOOTAGE 16,931 CONTACT: Scott Daves @ Permits Today 140 So. Lake Ave., Suite 323 Pasadena, CA 91101 Tel. 626/585 -2931 Fax 626/ 792 -5777 permitstodav' . com 1+0 South Lake Ave. #325 • Pasadena, CA 91101 • Tel: 626 -585 -2951 Fax: 626 -792 -5777 2 PERMITS TODAY ARCHITECT: Nicholas J. Tricarico Architects 500 Valley Rd. Wayne. NJ 07470 Tel. 973/692 -0222 Fax 973/692 -0223 Nicholas J. Tricarico, Lic. #2608 TENANT: Thomasville Furniture 401 E. Main St. Thomasville, NC 27360 Tracy Bennett Tel. 336/313 -4409 Fax 336/472 -4099 CONTRACTOR: TBD Any other questions please feel free to contact my self at the above number. Please fax a copy of any comments to our offices at 626/ 792 -5777. Thank you. 140 South Lake Ave. #325 • Pasadena, CA 91101 • Tel: 626 - 585 -2931 Fax: 62.6 -792 -5777 IA L Form 2a Project Name: Page: 1 SUMMARY Project 1. Project Name THOMASVILLE 2. Project Address 6650 S.W. BONITA ROAD 3. City/Town TIGARD 5. County I Washington 4. Building, Gross Area (ft2) 16,934 6. No. of Floors I 1 7. Construction Site Elevation Above 2,000 ft? ❑ YES 0 NO Attached Chapter Type ID Description Attach Forms and Building Envelope Form 3a Building Envelope - General ❑ Worksheets 3b Prescriptive Path - All Climate Zones ❑ * CodeComp Report for Simplified Trade -off ❑ * In lieu of 3b * Floppy disc with .occ CodeComp file ❑ Check boxes to Worksheet 3a Wall U- factor ❑ indicate attached 3b Roof U- factor ❑ forms and 3c Floor U- factor ❑ worksheets 3d Window /Skylight Schedule ❑ Systems Form 4a Systems - General El 4b Complex Systems ❑ Worksheet 4a Unitary Air Conditioners - Air Cooled 0 4b Unitary Air Cond. - Water & Evap Cooled ❑ 4c Unitary Heat Pump - Air Cooled ❑ 4d Unitary Heat Pump - Water Cooled ❑ 4e Packaged Terminal A.C. - Air Cooled ❑ 4f Packaged Terminal Heat Pump - Air Cooled ❑ 4g Water Chilling Pkgs - Water & Air Cooled ❑ 4h Heat Rejection Equipment ❑ 4i Boiler - Gas -Fired and Oil -Fired ❑ 4j Furnace & Unit Heaters - Gas and Oil -Fired ❑ 4k Simultaneous Heating and Cooling ❑ 41 Air Transport Energy ❑ 4m Natural Ventilation ❑ Lighting Form 5a Lighting - General 0 5b Interior Lighting Power - Tenant Method 0 5c Int. Ltng. Power - Space -by -Space Method ❑ Worksheet 5a Lighting Schedule 0 5b Interior Lighting Power p Applicant 7. Name NICHOLAS J. TRICARICO r ' `d. elephone (973) 692 -0222 8. Company NICHOLAS J. TRICARICO A&D ' ,/ I - e 11/19/07 9. Signature )11 A Cr ?,, % 0 < °`' Attached No. of Pages Description of Documentation 0; , t p f Document- O N o. L3A 0 � . ,�1 i `. I : L L `'� , N. J. ation z y, f �-�; �-i e u L,ompnanc.e wiin v eneuive u uu uuc Form 5a Project Name: THOMASVILLE Page: 2 LIGHTING - GENERAL 1. Interior Exceptions (Section 1313.1) ❑ No Interior Lighting. The building plans and specifications do not call for new or altered interior lighting. Skip to item 5, Exterior building Lighting - General, below. Exceptions ❑ Exceptions. 1. The building or part of the building qualifies for an exception from code lighting Discussion of qualifying requirements. Applicable code exception is number: exceptions in instructions section. 2. Lighting equipment that qualifies for an exception - in addition to general lighting and is separately controlled. Applicable code exception is number: Areas of the building and equipment that qualify for any exceptions: Plans /Specs Show compliance by including a drawing sheet, detail number, and/or specification section and subparagraph. 2. Local Shut -off controls (Section 1313.3.1.1) 9 Complies. At least one local shut -off lighting control for every 2,000 square feet of lighted floor area and for all spaces enclosed by walls or ceiling height partitions. This control(s) is detailed in the building plans on drawing number: ❑ Exception. The building or part of the building qualifies for an exception. Applicable code exception is Section 1313.3.1.1, Exception: Portions of the building that qualify: 3. Automatic Shutoff Controls (Section 1313.3.1.2) ❑ Not Applicable. Office floor area is not over 2,000 square feet of contiguous office floor area or permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting or conference rooms, or school classrooms. ID Complies. All interior lighting systems are equipped with a separate automatic control to shut off lighting during unoccupied periods. Offices less than 300 square feet, meeting and conference rooms, and school classrooms shall be equipped with occupancy sensors that comply with Section 1313.3.1.2.1. Compliance details in plans /specs: ❑ Exception. The building or part of the building qualifies for an exception. The applicable code exception is Section 1313.3.1,2, Exception: Portions of the building that qualify: 4. Daylighting Controls (1313.3.1.3) El No classrooms or atriums with skylights or window to wall ratio greater than 50 %. ❑ Complies. All classrooms and atriums with window to wall ratio greater than 50% and /or skylights are equipped with automatic daylight sensing controls, as required by Section 1313.3.1.3.1 and Section 1313.3.1.3.2. The daylight sensors specified comply with Section 1313.3.1.3.3. Compliance details in plans /specs: Exterior Build- 5. Exterior Lighting (Section 1313.5) ing Lighting E7 Complies. The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior. is lighting directed to illuminate ❑ Exception. The building plans indicate luminaires with incandescent or mercury vapor lamps, but are the exterior of the building and specified for use in or around swimming pools, water features, or other locations subject to requirements adjacent walkways and of Article 680 of the 2002 National Electrical Code. loading areas with or without canopies. Clock Switches 6. Exterior and Canopy Lighting Controls (Section 1313.3.2) shall be astronomic (seasonal 9 Complies. The building plans and specifications include photoelectric and /or clock switches on all exterior correcting) type with separate lighting systems which are designed and programmed to extinguish lights when daylight is present, as programs for each day of the required by Section 1313.3.2. week and shall store energy to maintain timekeeping during power outages. 7. Interior Connected Lighting Power (Section 1313.4) YES Complies. The interior lighting power does not exceed the interior power allowance established . w y in either the Tenant Space Method (Form 5b) or the Space -by -Space Method (Form 5c). C Tenant Space Method (Form 5b) 6' Space -by -Space Method (Form 5c) 5 -1 Compliance with OSSC, effective 01/01/05 4 Form 5c Project Name: THOMASVILLE Page: 3 INTERIOR LIGHTING POWER - Space -by -Space Method Lighting 1. Total Interior Lighting Power Budget from Worksheet 5b -1 (Sum of Column (I)) 30,182 Power Budget 2. Total length of track lighting (ft) 520 Track Lighting Power 3. Line 2 multiplied by 37.5 Watts /ft 19,500 4. Total amperage of circuit breaker(s) serving track lighting (amps) 540 5. Voltage of circuit breaker serving track lighting (volts) 120 6. Maximum wattage of track lighting (multiply line 4 by line 5) 64,800 7. Track Lighting Power (lesser value of line 3 or line 6) 19,500 8. Total Interior Lighting Power from Worksheet 5b -1 (Sum of Column (m)) + 9,803 Building's 9. Total Adjusted Lighting Power (line 7 + line 8) = 29,303 Lighting Power YES 10. Does design meet budget? Line 9 must be no greater than line 1. sf 5 -3 Compliance with OSSC, effective 01/01/05 1 Work: Project Name: THOMASVILLE Page: 4 - LIGHTING SCHEDULE (a) (b) (c) (d) (e) (f) Lum Luminaire Is Luminaire ID Luminaire Lamp Ballasts Power From Type Description No. Description No. Description (watts) Table 5c Ap Compact Fluorescent Triple or Quad 1- CFTR42WGX24q -4- ELECT -46W - 1 CFTR42WGX24q -4 1 Electronic 46 YES B Fluorescent Linear Lamps T5 • , 2-F35T5-ELECT-78W • 2 F35T5 1 Elect. Program Start 78 YES „ � . 37.5 YES Track Lighting . Track Lighting -- -- -- D Compact F or Quad _ 1- CFTR42WGX24q -4 ELECT -46W 1 CFTR42WGX24q -4 1 Electronic 46 YES User Defined Incandescent � F 1 GE100PAR /HIR -- -- 100 NO .._ ,_ .. ___ __._,,. �_,__.,_,�.... FD User Defined f Fncandescent Downlight .1 GE100PAR /HIR - 100 NO G Fluorescent T8 4 bot 2- F32T8/30ES -ELECT NO -54W "7 2 F32T8 /30ES 1 Electronic Normal Output. IS 54 YES M Fluorescent Rapid Start T8 - 3 foot 1 -F25T8 -ELECT NO -27W ` 1 F25T8 1 Electronic Normal Output. RS 27 YES Q 12 Volt Tungsten Habgen Lamps • 1-20 watt lamp - EPS -23W - 1 20 watt lamp 1 Electronic Power Supply 23 YES R Fluorescent Rapid Start T8 -3 foot , 1- F25T8 -ELECT NO -27W - 1 F25T8 1 Electronic Normal Output. RS 27 YES ✓ User Defined ., GE Incandescent Uplihgt 1 GE 25BM 1 Electronic 25 NO W User Defined GE Incandescent Downlight 1 GE 50PAR2OH /FL 50 NO Z 12 Volt Tungsten Habgen Lamps 1 35 watt lamp- EPS -38W 1 35 watt lamp 1 Electronic Power Supply 38 YES V I v Z. veav . . v 4 ... w : _ 0,.. ,...„,_ ______. ..„............._.............______,„„„.„....„„......____.,„„.„„,_,..... „,, J , „. . ,......____ _ , .... ...„.„.._„..„...,„_____.....____ „,.„ „.„. ,,, _. .................._ ..„_. _, ,. „ ............._ ,...„„ _ ... J ._„„ , ...„..„.„,„________ , .1 60218_THOMASVI LLE_5ltg. xls Worksheet 5b-1 Project Name: THOMASVILLE Page: 5 INTERIOR LIGHTING POWER Space -by -Space Method Only Skip to column (f) if using the Tenant Space Method (a) (b) (C) (d) (e) Lure ID (9) (h) (ft (i) (k) from Quantity of Room ID (do Space Type Space Lighting Power Worksheet Luminaires (or Luminaire Lighting Room not leave any Area (Table 13-H) Type Budget 5a Column lineal ft. for track Power Exempt Power Total Ltg. blanks) (ft (enter space type only once per room) LPD (b) x (d) (a) lighting) (Watts) Fixtures (g) x (h) Power Each room SALES 14047 Retail - Other Merchandise Sales Area 2 28,094 AP L i 46 46 ❑ 2,116 35,168 must be STORAGE — — B :I 1 78 ❑ 78 402 identified. SALES — — C,C1 z i 244 38 O 9,150 35,168 Describe luminaires for each SALES — — D LI 17 46 ❑ 782 — individual room in SALES — — F 4 100 ❑ 400 — plans. SALES — — FD 5 100 ❑ 500 — STORAGE 566 Active Storage 0.8 453 G 6 54 ❑ 324 402 OFFICE 1159 Office- enclosed 1.1 1,275 M z i 1 27 ❑ 27 2,511 For track lighting SALES — — Q 4 23 ❑ 92 35,168 enter lineal feet in OFFICE — — R ;j 14 27 ❑ 378 2,511 column column (g) . RESTROOM 400 Restrooms 0.9 360 V 2i 2 25 ❑ 50 372 Column (k), enter SALES — — W 4 +l 10 50 ❑ 500 35,168 sum of column (j) SALES — — Z LI 56 38 ❑ 2,128 — for each room only OFFICE — — B 27 78 ❑ 2,106 2,511 once at first entry q _ for the room . See RESTROOM — — D J 7 46 ❑ 322 372 example in SALES — — C,C1 11 520 38 ❑ 19,500 35,168 instructions. — — ❑ 27 ❑ - - - ❑ - - � - ❑ - - - - J - ❑ - - - ❑ - - 4 - ❑ - :1 � - ❑ - - : - ❑ - - - ❑ - - - - - ❑ - - - - - ❑ - - - - ❑ - - - - - ❑ - - - - - ❑ - - - - - ❑ - - - - J - ❑ - - - - - ❑ - - - ❑ - - - - - ❑ - - - - - ❑ - - - - 3� - s ❑ - - - - J i - ❑ - - - - zi. - ❑ - — 16,172 Worksheet 5b-1 Total Budget 30,182 Wksht 5b-1 Total Lighting Power (excluding exemptttrack fixtures) 9,803 Other Pages Total Number of Additional Worksheet 5b List the additional worksheets nece- ssary to catalog all - luminaires in (I) (m) (n) building Lighting Power Budget Space Proposed Buiding Lighting by -Space only (Total of Power (Total of column (k), Area Sqft. (not required Worksheet Number column (e)) excluding exempt/track) for Tenant Method) 5b -1 30,182 9,803 16,172 5b-2 5b -3 Sum of additional 5b worksheets ° a°- 30,182 9,803 16,172 ; Total Budget (of all worksheets) ..� v o s . 5 -5 Compliance with OSSC, effective 01/01/05 6C/ p2o 7-0o /o,S Form 2a Project Name: Page: 1 SUMMARY Project 1. Project Name THOMASVILLE , 7 j • 2. Project Address 6650 S.W. BONITA ROAD''G 0 t 3. City/Town TIGARD CTI ( € 5. Co un t y ! Washington A 4. Building, Gross Area (ft2) 16,934 ` C JfT r)r 6. No. of Floors' 1 7. Construction Site Elevation Above 2,000 ft? ❑ YES 0 NO Attached Chapter Type ID Description Attach Forms and Building Envelope Form 3a Building Envelope - General ❑ 3b Prescriptive Path - All Climate Zones ❑ Worksheets * CodeComp Report for Simplified Trade -off ❑ * In lieu of 3b * Floppy disc with .occ CodeComp file ❑ Check boxes to Worksheet 3a Wall U- factor ❑ indicate attached 3b Roof U- factor ❑ forms and 3c Floor U- factor ❑ worksheets 3d Window /Skylight Schedule ❑ Systems Form 4a Systems - General H 4b Complex Systems ❑ Worksheet 4a Unitary Air Conditioners - Air Cooled • 4b Unitary Air Cond. - Water & Evap Cooled ❑ 4c Unitary Heat Pump - Air Cooled ❑ 4d Unitary Heat Pump - Water Cooled ❑ 4e Packaged Terminal A.C. - Air Cooled ❑ 4f Packaged Terminal Heat Pump - Air Cooled ❑ 4g Water Chilling Pkgs - Water & Air Cooled ❑ 4h Heat Rejection Equipment ❑ 4i Boiler - Gas -Fired and Oil -Fired ❑ 4j Furnace & Unit Heaters - Gas and Oil -Fired ❑ 4k Simultaneous Heating and Cooling ❑ 41 Air Transport Energy ❑ 4m Natural Ventilation ❑ Lighting Form 5a Lighting - General H 5b Interior Lighting Power - Tenant Method II 5c Int. Ltng. Power - Space -by -Space Method ❑ ),IVbrksheet _5a Lighting Schedule IO r a , Y : , 5b" 6 ;0 - Anterior Lighting Power II � u NI IC h 0 i � . ` E Applicant 7. Name , NI .4, TRICARICO 10. Telephone (973) 692-0222 8. Company NICIN; J. TRIO/ RICO A&D PC 11. Date 07/17/07 9. Signature ��� Klf�;'7'1� p ^ � ,. Attached No of, Pages De • ` •cumentation Document- ation uompiiance wrrn k./.0u, errecuve u iiu vuo Form 5a Project Name: THOMASVILLE Page: 2 LIGHTING - GENERAL 1. Interior Exceptions (Section 1313.1) ❑ No Interior Lighting. The building plans and specifications do not call for new or altered interior lighting. Skip to item 5, Exterior building Lighting - General, below. Exceptions ❑ Exceptions. 1. The building or part of the building qualifies for an exception from code lighting Discussion of qualifying requirements. Applicable code exception is number: exceptions in instructions section. 2. Lighting equipment that qualifies for an exception - in addition to general lighting and is separately controlled. Applicable code exception is number: Areas of the building and equipment that qualify for any exceptions: Plans /Specs Show compliance by including a drawing sheet, detail number, and /or specification section and ' subparagraph. 2. Local Shut -off controls (Section 1313.3.1.1) D Complies. At least one local shut -off lighting control for every 2,000 square feet of lighted floor area and for all spaces enclosed by walls or ceiling height partitions. This control(s) is detailed in the building plans on drawing number: ❑ Exception. The building or part of the building qualifies for an exception. Applicable code exception is Section 1313.3.1.1, Exception: Portions of the building that qualify: 3. Automatic Shutoff Controls (Section 1313.3.1.2) ❑ Not Applicable. Office floor area is not over 2,000 square feet of contiguous office floor area or permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting or conference rooms, or school classrooms. O Complies. All interior lighting systems are equipped with a separate automatic control to shut off lighting during unoccupied periods. Offices less than 300 square feet, meeting and conference rooms, and school classrooms shall be equipped with occupancy sensors that comply with Section 1313.3.1.2.1. Compliance details in plans /specs: ❑ Exception. The building or part of the building qualifies for an exception. The applicable code exception is Section 1313.3.1,2, Exception: Portions of the building that qualify: 4. Daylighting Controls (1313.3.1.3) D No classrooms or atriums with skylights or window to wall ratio greater than 50 %. ❑ Complies. All classrooms and atriums with window to wall ratio greater than 50% and /or skylights are equipped with automatic daylight sensing controls, as required by Section 1313.3.1.3.1 and Section 1313.3.1.3.2. The daylight sensors specified comply with Section 1313.3.1.3.3. Compliance details in plans /specs: Exterior Build- 5. Exterior Lighting (Section 1313.5) ing Lighting 2 Complies. The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior. is lighting directed to illuminate ❑ Exception. The building plans indicate luminaires with incandescent or mercury vapor lamps, but are the exterior of the building and specified for use in or around swimming pools, water features, or other locations subject to requirements adjacent walkways and of Article 680 of the 2002 National Electrical Code. loading areas with or without canopies. ■ Clock Switches 6. Exterior and Canopy Lighting Controls (Section 1313.3.2) shall be astronomic (seasonal D Complies. The building plans and specifications include photoelectric and /or clock switches on all exterior correcting) type with separate lighting systems which are designed and programmed to extinguish lights when daylight is present, as programs for each day of the required by Section 1313.3.2. week and shall store energy to maintain timekeeping during power outages. 7. Interior Connected Lighting Power (Section 1313.4) YES Complies. The interior lighting power does not exceed the interior power allowance established :.r.. ,„ in either the Tenant Space Method (Form 5b) or the Space -by -Space Method (Form 5c). kt, Tenant Space Method (Form 5b) Space-by-Space Method (Form 5c) 5 -1 Compliance with OSSC, effective 01/01/05 Form 5c Project Name: THOMASVILLE Page: 3 INTERIOR LIGHTING POWER - Space - by - Space Method Lighting 1. Total Interior Lighting Power Budget from Worksheet 5b -1 (Sum of Column (I)) 30,182 Power Budget 2. Total length of track lighting (ft) 520 Track Lighting Power 3. Line 2 multiplied by 37.5 Watts /ft 19,500 4. Total amperage of circuit breaker(s) serving track lighting (amps) 540 5. Voltage of circuit breaker serving track lighting (volts) 120 6. Maximum wattage of track lighting (multiply line 4 by line 5) 64,800 7. Track Lighting Power (lesser value of line 3 or line 6) 19,500 8. Total Interior Lighting Power from Worksheet 5b -1 (Sum of Column (m)) + 10,104 Building's 9. Total Adjusted Lighting Power (line 7 + line 8) = 29,604 Lighting Power YES 10. Does design meet budget? Line 9 must be no greater than line 1. 5-3 Compliance with OSSC, effective 01/01/05 Work Project Name: THOMASVILLE Page: 4 . LIGHTING SCHEDULE (a) (b) (c) (d) (e) (f) Lum Luminaire Is Luminaire ID Luminaire Lamp Ballasts Power From _ _ T„ype _•• •_ Description _• No. Description No. Description (watts) Table 5c AP Compact Fluorescent Triple or Quad 1- CFTR42WGX24q -4- ELECT -46W - 1 CFTR42WGX24q -4 1 Electronic 46 YES B Fluorescent Linear Lamps T5 2- F35T5- ELECT -78W - 2 F35T5 1 Elect. Program Start 78 YES C,C1 Track Lighting Track Lighting -- -- -- 37.5 YES D Compact Fluorescent Triple or Quad - 1- CFTR42WGX24q -4- ELECT -46W - 1 CFTR42WGX24q -4 1 Electronic 46 YES F I User Defined kicandescentDownlight - 1 GE100PAR/HIR -- -- 100 NO • FD User Defined Incandescent Downlight ' 1 GE1 OOPAR/HIR -- -- 100 NO G Fluorescent TB -4 foot - 2- F32T8 /30ES- ELECTNO -54W - 2 F32T8 /30ES 1 Electronic Normal Output. IS 54 YES M ( Fluorescent Rapid Start T8 - 3 foot T8 -EL 1 -F25ECT NO-27W - 1 F25T8 1 Electronic Normal Output. RS 27 YES Q 12 Volt Tungsten Halogen Lamps 1 -20 watt lamp - EPS -23W ■ 1 20 watt lamp 1 Electronic Power Supply 23 YES R Fluorescent Rapid Start T8 - 3 foot 1 -F25T8 -ELECT NO -27W ' 1 F25T8 1 Electronic Normal Output. RS 27 YES ✓ User Defined GE Incandescent Uplihgt ' 1 GE 25BM 1 Electronic 25 NO W User Defined • GE Incandescent Downlight - 1 GE 50PAR2OH /FL 50 NO z 12 Volt Tungsten Halogen Lamps - -i 1-35 watt lamp- EPS -38W - 1 35 watt lamp 1 Electronic Power Supply 38 YES „._..........._. .... ..._..... A _ ._,I , ..... _ .., .. _ . _ _.„.. . _ _ __. . _ ____ _ . - - _ . . ___ . _ . _ „_,_ ___________ ......,- _ __ "....___ _ . . ________ _ . ______, .__„„„. ___ ____„_ _ _ _ _ _ _ _ ____5 .. _-_, . -.I , _ __, . ___ ____d 5 .: ____ -_-1 . 6021 8_THOMASV I LLE_5ltg.xls Worksheet 5b-1 Project Name: THOMASVILLE Page: 5 INTERIOR LIGHTING POWER Space -by -Space Method Only Skip to column (f) if using the Tenant Space Method (a) (b) (c) (d) (e) Lum ID (9) (h) (I) G) (k) from Quantity of Room ID (do Space Type Space Lighting Power Worksheet Luminaires (or Luminaire Lighting Room not leave any Area (Table 13-H) Type Budget 5a Column lineal R. for track Power Exempt Power Total Ltg. blanks) (ft (enter space type only once per room) LPD (b) x (d) ( lighting) (Watts) Fixtures (g) x (h) Power Each room SALES 14047 , Retail - Other Merchandise Sales Area 2 28,094 AP A 41 46 ❑ 1,886 36,120 must be STORAGE - - B zi 1 78 ❑ 78 402 identified. SALES - - C,C1 244 38 p 9,150 36,120 Describe luminaires for each SALES - - D 17 46 ❑ 782 - individual room in SALES - - F -1 4 100 ❑ 400 - plans. SALES - - FD 5 100 ❑ 500 - STORAGE 566 Active Storage 0.8 453 G ▪ 6 54 ❑ 324 402 OFFICE 1159 Office- enclosed 1.1 1,275 M -1 1 27 ❑ 27 1,860 For track lighting SALES - - 0 -1 4 23 ❑ 92 36,120 enter lineal feet in OFFICE - - R 13 27 ❑ 351 1,860 column column (g) . RESTROOM 400 Restrooms 0.9 360 V ,j 2 25 ❑ 50 372 Column (k), enter SALES - - W 23 50 ❑ 1,150 36,120 sum of column (J) SALES - - Z _ 70 38 ❑ 2,660 - for each room only OFFICE - - B - 19 78 ❑ 1,482 1,860 once at first entry for the room . See RESTROOM - - D ▪ 7 46 ❑ 322 372 example in SALES - - C,C1 J 520 38 ❑ 19,500 36,120 instructions. - - - ❑ - - 27 ❑ - - - - ,d - ❑ - - - ❑ - - J - ❑ - - - 1 - ❑ - - - ❑ - - - - ❑ - - zl - ❑ - - A, - ❑ - - - - - ❑ - - - - - - ❑ - - - - - ❑ - - - - - ❑ - - - - ._j - ❑ - - - - zI _ - ❑ - - - - - ❑ - , - - - - ❑ - - - - - ❑ - - - - - • ❑ - - - - - - ❑ - - - - zl - ❑ - - - A - ❑ - - - - -1 - ❑ - - - - zl - ❑ - - 16,172 Worksheet 5b-1 Total Budge t 30,182 Wksht 5b-1 Total Lighting Power (excluding exempt/track fixtures) 10,104 Other Pages Total Number of Additional Worksheet 5b I 0 List the additional worksheets nece- ssary to catalog all - - luminaires in (I) (m) (n) building Lighting Power Budget: Space Proposed Buiding Lighting by -Space only (Total of Power (Total of column (k), Area Sqft. (not required Worksheet Number column (e)) excluding exempt/track) for Tenant Method) 5b-1 30,182 10,104 16,172 5b-2 5b-3 Sum of additional 5b worksheets _ / ~6": " 30,182 10,104 16,172 Total Budget (of all worksheets) 5-5 Compliance with OSSC, effective 01/01/05