Correspondence City Of Tigard, Oregon ® 13125 SW Hall Blvd. O Tigard, OR 97223
August 22, 2007
RE: MECHANICAL FOR THOMASVILLE
kipttoomy
Project Information
Building Permit: MEC2007 -00489 Construction Type: VB
Tenant Name: Thomasville Occupancy Type: M
Address: to e,5 - p n" W Bonita Dr. Occupant Load: 495
Area: NA Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty
Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007
edition. The submitted plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air
Conditioning Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the
appliance. The shutoff valve shall be located in the same room and within
six feet of the appliance served. Access shall be provided to the shutoff
valve. C409.5 OMSC
3. Equipment and appliances regulated by this code requiring electrical
connections shall have a positive means of disconnect in accordance with the
Electrical Code. 301.7 OMSC
4. Permanent equipment supported by the structure, 400 lbs and over, shall
have their attachments designed in accordance with the Building Code.
301.16 OMSC
5. Appliances shall be accessible for inspection, service, repair or replacement
without removal of permanent construction. 306.1 OMSC
6. Manufacturer's installation instructions shall be available on the jobsite at
the time of inspection. 304.1 OMSC
7. Condensate from cooling coils or evaporators shall be collected and
discharged to an approved plumbing fixture or disposal area. 307.1 OMSC
Phone: 503.639.4171 ® Fax: 503.684.7297 o www.tigard - or.gov • TTY Relay: 503.684.2772
8. Smoke detectors shall be installed in return air systems with a design
capacity greater than 2000 cfm. Upon activation, the smoke detector
shall shut down the air distribution system. Smoke detectors shall be
connected to a fare alarm system and shall activate an audible and
visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1
OMSC
9. Suspended -type unit heaters shall be supported by non - combustible elements
that are designed and constructed to accommodate the weight and dynamic
loads and shall be sway braced. 920.2 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval
stamp, shall be maintained on the jobsite. The plans shall be available to the
Building Division inspectors throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all
new buildings in such a position as to be plainly visible and legible from the street
or road fronting the property.
When submitting revised drawings or additional information, please attach a copy
of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal
assists the City of Tigard in tracking and processing the documents.
• espectfully,
an Nelson,
Senior Plans Examiner