Correspondence FL « 2 7 - ( 7 f 7 70 b/.J orvir� /�5 Gary Noble From: Katie Showalter [Katie @hillsboroelectric.com] Sent: Wednesday, February 06, 2008 12:01 PM To: Gary Noble Cc: John Hoffard; Katie Showalter Subject: Paul Schatz Attachments: D00080206.pdf I just received a call from Luke the onsite electrician at Paul Schatz. I have a few concerns about your inspection that took place today: 1. I added to our permit #ELC2007 -00606 for an additional HVAC circuit and Low Voltage circuit for Fire Alarm (please see description given by City of Tigard on your correction report) — please see attached permit application for clarification. I have also enclosed our original permit application that states that we pulled circuits for exterior lighting, one (1) HVAC unit, shell receptacles and a new service. 2. You asked that Hillsboro Electric pull a permit for the house panel at Paul Schatz — you were made aware that we had nothing to do with this panel, but still insisted on having us pull the permit. Now I am hearing that you want us to contact Paul Schatz and find out who did the electrical in the building to have them pull the permit. Is this correct? If so I need a credit for the permit that we pulled (permit# ELC2008- 00044) for that panel. I don't understand why this needed to be done if we were just using existing circuits for site lighting (relocating light poles) ? ?? I have spoken with the contractor and no one worked on this panel — Hillsboro Electric only reused circuits for the site lighting, as per our permit# ELC2007- 00657. This panel has been in the building since the building was built. Does the City of Tigard not have any records of the original permit for that space? 3. If I remember correctly we had the site lighting as a part of our permit# ELC2007 -00376 for the Thomasville space — and you only wanted us to pull a permit for the site lighting due to the address changes that took place. You didn't want the site lighting to be under permit# ELC2007 -00376 because of the address 6650 SW Bonita Road. So I then pulled permit# ELC2007 -00657 so that it would be under the address 6600 SW Bonita Road. 4. I will be contacting PGE to hook -up the service at the new building (Permit# ELC2007- 00606) today and will recall in a final once that is complete. Please let me know if I have missed anything that needs to happen prior to you coming out again for a final inspection for all of Hillsboro Electric's work. • Thank you, Katie Showalter Project Manager 1 Gary Noble From: Katie Showalter [Katie @hillsboroelectric.com] Sent: Friday, December 21, 2007 4:51 PM To: Gary Noble Cc: Katie Showalter Subject: FW: Attachments: D00071221.pdf Gary, Attached is the fault current for the 400amp service — 6670 SW Bonita Road. Please let me know if you have any questions. Please also if you could call John (Hawk) at 971 - 219 -8721. Thank you and have a happy holiday. Katie «D00071221. pdf» 1 'i21-200T 04:42PM FROM- .� , 4 T -711 P.001 /001 F -189 1• • J LCD ®d -- of)(o °( " .....'� „I 5. . 'Ir „ 1 .;;, ,,,., I,'I• ,•r ,I' , ', ,' 1' Portland General Eleciric Company ■ MEMORANDUM 12/21/07 ; , TO: CONTACT: JOHN W HILLSBORO ELECTRIC ) ' • PHONE: 971- 219 -8721 CUSTOMER NAME: PAUL SCHATZ ADDRESS: 6670 SW. BONITA RD_, TIGARD l FROM PGE ENGR: MILO STARR ® 1 .r•1 ,1 i ' 503-570-4414 ( f ! ;I J � l rJ y; SUBJECT: 3 -PHASE SECONDARY LINE -UNE F- ULT CURRENT (RMS • TRANSFORMER DATA 1Z. 0 XFMR Impedance r /,): W _ 3.6 % RADIAL NETORK . '' TRANSFORMER SIZE: 300 KVA XFMR ? NO Secondary VOLTAGE (L to L): 208 v WYE , ,VAULT - -> VAULT (or Pole - -> Pile) SECONDARY : a” � 1 ;1 ' 1 I , Secondary Wire LENGTH: 0 Feet WIRE SIZE lI of ' ; I ' ; Number of SECONDARY RUNS; 1 Run(s) of: T. a Secondary WIRE Resistance R: 0.0773 Ohms /1000' '' + , Secondary WIRE Reactance X: 0.0258 Ohms /1000' I 1.i i' VAULT ( or Pole) - -> PANEL SECONDARY (or Svc Drop) ` 1 ' I Service Wire LENGTH: 30 Feet I WIRE SIZE ° 1 I Number of Service RUNS; 1 Run(s) of: 1350 OX UG Iy'; 1. , '' ' Service WIRE Resistance R: 0.0600 Ohms /1000' 'r.' Service WIRE Reactance X: 0.0330 Ohms /1000' 1. 1 _ ' ' FAULT CURRENT: 14,353 Amps , I � , . . , '.1 1 (or SHORT CIRCUIT CURRENT) I ; , (or INTERRUPTING CURRENT) i' ' ' Based on a panel size of: 400 AMP Amps Is 1 I To Print This Page; "Ctrl M and choose "Print 3-phase Data" ' . Tern date by Wayne Amondson Convened to Excel by Allen Cam • bell, BEST Coro ullIno 1/25,2400 ' l �' ..11 1 . • , , ii;.I' .. ; '4' .I ' .1 {A; Iy } 1 , ,if. iFli, i 1�' : 1 ',�� ' , l ' . ' l 1 I:i. 1 i t ; + .! , 1 J I