Correspondence FL « 2 7 -
( 7 f 7 70 b/.J orvir� /�5
Gary Noble
From: Katie Showalter [Katie @hillsboroelectric.com]
Sent: Wednesday, February 06, 2008 12:01 PM
To: Gary Noble
Cc: John Hoffard; Katie Showalter
Subject: Paul Schatz
Attachments: D00080206.pdf
I just received a call from Luke the onsite electrician at Paul Schatz. I have a few concerns about your inspection that
took place today:
1. I added to our permit #ELC2007 -00606 for an additional HVAC circuit and Low Voltage circuit for Fire Alarm
(please see description given by City of Tigard on your correction report) — please see attached permit application
for clarification. I have also enclosed our original permit application that states that we pulled circuits for exterior
lighting, one (1) HVAC unit, shell receptacles and a new service.
2. You asked that Hillsboro Electric pull a permit for the house panel at Paul Schatz — you were made aware that we
had nothing to do with this panel, but still insisted on having us pull the permit. Now I am hearing that you want
us to contact Paul Schatz and find out who did the electrical in the building to have them pull the permit. Is this
correct? If so I need a credit for the permit that we pulled (permit# ELC2008- 00044) for that panel. I don't
understand why this needed to be done if we were just using existing circuits for site lighting (relocating light
poles) ? ?? I have spoken with the contractor and no one worked on this panel — Hillsboro Electric only reused
circuits for the site lighting, as per our permit# ELC2007- 00657. This panel has been in the building since the
building was built. Does the City of Tigard not have any records of the original permit for that space?
3. If I remember correctly we had the site lighting as a part of our permit# ELC2007 -00376 for the Thomasville space
— and you only wanted us to pull a permit for the site lighting due to the address changes that took place. You
didn't want the site lighting to be under permit# ELC2007 -00376 because of the address 6650 SW Bonita Road.
So I then pulled permit# ELC2007 -00657 so that it would be under the address 6600 SW Bonita Road.
4. I will be contacting PGE to hook -up the service at the new building (Permit# ELC2007- 00606) today and will recall
in a final once that is complete.
Please let me know if I have missed anything that needs to happen prior to you coming out again for a final inspection for
all of Hillsboro Electric's work.
•
Thank you,
Katie Showalter
Project Manager
1
Gary Noble
From: Katie Showalter [Katie @hillsboroelectric.com]
Sent: Friday, December 21, 2007 4:51 PM
To: Gary Noble
Cc: Katie Showalter
Subject: FW:
Attachments: D00071221.pdf
Gary,
Attached is the fault current for the 400amp service — 6670 SW Bonita Road. Please let me know if you have any
questions.
Please also if you could call John (Hawk) at 971 - 219 -8721.
Thank you and have a happy holiday.
Katie
«D00071221. pdf»
1
'i21-200T 04:42PM FROM- .� , 4 T -711 P.001 /001 F -189
1• • J
LCD ®d -- of)(o °(
" .....'� „I 5. . 'Ir „ 1 .;;, ,,,., I,'I• ,•r ,I' , ', ,' 1'
Portland General Eleciric Company
■
MEMORANDUM
12/21/07 ; ,
TO: CONTACT: JOHN W HILLSBORO ELECTRIC ) ' •
PHONE: 971- 219 -8721
CUSTOMER NAME: PAUL SCHATZ
ADDRESS: 6670 SW. BONITA RD_, TIGARD
l
FROM PGE ENGR: MILO STARR ® 1 .r•1 ,1
i ' 503-570-4414 ( f ! ;I
J � l rJ y;
SUBJECT: 3 -PHASE SECONDARY LINE -UNE F- ULT CURRENT (RMS •
TRANSFORMER DATA 1Z. 0
XFMR Impedance r /,): W
_ 3.6 % RADIAL NETORK
. '' TRANSFORMER SIZE: 300 KVA XFMR ? NO
Secondary VOLTAGE (L to L): 208 v WYE ,
,VAULT - -> VAULT (or Pole - -> Pile) SECONDARY : a” �
1 ;1 ' 1 I , Secondary Wire LENGTH: 0 Feet WIRE SIZE lI of '
; I
' ; Number of SECONDARY RUNS; 1 Run(s) of: T.
a
Secondary WIRE Resistance R: 0.0773 Ohms /1000' '' + ,
Secondary WIRE Reactance X: 0.0258 Ohms /1000' I
1.i
i' VAULT ( or Pole) - -> PANEL SECONDARY (or Svc Drop) `
1 ' I Service Wire LENGTH: 30 Feet
I WIRE SIZE ° 1
I
Number of Service RUNS; 1 Run(s) of: 1350 OX UG Iy';
1.
,
'' ' Service WIRE Resistance R: 0.0600 Ohms /1000'
'r.'
Service WIRE Reactance X: 0.0330 Ohms /1000'
1. 1 _ '
' FAULT CURRENT: 14,353 Amps , I � , .
.
, '.1
1
(or SHORT CIRCUIT CURRENT) I ; ,
(or INTERRUPTING CURRENT) i'
' ' Based on a panel size of: 400 AMP Amps
Is
1 I
To Print This Page; "Ctrl M and choose "Print 3-phase Data" '
. Tern date by Wayne Amondson Convened to Excel by Allen Cam • bell, BEST Coro ullIno 1/25,2400 ' l �'
..11 1 . • , , ii;.I' .. ; '4' .I ' .1 {A; Iy } 1 , ,if. iFli, i 1�' : 1
',�� ' , l ' . ' l 1 I:i. 1 i t ; + .! , 1 J I