Loading...
Report 01/11/2005 15:10 503 - 443 -3700 TM RIPPEY PAGE 02 1\A RIPPEY Field Report CONSULTING ENGINEERS 7650 SW Sevcland Street Phone: (503) 443 -3900 Suite 100 Fax: (503) 443 -3700 Tigard, Oregon 97223 Issue Date: 1/11/05 .. • PROJECT INFOATION .• • Project Name: 71=55= Beveland Buildings Project #: 41.1.1 Owner: Beveland Business Park, LLC Permit ht: BUP2004 -00295 . 'SITE IN#O IATI{1rN Location: 7155 SW Beveland St. Observation Date: 12 -29 -04 Observation Time: 9:00 am Weather: Overcast Temperature: 45 deg Contractor: SI Grace, LLC Present On -Site: Ralph Turnba.ugh, TM Rippey Consulting Engineers OB;;ERVATION SUMMA; . Area(s) Inspected: Roof at Building 42 Purpose of Observation: Observe roof nailing and strapping. Estimate ofProgess: 95% Completed Workmanship Level: satisfactory DISTRIBUTION Copies to: Beveland Business Park, LLC - -• Dalton .rooks Mildren Design Group — Jack Kriz City of Tigard Building Department TM Rippey Consulting Engineers 7070 SW Fir Loop #100, Tigard, Oregon 97223 (503) 443 -3900 Fax (503) 443 -3700 01/11/2005 15:10 503 - 443 -3700 TM RIPPEY PAGE 03 • Project Name — Field Report Date Page 2 or 2 Note: Listed below are items noted in previous field observations that have not been addressed to date. Items noted in this or previous field observations must be addressed and docrtrnented, for review bey all affected parties to be considered as closed. na .CURRENT NOTED ITEMS 1. Parapet wall straps were not installed per detail Resolution: The contractor was informed and 1 /S4.10 the straps were being instal led while we were on site. 2. One sheathing panel joint was warped. Resolution: The contractor was instructed to install blocking at this location below the roof deck. 3. The sheating was observed to be installed with Resolution: It was our understanding that the all joints abutting tight rather than having a • building was to be roofed the following day 1/8" gap per the structural general notes. such that the roof sheathing would not be exposed to prolonged wet weather. 4. `Shiners' were observed at the strap to blocking Resolution: The contractor was instructed to connections at the Southwest corner of the roof. remove the nails and re -nail the strap into the blocking. 5. All other nailing and strapping appeared t_ o be in conformance with the project documents. Any work observed and noted above shall not be considered a waiver of the duties and responsibilities of other parties or of the requirement of strict compliance with the Contract Documents and the intent of the project plans and specifications. This report shall not be considered to specifically address every detail or location of the work in progress, but is rather a general observation of field conditions of the day of t he report. Submitted by: Ralph Turnbau.gh TM Rippey Consulting Engineers TM Rippey Consulting Engineers 7070 SW Fir Loop #100, Tigard Oregon 97223 (503) 443 -3900 Fax (503) 443 -3700 01/11/2005 15:10 503 - 443 -3700 TM RIPPEY PAGE 01 TM RIPPER 7650 SW Beveland Se, Suite 100 Tigard, Oregon 97223 CONSULTING ENGINEERS Phone: (503)443 -3900 Fax: (503)443 -3700 FACSIMILE TRANSMITTAL DATE: January I. i, 2005 PROJECT NO.: 4111 PLEASE DELIVER THE FOLLOWING PAGES IMMEDIATELY TO: COMPANY: SI Grace ATTENTION: Dalton Brooks PROJECT: Beveland Business Park, LLC DESCRIPTION: Field Report Dated 1/11/05 Regarding Roof Nailing and Strapping Observation REMARKS: CC: Jack Kriz, Mildren Design Group - (503)244 -0417 City of Tigard Building Department - (503)684 -7297 FROM: Ralph. Tumbaugh RECEIVER'S FAX NO.: (503)620 -7934 THERE ARE 3 PAGES, INCLUDING THIS TRANSMITTAL SHEET. OFFIICEMVIRPAX if 4 7 57 iFc/,70° f — 'V,2-95 • - 7/s 7 8 tel/ c .Form 2a Project Name:I I Page:I SUMMARY Project 1. Project Name 7f55 15x4ec.At.lfl 13vmw1/4, (1 li-DiP 1 2. Project Address -j 55 13cvA..hr ID 3. City/Town Tj yhe.D 5. County 1 0,6,m • 4. Building, Gross Area (ft2) g, 4-9 G. Se? f�: 6. No. of Floors I Z 7. Construction Site Elevation Above 2,000 ft? ❑(ES I NO Attached Chapter Type ID Description Attach Forms and Building Envelope Form 3a Building Envelope - General 0 Worksheets 3b Prescriptive Path - All Climate Zones la Worksheet 3a Wall U- factor ❑ Check boxes to 3b Roof U- factor ❑ indicate attached 3c Floor U- factor ❑ forms and 3d Window /Skylight Schedule IZ worksheets Systems Form 4a Systems - General ❑ 4b Complex Systems ❑ `U �� Worksheet 4a Unitary Air Conditioners - Air Cooled ❑ e ('' 4b Unitary Air Cond. - Water & Evap Cooled ❑ V 4c Unitary Heat Pump - Air Cooled ❑ N ')S' 4d Unitary Heat Pump - Water Cooled ❑ � , �0 4e Packaged Terminal A.C. - Air Cooled ❑ 01\I O �9` 4f Packaged Terminal Heat Pump - Air Cooled ❑ � ,�G, 4g Water Chilling Pkgs - Water & Air Cooled ❑ R 0 )11. 4h Heat Rejection Equipment ❑ 4i Boiler - Gas -Fired and Oil -Fired ❑ 4j Furnace & Unit Heaters - Gas and Oil -Fired ❑ 4k Simultaneous Heating and Cooling ❑ 41 Air Transport Energy ❑ 4m Natural Ventilation ❑ Lighting Form 5a Lighting - General ❑ 5b Interior Lighting Power - Tenant Method ❑ 5c Int. Ltng. Power - Space -by -Space Method ❑ Worksheet 5a Lighting Schedule ❑ 5b Interior Lighting Power ❑ Applicant 7. Name 10. Telephone 503.244 -oSSZ. 8. Company 11iLoR tsi11%-i. l -jRcup 11. Date 9. Signature Attached No. of Pages Description of Documentation Document- I - 3€ ation / -rAsi.,� 3 c / 5.1..A7-4 1 e.4-4A'n o1 Summary040104.xls • Form 3a Project Name: Page: BUILDING ENVELOPE - GENERAL Check all boxes that 1. Exceptions (Section 1312) apply ❑ No Envelope Components. The building plans do not call for new or altered building envelope components, e.g., walls, floors or roof /ceilings. ❑ A Non - conditioned Building. The proposed structure has no spaces heated or cooled by an HVAC system. Exceptions ❑ Exception. All new or altered building envelope components do not comply with the Discussion of qualifying requirements, Section 1312, but qualify for Exception 1 ❑ 2 ❑ 3 ❑ 4 ❑ 5 ❑ exceptions in instructions Portions of the building that qualify: section. The plans /specs show compliance in the following locations: 2. Air Leakage (Section 1312.1.1) Plans /Specs $1 Complies. Plans require that penetrations in the building envelope are sealed and that Stow complince by windows and doors are caulked, gasketed or weatherstripped. including a drawing The plans /specs show compliance in the following locations: sheet, detail number, -` specification section I A C�+U�pal� N5 and/or subparagraph. (`- 3. Suspended Ceiling (Section 1312.1.2.1) 181 Complies. Building plans do not show suspended ceilings used to separate conditioned space from unconditioned space. No exceptions permitted. 4. Recessed Light Fixtures (Section 1312.1.2.2) ® Complies. The building plans do not show recessed light fixtures installed in ceilings separating conditioned spaces from unconditioned spaces. ❑ Exception. The building plans require that fixtures installed in direct contact with insulation be insulation coverage (IC) rated. The plans /specs show compliance in the following locations: 5. Moisture Control (Section 1312.1.4) NJ Complies. A one -perm vapor retarder is installed on the warm side (in winter) of all exterior floors, walls and ceilings, and a ground cover is installed in the crawl space for both new and existing buildings where insulation is installed. The plans /specs show compliance in the following locations: ❑ Exception. All new or altered building envelope components do not comply with the vapor retarder requirements of the code, but qualify for an exception. Note applicable exception. Section 1312.1.4, Exception 1 ❑ 2 ❑ Portions of the building that comply: I I Climate 6. Climate Zones Zones lid Zone 1 - A building site is in Climate Zone 1 if its elevation is less than 3000 feet above sea level and it is in one of the following counties: Benton, Columbia, Clackamas, Clatsop, Coos, Curry, Douglas, Jackson, Josephine, Lane, Lincoln, Linn, Marion, Multnomah, Polk, • Tillamook, Yamhill, or Washington N ❑ Zone 2 - Building sites not in Zone 1, or where construction site elevation is 3000 feet or higher in Zone 1, are in Zone 2. 3 -1 <a r L" fr 3913 Vii THOMAS J. KRIZ " 0 G , C1 OF 0' Form 3b Project Name: Page: PRESCRIPTIVE PATH Part 1 of 4 Glazing Conditioned Percent Space ZZ7O 1 _ SG Z8.3 x 100 = 40.3 Calculation Semi - See instruction section Conditioned X 100 = fora discussion of Space glazing percent calculation. Conditioned Mechanical - X 100 = Penthouse in ow rea Exterior Wall Area Glazing (total rough frame ft') (gross f) Percent Windows From Worksheet 3d, Window Thermal Performance' Window Shading Coefficient place the highest (from Worksheet 3d) (from Worksheet 3d) Overall Window U- factor and highest ) , 40 Center-of -Glass SC. Notes 1 From Worksheet 3d, place the highest Overall Window U- factor or write -in MA (Minimum Assembly). See "Window Requirements" in table on the following page for specific MA requirements. 2 From Worksheet 3d, place the highest "center -of- glass" shading coefficient (SC) for glass or write -in MA (Minimum Assembly). See "Window Requirements" in the following table for specific MA requirements. Shading Coefficient (SC) can be calculated from the Solar Heat Gain Coefficient using the equation: SC = SHGC + 0.87. Manufacturers data may also be used to document SC. Wall / Insulation Type R - Value Walls Insulation Only U- Factor See instruction � `_ or section fora P- I9 -.err r- er _ rte. 1 ( 4 or 6 discussion of wall requirements. or or Below -Grade R -Value Walls Below -Grade Walls Insulation Only U - Factor (Min. R -7.5) (Max. 0.11) See instruction section or - for a discussion of below grade wall requirements. Notes 3 Submit Worksheet 3a for each calculated assembly U- factor 3 -2 / • . _ Form 3b Project Name: Page: PRESCRIPTIVE PATH Part 2 of 4 Code Requirements - Zone 1 _ Discussion of these requirements in the instruction section. ZONE 1 Wall Requirements _ Window Requirements Wall / Insulation Type Max. Glazing R -Value U- Max. U- Factor Max. Shading Fraction` Insulation Only Factor Coefficient U to 15% CMU 'Masonry wfnte loose fill' insulation N/A 0.30 p Masonry or concrete w /cont. exterior insulation 1.4 or 0.300 0.540 0.57 CMU Masonry w /integral rigid fill insulation N/A 0.210 Masonry or concrete w /interior insulation 11 or 0. 130 Up to 30% Masonry or concrete w /cont. exterior insulation 2.8 or 0 . 210 0.540' 0.57' Frame (wood or metal framing) 13 or 0.130 Other (provide short description) 13 or 0.130 CMU Masonry w /integral rigid fill insulation N/A 0.210 Masonry or concrete w /interior insulation 11 or 0.130 Up to 40% Masony or concrete w /cont. exterior insulation 2.8 or 0.210 0.370 0.35 Frame (wood or metal framing) 13 or 0. 130 Other (provide short description) 13 or 0.130 Code Requirements - Zone 2 Discussion of these requirements in the instruction section ZONE 2 Wall R_ equirements _ Window Requirements Wall / Insulation Type Max. Glazing R -Value U- Max. U- Factor Max. Shading Fraction` Insulation Only Factor Coefficient Up to 15% CMU 'Masonry w/integral loose fill' insulation N/A 0.300 .30 > > Masonry or concrete w /cont. exterior insulation 1.8 or 0.270 0.500 0.57 CMU Masonry wfintegral rigid fill insulation N/A 0.160 Masonry or concrete w/interior insulation 13 or 0.090 • Up to 30% Mason or concrete w /cont. exterior insulation 4.3 or 0.160 0.500' 0.57' Frame (wood or metal framing) 19 or 0.090 Other (provide short description) 19 or 0.090 CMU Masonry w/integral rigid fill insulation N/A 0.160 Masonry or concrete w/interior insulation 11 or 0.090 Up to 40% Masony or concrete w /cont. exterior insulation 2.8 or 0.160 0.370 0.43 Frame (wood or metal framing) 13 or 0.090 Other (provide short description) 13 or 0.090 Notes 4 The Simplified Trade -off Approach must be used if glazing fraction exceeds allowable percentages. 5 Minimum weight of masonry and concrete walls = 45 Ib/ft2 of wall face area 6 All cores to be filled. At least 50% of cores must be tilled with vermiculite or equivalent fill insulation. 7 rrescnpuve raft tivinimurn rtssemoiyf is a uouoie -giazeo winnow wan a u.o roar air space, iow-e coating to < = u.au/ aria aluminum frame. rvw shading coefficient description is a tinted outboard pane of glass. 6 All cores except bond beams must contain rigid insulation inserts approved for use in reinforced masonry walls 4%',,, 9 Batt insulation installed in metal or wood frame walls shall be insulated to the full depth of the cavity, up to 6 inches in depth. 10 Prescriptive MA Minimum Assembly) is a double lazed window with a 0.5 inch argon filled coating ( 0.05) ( y) y g space, lower coatin e<= 0.05 and thermal break frame. MA shading coefficient description is a 0.25 -inch thick glass with low-e coating (e <= 0.05). Zone 1 includes a tinted outdoor pane. 3 -3 • Form 3b • Project Name: Page: PRESCRIPTIVE PATH Part 3 of 4 Roofs/ R -Value U-Factor Ceilings Roof / Ceiling" Insulation Onl Max 0.050) See instruction section (Mi R - 19) for a dicussion of e -19 t p Ika i fora (Na -" pi-' -� W OOO -te— le R - 19 or roofs /ceilings. ' AboD JO l'$r Notes 11 Write -in a short description for assembly with the lowest insulation R -value or the highest assembly U- factor. 12 Submit Worksheet 3b for each calculated roof /ceiling assembly U- factor. Skylights Includes glazed Conditioned 11 smoke vents. Space X 100 = See instruction Semi - Conditioned section fora Space flG _ X 100= dicussion of skylights. Conditioned Mechanical tJA T X 100 = PAnthnuen Skylight Area Roof /Ceiling Area Skylight (total rough (gross R2 frame ft2) (9 ) Percent" Skylights From Worksheet 3d, place the highest Skylight Thermal Performance" Skylight Shading Coefficient' Overall Vertical WAMOw U - factor and (from Worksheet 3d) (hoer Worksheet 3d) highest Center -of - Glass SC. Code Compliance Option Thermal Performance Shading Coefficient Requirements Overall Vertical U - Factor Center of Glass SC Performance U -1.230 for overall assembly in overhead plane SC -0.47 center -of -glass Minimum Assembly (MA) Double glazed, 0.5 -inch airspace N/A Notes 13 Skylight percentage area is based on total skylight and smoke vent rough frame area divided by total conditioned roof area. Percentage must not exceed 6 percent of total roof /ceiling area in conditioned building space. The Simplified Trade -off Approach must be used if glazing fraction exceeds allowable percentages. 14 From Worksheet 3d, place the highest Overall Vertical U -factor or write -in MA (Minimum Assembly). See "Skylight Requirements" in table above for specific MA requirements. to From Worksheet 3d, place the highest *centerof- glass" shading coefficient (SC) for glass. See "Skylight Requirements" in the following table for specific MA requirements. Shading Coefficient (SC) can be calculated from the Solar Heat Gain Coefficient using the equation: SC = SHGC + 0.87. Manufacturers data may also be used to document SC. f •., 3-4 Form 3b Project Name: Page: PRESCRIPTIVE PATH Part 4 of 4 Floors Floors over Unconditioned Spaces R -Value U- Factor See instruction Insulation Only section for a dicussion of floors. Heated Concrete Slab Edge R - Value Insulation Only Heated Slab -on -Grade (Section 1312.1.2.4) ❑ Complies. Building plans show insulation extending downward from the top of the slab a minimum distance of 24 inches or downward and under the slab for a combined minimum distance of 24 inches or to the bottom of the thickened edge of the of slabs used as a foundation. The plans /specs show compliance in the following locations: Notes 18 Write -in a short description for assembly with the lowest insulation R -value or the highest assembly U- factor. 17 Submit Worksheet 3c for each calculated floor assembly U- factor. It Write -in a short description for Heated Slab, which has heat, integrated into slab such as hydronic heat. If more than one floor type, enter the lowest insulation R -value or the highest component U -factor of any floor. Code Compliance Options Component Min. R -Value Max. U- Require- Insulation Only Factor 171Pntc Floor over Unconditioned Spaces 11 or 0.070 Component Climate Zone 1 Climate Zone 2 Heated Concrete Slab Edge, Min. R -Value 7.5 I or I 10 .0 Doors Doors U- Factor See instruction R - Valu e Center -of -Panel section for a with leaf width greater than 4' Insulation Only (Max. 0.20) dicussion of doors. ( (Min. R -5) or Notes 19 Write -in a short description for Doors. If more than one door type, enter the lowest insulation R -value or the highest center -of -panel U -factor of any door. Glazing in these doors is exempt from U -factor and SC requirements. Doors with a leaf width 4-ft or less and overhead coil doors are exempt. c tSf x • 3 -5 I Worksheet 3a (Cont.) Project Name: Page: Wall U- factors Aluminum (a) (b) ( c) (d) Siding on Layer Description Detail R - value 4. Stud Wall See Table 3a for R- : :■ Exterior Moving Air 0.17 values of framing & A Exterior Finish insulation. -; EIS 1 's B Rigid Insulation See Table 3b for R- C Concrete values of aluminum D Framing & Insulation siding, plywood sheathing and �� E Gypsum Wallboard gypsum wallboard 't°; �--4 Interior Still Air 0.6E See Table 3d for R- — 1. Total column (d) 2. Assembly U- factor (Invert the amount in line 1) Generic (a) (b) (c) (d) Wall Layer Description Detail R -value See tame 3a for R e . ■ Exterior Moving Air o- t 7 values of framing r , , ■ A c tc., t/ a_ 0, (A & insulation. B + I N�� / 3. 6 - See Table 3b for R " ` : ,,,. a . : � ,w �.1 �G►j2Q D s values of building D materials '� f : E See Table 3d for R e F values of exterior � and interior I PAIN surfaces NI ® Iir Interior Still Air C. 4,g 1. Total column (d) /5 %0 2. Assembly U- factor (Invert the amount in line 1) o. o (Q 4- 3-7 Worksheet 3d Project Name: Page: Window /Skylight Schedule u a dditional pages if necessary) Window Properties - List All Window Types in Project (a) (b) (c) (d) (e) (1) (9) (h) (I) (I) (k) Mass t,emer of Overall t,enrer or Documentation Manufacturer's Window Frame Thick- Other (triple pane, air Glass window Glass Name Source Model / No. Type /Class Type Glass Tint ness space, argon, low E) U -factor u- factor SC 44-.)13 ER TruFAI! 451 FI KEO Aw*1. y( l /4" Ate"spkce 0.35 O.So 0.40 low E. Skylight Properties - List All Skylight Types In Project (a) (b) (c) (d) (e) (f) (g) (h) (I) G) (k) • usass t.enrer or Overall Lerner or Documentation Manufacturer's Skylight Frame Thick- - Other nes, air Glass (f Pa Window Glass Name Source Model / No. Type /Class 'type Glass Tint -rWSS Space, argon, low E) U -factor v- factor SC Column Instructions (a) Enter the name of the window or skylight product. It is recommended that you choose a name that corresponds with that used on project plans and specifications. (b) Provide documentation source. Write -in "NFRC" if window is rated through NFRC 100-97 Procedure for Determining Fenestration Product Thermal Performance. Enter all columns except (i). Write -in "ASHRAE Default W/Mfg COG" if Center -of -Glass U -factor and Shading Coefficient is available from glass manufacturer. Enter all columns. Columns (i) and (k) from manufacturer's data sheet. Write in " ASHRAE Default" if only descriptive parameters of window are known. Enter all columns. Columns (i), (j), and (k) from ASHRAE default table. (c) If Document Source is either "NFRC" or " ASHRAE Default W/Mfg COG," enter the manufacturer's model number. (d) For windows, choices are Fixed, Operable, or Curtain Wall. For Skylights, choices are Manufactured or Site Built. (e) Choices am wood, vinyl, reinforced vinyl, aluminum dad, insulated fiberglass, aluminum, aluminium w/thermal break (see definitions for thermal break requirements.) (f) Enter glass tint. Write "dear if there is no tint. (g) Enter glass thickness (h) Include window properties such as argon fill, low -e coating, insulating spacers, etc. (i) COG U -factor from manufacture's data or ASHRAE 2001 Fundamentals Handbook, Chapter 30, Table 4. For NFRC rated products leave blank. (j) Overall U -factor from NFRC rating orASHRAE 2001 Fundamentals Handbook, Chapter 30, Table 4. For skylights value must be for horizontal position. (k) COG Shading Coefficient from manufacture's data or ASHRAE 2001 Fundamentals Handbook, Chapter 30, Table 4. For NFRC rated products SHGC is provided. To convert SHGC to SC. SC = SHGC/0.87. 3 -11 4 Table 3e . : WINDOW U- FACTORS I FRAME TYPE pc• \tea � eel J� ice .0 e \ ,i- e cP \\ �a U- Factors I GLAZING TYPE p \ 6 \a r 0 4 \ � �` � 0 Values are based \p '\ *\ � � app a \pa on the 1997 ¢, t` S \ ,§c` e �� pp y J\ ASHRAE Handbook G P P P `� \C` Single Glazing of Fundamentals Table 29-5, for '/s' glass 1.04 fixed -frame '/4' acrylic/polycarb 0.88 ' 9 3 • ,1:44,•.; windows. Operable Ys" acrylic/polycarb 0 lic/ of cart � e "1011g7 �' A e • windows will have Double Glazing .96 e e�e,c higher U factors. '/4" airspace 0.55 69 e . , e 0 . 53 Many window types /z" alts ace ` are not represented p 0 0. ' x < 0.50 0 50 0.48 in the table, and the W argon space 0.51 0 66 9 0.53 0.52 0.50 user must provide W argon space 0.45 0' ,' 0.54 0.48 0.48 0.45 manufacturer test 4 ° D ouble Glazing, e=0.40 results. ' /a' airspace 0.49 0 5 8 0.51 0.51 0.49 Interpolate between ' /z' airspace 0.40 V057 0.50 0.44 0.44 0.41 emissivities when l/4" argon space 0.43 0 ', 0.53 0.46 0.46 0.44 needed. When manufacturers' data W argon space 0.36 0.53 0.47 0.41 0.40 0.38 are not available, Double Glazing, a =0.20 assume that glass 1/4" airspace 0.45 BIM 0.54 0.48 0.48 0.45 with a pyrolytic Ilh airspace (hard) coating has 0.35 0.53 0.46 0.40 0.39 0.37 ' /4 an emissivity of ' argon space 0.38 Hi= 0.48 0.42 0.42 0.40 0.40, and that glass '/" argon space 0.30 0.48 0.41 0.36 0.35 0.33 with a sputtered *. Double Glazing, a =0.10 (soft) coating has 1 /4' airspace 0.42 an emissivity of v9" 0.52 0.46 0.45 0.43 0.10. • 4 'h" airspace 0.32 0.50 0.43 0.37 0.37 0.35 Krypton gas fills, or 1/4" argon space 0.35 0.53 0.46 0.40 0.39 0.37 krypton/argon 1/2" argon space 0.27 0.46 0.39 0.33 0.33 0.31 combinations, can Double Glazing, a =0.05 be substituted for ' /4` airspace " '" p 0 . 41 e , . n;' 0.51 0.45 0.44 0.42 argon. 1/2" airspace 0.30 0.48 0.41 0.36 0.35 0.33 For glazing gaps ' /a' argon space 0.33 0.51 0.44 0.38 0.38 0.36 between''% inch and I " argon space 0.25 0.44 0.37 0.32 0.31 0.29 ''4 inch, use '4 inch. Other For glazing gaps Glass block 0.51 over 4 inch, use '/ inch. Shaded values do not meet prescriptive path code requirement for climate zone 1; i.e., they are greater than 0.54. For climate zone 1 U- factor must be no greater than 0.54. For climate zone 2 U- factor must be no greater than 0.50. (10 /00) Tables 3 -27 4 Table 3f . - - FENESTRATION SHADING COEFFICIENTS - Shading Coefficient Oregon code Center -of -Glass requires that the Shading Equivalent center - of - glass Glazing Description shading coefficient g Coefficient (SCc) SHGC for non- merchan- dise glazing be less Single Glazing than or equal to 0.57. ' /e" clear 1 f x ' x 87 /a" clear Rk . 41. 8 2 ' Single acrylic or polycarbonate clear e • . . SC = Shading Single acrylic, gray or bronze e . ® r Coefficient for the glazing system Single Ye" polycarbonate, gray or bronze il 4t 0. . . (center of glass) Glass Block sc =SHGC Clear ` 0.87 Frosted 0.50 0.44 Double Glazing -' /e" thick SHGC = Solar clear -7 Heat Gain '® Coefficient (center bronze of glass) green or gray ' bronze, low -e with e=0.2 ,; , " I green or gray, low-e with e=0.2 0 >, e = Infrared ,. f f emissivity of the tinted, low-e with e=0.1 0.57 0.50 glazing layer clear, low -e with e=0.05 0.48 0.42 Double Glazing -' /a' thick Values are from the clear . 8 . 1997 ASHRAE clear, low with e=0.2 ,-'� - Handbook of Fundamentals, clear, low-e on outer pane with e=0.2 a ® a 0 �� . Table 29 - 11. Unless clear, low-e with e=0.1 otherwise noted, • " t ; c low on outer pane with a =0.1 :::: g e ::: tinted glass and bronze - . • reflective glass . , + e coatings are on the bluegreen ®��� •,....,,, � ® ® , outer pane and low green 0.54 0. e coatings are bronze, low -e with e=0.2 0.52 0.45 applied to inner gray 0.51 0.44 pane in double - grazed systems. green, low -e with e=0.2 0.48 0.42 gray, low -e with e=0.2 0.46 0.40 bronze or green, low -e with e=0.1 0.45 0.39 clear, low -e on outer pane with e=0.05 0.43 0.37 .. gray, low -e with e=0.1 0.40 0.35 green, low -e on outer pane with a =0-05 0.35 0.30 titanium reflective 0.33 0.29 blue, low -e on outer pane with e=0.05 0.32 0.28 gray, low -e on outer pane with e=0.05 0.27 0.23 stainless steel reflective 0.26 0.23 Shaded values do not meet prescriptive path code requirement; i.e., the SCc is greater than 0.57. (1 0/00) Tables 3 -29 rage 1 0l 1 j L� SO 9 L Tinted Glasses - - ' ' With PPG's glare reducing tinted glasses, architects can de: facades that make a visual statement while maintaining enE , i = 1 � � efficiency and occupant comfort. g -ii i ::s Solargray® Glass For nearly 40 years, Solargray® glass has been selected fc y commercial structures because of its cool light -gray appear ability to control solar heat gain and glare. Solargray® glass inch insulating unit provides a visible light transmittance of 4 gray color makes Solargray® glass an attractive choice, co almost any other exterior cladding material. Delta Faucet Co. Corporate Office Building Solarbronze® Glass The warmth of its bronze tint has made Solarbronze® float Products: 1" So/argrap® I.G. Units popular glass solution since 1959 for commercial buildings. Location: Indianapolis, Indiana Solarbronze® glass reduces solar heat gain and glare whit( visible light transmittance of 48% in a one inch insulating un Architect: Cooler, Schubert, Olds & Solarbronze® glass imparts a subtle richness from the exte Associates adds a warm glow to interior decors without noticeably influE Click here for more details on this project. color. Click here for a listing of additional projects using Solargray®. Click here to view Architectural Glass Specifications for this PPG glass products that can be used to build Section 8800 Specifications for your projects. Solargray® & Solarbronze® Performance - One Inch Insulating Glass Unit Comparison Using 1/4" (6mm) Glass Visible Light Winter Light Product Shaing Gain I Transmittance Nighttime U -value Coefdficient (LSG) Uncoated Solargray 1/4" /6mm, Monolithic 44 1.09 0.66 0.77 Solarbronze 1/4" /6mm, Monolithic 53 1.09 0.72 0.85 Solargray + 1/2" Air + Clear, I.G. Unit 40 0.48 0.52 0.89 Solarbronze + 1/2" Air + Clear, I.G. Unit 48 0.48 0.58 0.96 SUNGATE Low - Solargray + 1/2" Air + Sungate 100 (3) I.G. Unit 36 0.31 0.40 1.06 Solarbronze + 1/2" Air + Sungate 100 (3) I.G. Unit 44 0.31 0.45 1.13 Solargray + 1/2" Air + Sungate 500 (3) I.G. Unit 37 0.35 0.45 0.95 Solarbronze + 1/2" Air + Sungate 500 (3) I.G. Unit 44 0.35 0.52 0.98 SOLARBAN Solar Control Low - E Solargray + 1/2" Air + Solarban 60 (3) I.G. Unit 35 0.29 0.32 1.25 Solarbronze + 1/2" Air + Solarban 60 (3) I.G. Unit 41 0.29 0.36 1.32 1 2 3 4 itt 114` {6rtun) -: • 114" (6rnm) �y Glass Clear Glass t5 ' Outside 'w-4,-- Inside http : / /www.ppg.com/gls_commercial /products /solargray.asp 04/30/2004