Loading...
Specifications 1 PROJECT MANUAL FOR "a RECEIVED ;MAY 14 2004 CITY OF TIGARD ' TIGARD HIGH SCHOO1 U LDING DIVISION ADDITION / REMODEL PHASE TI I 1 _ Tigard - Tualatin School District ' 6960 Sandburg Road Tigard, Oregon 97223 May 3, 2004 1 11I • O a L w� ' D U L L O L S O N W E E K E S PL-01 Covtu FxiotaQ SET NO. 1 ' PROJECT MANUAL FOR: r 1 TIGA ' II HIGH SCHOOL ADDITION / REMODEL PHASE II for 1 ' (OWNER) Tigard - Tualatin School District ' 6960 Sandburg Road Tigard, Oregon 97223 (ARCHITECT) Dull Olson Weekes Architects, Inc. 319 SW Washington St., No. 200 ' Portland, OR 97204 PH: 226-6950 / FAX: 273-9192 1 ozD Ar, 2282 OF 3, 2004 TABLE OF CONTENTS I DIVISION 0 - BIDDING REQUIREMENTS, CONTRACT FORMS, AND CONDITIONS OF THE CONTRACT By General Contractor I DIVISION I GENERAL REQUIREMENTS By General Contractor 1 DIVISION 2 - SITE WORK Section 02010 Sitework General Requirements ' 02060 Building Demolition 5 . 02200 Site Demolition 4 02315 Earthwork 4 02316 Trenching, Back and Compaction 8 02350 Geotextile Fabric 7 02370 Slope Protection and Erosion Control 3 02510 Exterior Water Distribution 6 I 02620 Foundation Drainage 6 02630 Storm. Drainage System c i 02740 Asphalt Concrete Paving 5 I 02750 Site Concrete 12 02800 Site Furnishings 2 02810 Irrigation 8 I 02920 Soil Preparation 4 02930 Lawns 02950 Plant Material 4 02990 Landscape Warranty 4 I 2 DIVISION 3 - CONCRETE 1 Section 03100 Concrete Formwork 5 03201 Reinforcing and Concrete • 10 03600 Grout 03930 Composite Fiber Reinforcement 4 I 6 DIVISION 4 - MASONRY I Section 04100 Mortar and Masonry Grout 4 04320 Veneer Masonry System 7 I DIVISIONS METALS Section. 05120 Structural Steel 05210 Steel Joists 6 I 05310 Metal Deck 6 05400 Cold - Formed Metal Framing 4 5 05500 Metal Fabrications I 05515 Metal Ladders 11 05800 Expansion Control • 2 3 I I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J TOC - Printed 5/3/04 • I TABLE OF CONTENTS I DIVISION 6 - WOOD & PLASTIC Section 06112 Framing and Sheathing 6 0618] Glue- Laminated Structural Units 4 I 06200 Finish Carpentry 5 06410 Custom Casework 10 I DIVISION 7 - THERMAL & MOISTURE PROTECTION Section 07130 Bentonite Waterproofing 3 I 07160 - Dampproofing 3 07212 Board Insulation 2 07213 Batt and Blanket Insulation 3 07250 Fireproofing 7 I 07260 Intumescent Mastic Fireproofing 4 07270 Firestopping 6 07420 Prefinished Composite Building Panels 4 07530 Membrane Roofing 1 2 I 07533 Single Ply Membrane Roofing 7 • 07611 Preformed Sheet Metal Roofing 7 07620. Sheet Metal Flashing and Trim 5 I 07631 Gutters and Downspouts 4 07710 Manufactured Roof Specialties 2 07820 Aluminum Framed Skylights 6 6 I 07900 Joint Sealants 8 DIVISION 8 - DOORS & WINDOWS I Section 08000 Door and Relite Schedule 21 08110 Metal Doors and Frames 08210 Wood Doors 5 I 5 • 08255 Integrated Metal Door Assemblies • 4 08305 Access Doors 2 08331 Coiling Doors 3 I 08380 Acoustic Door and Relite Assemblies 4 08410 Aluminum Entrances and Storefront 7 08700 Door Hardware 08800 Glazing 12 I . 7 DIVISION 9 - FINISHES I Section 09001 Interior Finish Legend 09100 Metal Support Systems 5 09120 Ceiling Suspension System 3 1 09220 Portland Cement Plaster (Stucco) 8 09260 Gypsum Board Systems 5 09311 Ceramic Floor Tile 5 09321 Ceramic Wall Tile 4 I 09511 Suspended Acoustical Ceilings 09512 Adhesive Applied Acoustical Ceilings 3 09520 Acoustical Wall Panels 3 09605 Concrete Floor Vapor Emission Sealer 3 I 3 • 09650 Resilient Flooring 5 09680 Carpeting 5 I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II. MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J TOC -2 Printed 5 /3/04 I TABLE OF CONTENTS ' 09830 Elastomeric Coatings 09860 Graffiti Resistant Coatings 4 09900 Painting • 3 09950 Wall Coverings 9 DIVISION 10 - SPECIALTIES • Section 10100 Visual Display Boards 10120 Tacksurfaces 4 10170 Plastic Toilet Compartments 3 10251 Clocks 10400 Identifying Devices 10508 Metal Lockers 8 8 10522 Fire Protection Specialties 4 10650 Operable Partitions 3 10800 Toilet and Bath Accessories 4 4 DIVISION 11 - EQUIPMENT Section 1 1 130 Audio — Visual Equipment 11600 Fume Hoods 3 2 tIVISION 12 - FURNISHINGS Section 12345 Laboratory Casework 12381 Music Specialty Casework 3 12512 Horizontal Louver Blinds 4 12693 Entry Mats 3 3 DIVISION 13 - SPECIAL CONSTRUCTION 1 Not Used.. • DIVISION 14 - CONVEYING SYSTEMS 1 14245 Hydraulic Passenger Elevator 10 DIVISION 15 - MECHANICAL Section 15050 Basic Mechanical Materials and Methods 15060 Pipes and Pipe Fittings 18 I 15090 Supports and Anchors 15100 Valves 4 15240 Mechanical Sound and Vibration Control 2 15250 Mechanical Insulation 2 1 3 15300 Fire Protection 15400 Plumbing 4 15500 Heating, Ventilation and Air Conditioning 6 15750 Heat Transfer 3 15850 Air Handling 1 15875 UVC Fixtures for HVAC Equipment 6 2 1 15880 Air Distribution 6 15900 Controls 40 15990 Testing, Adjusting, and Balancing 6 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE I1 MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 231 Printed 5 /3/04 TOC-3 TABLE OF CONTENTS ' DIVISION 16 - ELECTRICAL . Section 16050 Basic Electrical Materials and Methods 8 I16110 Conduits, Raceways and Fittings 4 16120 Conductors 16130 Boxes 3 ' 16140 Wiring Devices 2 16170 Circuits and Motor Disconnects 2 16180 Elevator Power Module Switch 2 16190 Supporting Devices 3 1.6195 Electrical Identification 2 16425 Switchboards 2 16450 Grounding 2 ' 16460 Energy Efficient Dry Type Transformers 2 16470 Panelboards 2 16475 Overcurrent Protective Devices 2 1 16500 Lighting Fixtures and Lamps 3 16723 Fire Alarm and Detection System, 16730 Intercom and. Paging System 3 3 16735 GPS Wireless Clock System 4 ' 16740 Data, Telephone, and CATV Systems 16900 Lighting Controls 6 END OF TABLE OF CONTENTS 1 I 1 I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE .1. MAY 04 TIGARD — TUALATIN SCI -TOOL DISTRICT 231 -roc-4 Printed 5/3/04 • 1 • I SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS I PART 1 - GENERAL 1.01 DESCRIPTION I A. Requirements Included: Provide all materials, labor and equipment required to install complete mechanical work. I 1.02 QUALITY ASSURANCE A. Codes and Standards: Comply with the provisions of the following codes, standards and specifications, except where more stringent requirements are shown or specified: I 1: State of Oregon Structural Specialty Code. 2. State of Oregon Mechanical Specialty Code. 3.. State of Oregon Plumbing Specialty Code. I 4. State of Oregon Uniform Fire Code. 5. • ' NFPA and other Standards referenced in the above codes. B. Permits, Licenses, Fees, and Taxes: Obtain and pay for all permits, licenses, fees and • taxes I applicable to this project as required by law. C. Drawings: Do not scale drawings for roughing -in measurements, nor use as shop drawings. Make field measurements and prepare shop drawings as required. Coordinate work with shop drawings I of other specification divisions. Field Wiring: It is the intent of these specifications that all systems shall be complete and operable. Refer to all drawings and specifications, especially the electrical drawings, to determine I voltage, phase, circuit ampacity and number of connections'provided.' Provide all necessary field wiring and devices from the point of connection indicated on the electrical drawings. All equipment shall be installed in compliance with the Electrical Code and the equipment's UL listing. Bring to the attention of the Architect in writing, all conflicts, incompatibilities, and /or I discrepancies prior to bid or as soon as discovered. 1.03 SUBMITTALS ' Installation Submittals: Clearly indicate which model, size; style, and options are to be provided. IA. Submit all equipment submittals bound together in groups. Deliver all at one time. Clearly indicate which model, size, style and options are to be provided. Arrangement of mechanical equipment has been based on items of specific manufacturer intended as somewhat typical of several makes which may be approved. ' B. Wiring Diagrams:. Submit complete wiring diagrams showing field - installed wiring and devices for all equipment requiring same. I C. Submittal Review: Comply with the contract documents where deviations, discrepancies, and conflicts between the submittals and the contract documents are discovered prior to or after the review process: I D. Project Record (As- Installed) Drawings: l... Obtain and pay for reproducible drawings or electronic media from Architect. 2: . Keep Drawings clean, undamaged, and up to date. I 3. Record and accurately indicate the following: a. Depths, sizes, and locations of all buried and concealed piping. b. Locations of all clean -outs. . I c: Changes, additions, and revisions due to change orders, obstructions, etc. Eradicate extraneous information. d. Locations of tracer wire terminal points. I 4. Make Drawings available when requested by Architect for review. ' 02(154 ' 'TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050-1 I SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS I 5. Submit as part of the required Project Closeout documents. Final submittal will be in the form of reproducible drawings. 6. Quality of entire set of project record drawings to match the quality of the contract I documents; quality to be judged by Architect. Computer -aided design drafting (CADD) shall be used to complete project record drawings. Use standards set in contract documents. Note field modifications, all addenda and change order items on project record drawings. If deficiencies are found in either the quality or the accuracy of the drawings, they will be returned unapproved. Additional review of subsequent submissions shall be at the contractor's expense. E. Operating and Maintenance Manuals: Submit three (3) sets of Operating and Maintenance I Instructions, including manufacturer's service data, wiring diagrams and parts lists for all major items of equipment, valve charts, balancing data, final control diagrams showing final set points, and any additional equipment added by change order, bound in three -ring, vinyl or canvas covered, loose -leaf binders organized with index and thumb -tab markers for each classification of I equipment or data. Comply with provisions of Section 01700 where applicable to the mechanical work. F. Record Drawings once approved shall be placed at: I 1. District archives. 2. District operation and maintenance department. 3. The school; laminate this set. G. Instruction Manual: Submit separate Instruction Manual 30 days prior to scheduling the required I Instruction Period. Include the following: 1. Description of each system and operational sequences. 2. Seasonal system adjustments. 3. Description and normal settings for time clocks, thermostats, fan and other motor switches, etc. 4. Normal valve settings. • 5. Emergency measures upon system failure. 6.. Cross reference information furnished by manufacturer in the Operating and Maintenance Manual above. 7. Operation and maintenance manual once approved shall be placed at: a. District archives. b. District operation and maintenance department. c. The school. 8. Provide laminated control drawings and wiring diagrams at each mechanical system (i.e. I air handler, boiler, etc.) if not provided under 15900. 1.04 STORAGE AND HANDLING A. Delivery: Deliver to project site with manufacturer's labels intact and legible. I B. Handling: Avoid damage. C. Storage: Inside protected from weather, dirt and construction dust. Where necessary to store outside, elevtite well above grade and enclose with durable, waterproof wrapping. • PART 2 - PRODUCTS I 2.01 GENERAL A. General: Provide all new materials and equipment, identical to apparatus or equipment in 111 successful operation for a minimum of two years. Provide materials of comparable quality omitted here but necessary to complete the work.. Maximum allowable variation from stated capacities, minus 5% to plus 10% as approved in each case. III B. Compatibility: Provide products which are compatible with other portions of the work and provide products with the proper or correct power and fuel - burning characteristics, and similar adaptations for the project. i 020.54 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -2 SECTION 15050 ' BASIC MECHANICAL MATERIALS AND METHODS C. Equipment scheduled by performance or model number shall be considered the basis of the design. If equipment of other specified manufacturer's provided in lieu of the design equipment the ' contractor is responsible for all changes and costs which may be necessary to accommodate this equipment, including different sizes and locations for connections, different electrical characteristics, different dimensions, different access requirements or any other differences which ' impact the project. 2.02 MOTORS A. Manufacturers: General Electric, Lincoln, Baldor, Wagner, Westinghouse or accepted substitute. Where selection of motor manufacturer is within Contractor's control (independent of mechanical equipment selection), provide motors produced by a single manufacturer to the greatest extent possible. B. Temperature Rating: Class B insulation, except where otherwise indicated or required for service indicated. C. Starting Capability: As required for service indicated, but not less than 5 starts per hour. ' D. Phases and Current: 1/3 horsepower and smaller capacitor -start single- phase; 1/2 horsepower and larger, squirrel -cage induction polyphase. Coordinate with actual current characteristics; specified in Division 16 and use no 230 /460 voltage motors on 208 voltage power or vice versa. E. Service Factor: 1.15 for polyphase; 1.35 for single - phase. F. Construction: General purpose, continuous duty; NEMA design "B ", except "C" for high starting ' torque applications. G. Frames: For single phase motor sizes NEMA No. 48, except 56 for heavy -duty applications. NEMA "T" frames for 1 horsepower and larger polyphase motors. H. Bearings: Ball or roller, and design for thrust where applicable; shaft seals and regreasable, except provide permanently sealed where not accessible for greasing. Sleeve -type bearings permitted only where indicated for light -duty fractional horsepower motors. Enclosure Type: Open drip -proof for normal concealed indoor use, guarded where exposed to employees or occupants. Type II for outdoor use, except weather- protected Type I where adequately housed. ' J. Overload Protection: Built -in thermal with internal sensing device for stopping motor, and for signaling where indicated on single phase motors. K. Speed: Not faster than synchronous speeds of 1800 RPM except on some pumps as approved in 1 each case. L. Efficiency: The manufacturer's highest efficiency motors tested under procedures recommended ' by NEMA (IEEE Standard 1 12, Test Method B). Minimum 86% efficiency at 3 HP increasing to 91% above 15 HP. Submit manufacturer's data if motor nameplate does not indicate minimum efficiency. M. Motors operated by Variable Frequency Drives shall be inverter rated duty motors. 2.03 STARTERS AND SWITCHES • A. Manufacturers: General Electric, ABB, Cutler - Hammer Square D, Furnas. Provide starters by same manufacturer throughout project. B. General: Provide each motor with starter or switch as approved and recommended by manufacturer of motor or equipment of which motor is a part. C. Starter Characteristics: Type I general purpose enclosure with padlock ears and supports for mounting as indicated. Starter type and size as recommended by motor manufacturer. Use no starter smaller than NEMA Size 1. 02(04 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -3 I SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS I • D. Manual Switches: Provide on motors 113 horsepower and smaller except where automatic control or interlock is indicated. Include pilot light. Provide overload protection where not protected by internal motor overload protection. I E. Magnetic Starters: Provide for 1/2 horsepower and larger motors, and for smaller motors on automatic control or with interlock switch. Include pilot lights, reset, trip -free relay on each phase, and devices for coordination with control system (including 120 volt transformer for control circuit I where service exceeds 120 volts). Provide automatic ambient temperature compensation for starter heaters. 2.04 DRIVES I A. Acceptable Manufacturers: Dayton, Gates, Browning. B. General: "V" section belt drives, multiple as required, sized on 1.5 times installed motor I horsepower. Provide standard slide rails or approved means of adjustment for each motor with belt drive. Use standard section belts and no sheave smaller than cataloged industry standard; provide countersunk center on shaft ends to receive speed counter tip. Variable pitch sheaves are approved only for initial balancing on variable frequency driven fans. Final drives must be fixed I sheave. Coordinate installation with balancer. 2.05 SOLID - STATE, VARIABLE -SPEED MOTOR CONTROLLERS A. General: Controllers listed and labeled as a complete unit and arranged to provide variable speed . I of a standard NEMA Design B 3 -phase induction motor by adjusting output voltage and frequency of controller. Designed and rated by the manufacturer for the type of load (e.g., fans, blowers, and pumps) used and also approved by the manufacturer for the type of connection used between the motor and load (direct connection or power transmission connection). B. Isolation Transformer: 1 -to -1 ratio, with capacity coordinated by the manufacturer for the controller, motor, drive, and load combination. I C. Ratings: I. Output Ratings: 3- phase, 6 to 60 Hz, with voltage proportional to frequency throughout I the voltage range. 2. Starting Torque: 100 percent of rated torque, or as indicated. 3. Speed Regulation: Plus or minus 1 percent. 4. Ambient Temperature: 0° C to 40° C. I 5. Efficiency: 95 percent minimum features shall at full load, 60 Hz. • D. Isolated Control Interface: Allow the controller to follow one of the following over an 1 I :1 speed range: 111 1. Electrical Signal: 4 to 20 milliamperes at 24 V. E. Internal Adjustability: Provide the following internal adjustment capabilities: I I. Minimum Speed: 5 to 25 percent of maximum RPM. 2. Maximum Speed: 80 to 100 percent of maximum RPM. 3. Acceleration: 2 to 22 seconds. 4. Deceleration: 2 to 22 seconds. I 5. Current Limit: 50 to 110 percent of maximum rating. F. Self- Protection And Reliability Features: 1. Input transient protection by means of surge suppressors. I 2. Snubber networks to protect against malfunction due to system voltage transients. 3. Motor Overload Relay: Adjustable and capable of NEMA class 10 performance. 4. Notch filter to prevent operation of the controller- motor -load combination at a natural I frequency of the combination. 5. Instantaneous Overcurrent Trip. 6. Loss of Phase Protection. 7. Reverse Phase Protection. i • 8. Under- and Over - Voltage Trips. 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -4 I . , SECTION 15050 I BASIC MECHANICAL MATERIALS AND METHODS 9. Overtemperature Trip. 10. . Short Circuit Protection. I I 1. Disconnect. G. Automatic Reset/Restart: Attempt 3 restarts after controller fault or on return of power to the system following an interruption and before shutting down for manual reset or fault correction. I Provide for restarting during deceleration without damage to the controller, motor, or load. H. Operation and Maintenance Features: Include: I 1. Status Lights: Door- mounted LED indicators to indicate power on, run, overvoltage, line fault, overcurrent, and external fault. 2. Elapsed Time Meter. 3. Panel - Mounted Operator Station: Start -stop and auto - manual selector switches with I 4. manual speed control potentiometer. Johnson Controls N2 connection. I. See Electrical Schedule for feeder size. Size terminal blocks at VFD for feeder size listed. J. Acceptable Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: II. ABB Power Distribution, Inc. 2. Graham 3. Square D Co. I K. VFD for HVAC Units and pumps to be the same manufacturer. . 2.06 GUARDS I A. Provide guards in accordance with State Safety Code and OSHA requirements over all rotating equipment including belts, shafts and couplings. Drive guards over belts and sheaves shall include 2 -1/2" diameter access opening at shaft ends for speed counter. Provide guards inside all air handlers. 2.07 ACCESS PANELS A. Manufacturers: Milcor, Bilco, Elmdor, Karp, Potter - Roemer or accepted substitute. Milcor Style I DW, K, or M panels as required by construction. B. Construction: Fire rated in fire rated partitions and ceilings. Provide flush key cylinder locks on all access panels less than 8' above the floor. Turn keys over to owners at project completion. l Screwdriver latches on all others. 2.08 MISCELLANEOUS STEEL I A. General: Provide all steel as required for adequate support of all mechanical equipment, standard angle or channel, I or H sections as required by application. Provide shop drawings of supports especially constructed for this project. Adequately cross braced and welded pipe stands may be used for supports. Provide suitable base plates for all stands and anchors for all hanging I equipment. Drill or burn support holes in center line of web of structural shapes only, and in only one leg of any one angle, and as far from center of length as possible. B. Paint: Apply one coat of black Rustoleum primer to shop fabricated items before delivery to job; I other painting as specified herein. FICATION MARKERS A. Pipe Markers: 1. See Chart Below: PIPE DIAMETER LETTER SIZE I with insulation I nzusa TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -5 I SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS I 3 /4" through 2- 1/4" . 3 /4" 2 -'h" through 7- 7/8" l- 3/4" I 8" through 10" 2- 'h" Over 10" 3 -'/2" PIPE COLOR I background Acid vent Yellow I Acid Waste Yellow Air Blue I Boiler Blowdown Yellow Boiler Feed Yellow • Boiler Feedwater Yellow I Chilled Water Return Green Chilled Water Supply Green Cold Water Green I Condensate Yellow Condensate Drain Yellow Condensate Return Yellow Condenser Water Return Green Condenser Water Supply Green Deionized Water Green Domestic Cold Water Green Domestic Hot Water Yellow I Domestic Hot Water Yellow Recirculation Fire Sprinkler Red I Heating Water Return Yellow Heater Water Supply Yellow I Heating Water Reverse Return Yellow 140° Hot Water Yellow Natural Gas Yellow I Refrigerant Liquid Yellow Refrigerant Suction Yellow I Sanitary Drain Green Steam Yellow Storm Drain Green I Sump Pump Discharge Yellow Tempered Water Yellow Vacuum Yellow I Vent Yellow 2. Provide direction arrows on all lines. I (12054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -6 Print,' Ild /7A /Ild I SECTION 15050 I BASIC MECHANICAL MATERIALS AND METHODS B. Nameplates: I i. Engraved nameplates, 1/16" thick, laminated 3 -ply plastic, center ply white, outer ply black, letters formed by exposing center ply. 2. Size: 3" by 5" nameplates with 1/4" high letters. I C. Valve tags: 1. Tag to identify what valve is. Example (Hot water shut -off valve for restroom 100 & 101). I 2. 3. Numbered brass tags referring to a valve chart are not acceptable. Provide engraved plastic or laminated plastic tags with chain attachment. I 2.10 PENETRATION FIRE STOPPING A. Through- penetration fire stopping system tested and listed by Underwriters Laboratories. 3M, Metacaulk, SpecSeal, or approved. I B. Select system for proper application based on wall construction, type of penetrating item, wall rating, etc. I PART 3 - EXECUTION • 3.01 LAYOUT AND COORDINATION l A. Site Examination: Before starting work, carefully examine site and all contract Drawings. Become thoroughly familiar with conditions governing work on this project. Verify all indicated elevations, building measurements, roughing -in dimensions and equipment locations before I proceeding with any of the work. B. Utility Locations: The location of all utilities, wires, conduits, pipes, ducts, or other service facilities are shown in a general way only on the Drawings and are taken from existing public records. Ascertain whether any additional facilities other than those shown on the plans may he I present and determine the exact location and elevations of all utilities prior to commencing installation. I C. Sleeves, Inserts, Cast -in -Place Work: Provide sleeves, inserts, anchoring devices, cast -in -place work, etc. which must be set in concrete sequenced at the proper time for the project schedule. D. Coordination: II. Where the work must be sequenced and positioned with precision in order to fit into the available space, prepare accurate scale shop drawings showing the actual physical dimensions required for the installation and submit prior to purchase- fabrication- installation of any of the elements involved in the coordination. I 2. Cooperate with other trades in furnishing material and information for sleeves, bucks, chases, mountings, backing, foundations and wiring required for installation of mechanical items. 3. Coordinate all work with other trades and determine in advance where interfacing of the I mechanical work and other work are required to be connected together. Provide all materials and equipment to make those connections. Submit shop drawings showing required connections where special conditions exist. I . E. Discrepancies: Report immediately any error, conflict or discrepancy in Plans, Specifications and /or existing conditions. Do not proceed with any questionable items of work until clarification of same has been made. Should rearrangement or re- routing of ducts or piping be necessary, provide for approval the simplest layout possible for that particular portion of the work. I F. Related Engineering Services: The cost for all professional engineering services related to Division 15 items of work shall be included in the hid, and will be paid for by the General Contractor. References to "structural engineer" in Division 15 do not refer to the project structural I engineer of record, unless that individual or firm is retained (independently) by the general contractor to perform Division 15 consulting services." I . 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -7 SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS 3.02 MECHANICAL EQUIPMENT WIRING A. Provide all mechanical equipment motors, automatic temperature, limit, float and similar control ' devices required, with wiring complete from power source indicated on Electrical Drawings. B. Provide properly rated motor overload and undervoltage protection and all manual or automatic motor operating devices for all mechanical equipment. C. Equipment and systems shown on the Drawings and /or specified, are based upon requirements of specific manufacturers which are intended as somewhat typical of several makes which may be approved. Provide all field wiring and /or devices necessary for a complete and operable system including controls for the actual selected equipment/system. D. Provide all starters for mechanical motors. Review Electrical Specifications and Drawings to • determine which mechanical motor starters will be provided under the Electrical Specification Sections and provide all others. 3.03 INSTALLATION A. Locating and Positioning Equipment: Observe all Codes, Regulations and good common practice in locating and installing mechanical equipment and material so that completed installation presents the least possible hazard. Maintain adequate clearances for repair and service to all equipment and comply with Code requirements. B. Arrangement Arrange ductwork and piping parallel with primary lines of the building construction, and with a minimum of 7' overhead clearance in all areas where possible. Unless indicated otherwise, conceal all piping and ductwork. Locate operating and control equipment properly to provide easy access, and arrange entire mechanical work with adequate access for operation and maintenance. Give right -of -way to piping which must slope for drainage. Set all equipment level or as recommended by manufacturer. Under no conditions shall beams, girders, footings or columns be cut for mechanical items. Casting of pipes into concrete is prohibited unless so shown on Drawings. C. Anchorage: Anchor and /or brace all mechanical equipment, piping and ductwork to resist displacement due to seismic action, include snubbers on equipment mounted on spring isolators. D. Access Panels: Provide access panels with proper backing reinforcement for all equipment, fire and smoke dampers, dielectric unions and valves requiring service and installed above ceilings, behind walls, or in furring, complete with correct frame for type of building construction involved. Exact size, number and location of access panels are not necessarily shown on Drawings. Use no panel smaller than 12" by 12" for simple manual access or smaller than 16" x 20" where personnel must pass through. E. Adjusting: Adjust and calibrate all automatic mechanical equipment, mixing valves, flush valves, float devices, etc. Adjust flow rates at each piece of equipment or fixture. F. Building Vapor Barrier: Wherever the building insulation vapor barrier is penetrated by mechanical piping, hangers, conduits, ductwork, etc., provide clear self - adhesive tape recommended by the insulation manufacturer around the penetrations. G. Mechanical System Identification: ' 1. Piping System: Indicate each pipe system by its generic name (abbreviated) as shown /scheduled /specified; except vent and drainage piping. Comply with UMC Standard 1 1 -2 / ANSI A13.1 for marker locations, letter sizes, and colors. Include arrows to show direction of flow and "Electric Traced" signs to identify heat cable wrapped piping. - 2. Valve Identification: Tag all valves as directed previously. 112054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -8 SECTION 15050 I BASIC MECHANICAL MATERIALS AND METI -IODS 3. Equipment: Provide engraved plastic- laminate signs at locations of major equipment, primary control devices, emergency equipment, dangerous elements of the mechanical I work and similar places. Provide text of sufficient clarity and lettering, of sufficient size to convey adequate information at each location, and permanently mount in an appropriate and effective location. For systems with multiple rooftop HVAC units, I comply with OMSC 304.5. Comply with recognized industry standards for color and design. H. Concrete Work: Coordinate with other work, particularly other concrete work and accessories. Comply with applicable provisions of Section 03310 for mechanical work concrete, including I formwork, reinforcement, mix design, material's (use mix designs and materials accepted for Division 3 work where possible), admixtures, accessories, (including waterstops), placing of wet concrete, finishing, curing, protecting, testing, submittals and other requirements of the concrete I 3.04 work. PROTECTION A. Protect all work and materials against loss or damage. Close all pipe openings with caps or plugs. At final completion, thoroughly clean and deliver all work and equipment in an unblemished new condition. Keep all motors and bearings in watertight and dustproof covers during entire course of installation. . I B. Protect floors, walls, framing and sheathing where pipe cutting and threading operations are conducted with plastic sheeting under plywood sheets. Extend plastic sheeting beyond the plywood. Clean -up metal cuttings, oil, etc., daily or as necessary to prevent debris from being . tracked beyond the protected area. Damages, as determined by the Architect, due to the pipe . 1 cutting /threading operation shall be repaired by the responsible trade. 3.05 CUTTING AND PATCHING I A. General: Comply with the requirements of Division 1 for the cutting and patching of other work to accommodate the installation of mechanical work. Do all necessary cutting and patching of existing building and yard surfaces required for completion of the mechanical work. Patch to match finish and color of adjacent surfaces. Coordinate work in remodel and new areas to avoid I cutting of new finished surfaces. 3.06 PIPE PENETRATION FIRE STOPPING I A. Install as recommended by manufacturer and in accordance with the product's UL listing. Below are the minimum installation requirements. 1. Install specified penetrating item(s) with required annular spacing in proper size wall or I 2. floor opening. Support penetrating item(s) adequately on both sides of construction. Clean all opening and penetrating item surfaces in penetration area to remove loose debris, dirt, oil, wax, grease, old caulking, etc. 3. If needed or required for gypsum or concrete block walls, install specified galvanized I steel wire mesh or sleeve recessed and centered inside wall around penetrating item(s) so that it is snug against perimeter of opening. . When required, install specified type and depth of backing material in annular space, recessed to required fill depth of fire stopping caulking. I 5. Gun, trowel, and /or pump fire stopping sealant to specified depth in annular space around penetrating item(s). Trowel sealant surfaces flush with wall or floor surfaces to a smooth, defect -free finish. Where required, apply specified size caulking bead around penetrating item(s) at zero annular contact areas and tool smooth. V i 3.07 EQUIPMENT REMOVAL . A. All removed mechanical equipment is the property of the Contractor unless indicated otherwise, . see 'D' below. Disconnect and remove all such equipment from the project property. Cap all piping in walls, below floors, and /or above ceilings in finished rooms. B. Disable electrical circuits by disconnection of both ends and make safe with wire nuts or other I approved methods. Remove conduit to concealed locations. Remove wire to panel or j -box if circuit is used for other devices. 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 1 5050 -9 SECTION 15050 BASIC MECHANICAL MATERIALS AND METHODS C. Reused Equipment: Reconnect piping, wiring and /or controls to restore original equipment functions unless indicated otherwise. D. Rooftop units and Carrier control modules and cabinets are to be delivered to Tigard - Tualatin School District maintenance headquarters in the same condition as found on site. Coordinate with Tigard- Tualatin School District for an inspection of all rooftop units and Carrier control modules. Document condition prior to construction beginning. Any damage or loss to be reimbursed by contractor to Tigard - Tualatin School District at market value determined by Carrier Corporation representative. 3.08 MECHANICAL PAINTING ' A. Minimum Requirements: Comply with minimum requirements of Section 09900, Painting. All mechanical equipment, piping, insulation, etc., exposed in finished areas, storage rooms and other locations except mechanical equipment rooms will be painted under Section 09900. B. Painting Materials: Material shall comply with Section 09900, Painting. C. Uninsulated Piping: Paint black or galvanized uninsulated piping located buried in ground, in concrete or masonry one (1) coat acid - resisting black paint. Paint black or galvanized uninsulated piping exposed to weather one (1) coat black asphaltum varnish. D. Iron Work: Paint hangers, rods, anchors, guides, threads of galvanized pipe, bases, supports, uncoated sheet metal and other iron work without factory finish, exposed to weather, one coat acid - resisting black paint. Apply one (1) coat Dixon's Aluminum Graphite No. 209 paint over the (1) coat primer as recommended by paint manufacturer to all hot metal surfaces. E. Sheet Metal: Apply one coat of zinc chromate to mechanical sheet metal exposed to weather, except no painting required on aluminum or stainless steel. Apply one coat of flat black paint to the inside of unlined ducts behind all grilles and registers. F. Insulated Piping and Other Insulated Surfaces: Paint insulated piping in half - round, split tile, or other inaccessible locations, one (I) coat asphalt emulsion. 3.09 TEMPORARY HEATING AND COOLING A. Comply with requirements of Section 01500. B. Permanent mechanical systems' equipment utilized for temporary heating, ventilating and cooling shall be started with all controls and safeties installed and operational. Start -up shall be done by a factory approved mechanic only. C. Owner's warranties shall not be abridged by contractor's use of the permanent systems' equipment prior to final acceptance. Warranty period shall begin at final completion. Warranty maintenance to be included. 3.10 MECHANICAL WORK CLOSEOUT A. General: Refer to the Division I sections for general closeout requirements. Calibrate all equipment requiring same. B. Record Drawings: Submit record set of drawings as previously specified in this Section. C. Closeout Equipment /Systems Operations: Sequence operations properly so that work of project will not be damaged or endangered. Coordinate with seasonal requirements. Operate each item of equipment and each system in a test run of appropriate duration with the Architect present, and with the Owner's operating personnel present, to demonstrate sustained, satisfactory performance. Adjust and correct operations as required for proper performance. Clean and lubricate each system, and replace dirty filters, excessively worn parts and similar expendable items of the work. 1 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050 -10 I SECTION 15050 ' BASIC MECHANICAL MATERIALS AND METHODS D. Operating Instructions: Conduct a full walk - through instruction seminar for the Owner's personnel who are to be involved in the continued operation and maintenance of mechanical equipment and ' systems. Provide written instructions outlining and explaining the identification system, operational diagrams, emergency and alarm provisions, sequencing requirements, seasonal provisions, security, safety, efficiency and similar features of the systems. See Section 15900 for control operating instruction requirements. Video tape or otherwise record the training session for future playback. Provide three copies (one each with O &M material). END OF SECTION I r I I I 1 I 021154 TIGARD HIGH SCHOOL ADDITION / REMODEL PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15050-11 1 SECTION 15060 PIPES AND PIPE FITTINGS I PART 1 - GENERAL I 1.01 DESCRIPTION A. Provide pipe, pipe fittings and related items required for complete piping system. I B. Related Work: Specified in Section 15090, Supports and Anchors, and in Section 15100, Valves. 1.02 QUALITY ASSURANCE I A. General: ASTM and ANSI Standards are indicated. In addition, special standards are referenced where neither ASTM nor ANSI Standards are applicable. I B. Concealed Plastic Piping: No concealed plastic piping inside the building unless approved by Code or Governing Authorities. C. Definitions: Where piping fluid is not indicated in the following paragraphs, provide similar I piping materials for similar fluids (i.e., "make -up water" = "domestic water "; "wet stand pipe" = "fire sprinkler pipe "; "drainage piping" = "sanitary /storm sewer piping "). D. Provide submittal for all piping. Leave tags and labels on piping to allow field inspection to verify I American Manufacturer. 1.03 STORAGE AND HANDLING I A. Deliver materials to the project site with galvanized pipe manufacturer's labels intact and legible as required by code. B. Provide factory - applied end caps on each length of pipe and tube. Maintain end caps through I shipping, storage and handling as required to prevent pipe -end damage and eliminate dirt and moisture from inside of pipe and tube. Protect flanges and fittings from moisture and dirt by inside storage and enclosure, or by packaging with durable, waterproof wrapping. I PART 2- PRODUCTS 2.01 PIPING MATERIALS I A. Galvanized Steel Pipe: 1. Applications: Aboveground only and 2" and smaller. I a. Natural gas piping on roof b. Sanitary waste c. Rain drain d. Plumbing vent I C. Domestic water for joining existing galvanized piping (distances not to exceed 20') for sizes 3" or larger only. 2. Pipe: Schedule 40, standard galvanized steel pipe, ASTM A -53 or A -106. I B. Black Steel Pipe: 1. Applications: a. Natural gas (Inside Building Only) b. Fire sprinklers c. Heating water d. Steam and condensate 2. Pipe: Schedule 40, standard black steel pipe ASTM A -120 or A -53. 3. Threaded Fittings: For above ground installations only. a. Banded class 120 cast iron fittings, ANSI B16.4 to 125 psi. I b. Compressed Air: Banded class 150 malleable iron fittings, ANSI B16.3 to 150 psi. 4. Welding Fittings: For al underground installations, beveled ends, seamless fittings of the same type and class of piping above. I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -1 Printed 04/30/04 SECTION 15060 1 PIPES AND PIPE FITTINGS C. Cast Iron Soil Pipe: 1. Application: 2" and larger. a. Sanitary waste b. Plumbing vent c. Rain drain 2. Pipe: Hubless cast iron soil pipe, CISPI 301 -90 /ASTM A888. 3. Fittings: a. Hubless Cast Iron Fittings: CISPI 30 -901 or cast iron hub and spigot fittings, ASTM A -74. b. Couplin Underground: Clamp -All Hi -Torq 125, Husky SD4000, Mission Heavy Weight, or approved substitute. c. Couplings Above Ground: Standard couplings meeting CISPI Designation 310 except rain drain couplings in systems greater than 20 feet water column, utilize couplings approved for underground locations. d. Couplings to Steel or Plastic Pipe in Concealed Locations: Fernco "LowFlex" or approved substitute. 4. Manufacturers: Cast iron pipe and fittings — AB &I, Charlotte Pipe, Tyler Pipe. D. Copper Pipe and Tube: I 1. Application: a. Domestic water b. Heating water c. Refrigerant d. Priming lines e. Pressure sewer f. Cooling condensate drain. 2. Pipe: ASTM B88. a. Above Ground Domestic Water, Heating Water, and Pressure Sewer: Type L hard temper copper with soldered joints. b. Underground Domestic Water, Pressure Sewer, and Priming Lines: Type L soft annealed with no joints or type K hard tempered copper with silver soldered joints. c. Refrigerant Piping: ANSI /ASME B31.5 or SAE J 513 -F, "Refrigeration Tube Fittings." Where conflicts occur, B31.5 shall govern. d. Above Ground Sanitary Waste and Vent: Copper tube and fitting DWV, ASTM ' B306. 3. Fittings: Wrought copper solder -joint fittings, ANSI B16.22. 4. Refrigerant Fittings: ANSI/ASME B31.5 or SAE J 513 -F, brazed or flange joints. E. Acid Resistant Pipe: I. Acceptable Manufacturers: Orion, Enfield. 2. Application: Acid sanitary waste and acid plumbing vent. 3. Pipe: Polypropylene plastic pipe, ASTM D2447 or ASTM D4101. 4. Fittings and Jointing Methods: Compatible with the piping system and with equal or better acid resistance and, unless otherwise indicated, made by the piping manufacturer and recommended for the service indicated. Mechanical joint with 300 series stainless steel band. F. Plastic Pipe — Drainage: 1. Application: a. Sanitary waste, below floor only b. Rain drain, below floor and outside tunnels only 2. Pipe: a. Acrylonitrile - butadiene - styrene (ABS) plastic drain, waste and vent piping and fittings (DWV): ASTM D2751 for 4" and 6 "; ASTM D2680 for 8" and larger. b. Poly(vinyl chloride) (PVC) plastic drain, waste and vent pipe and fittings (DWV): ASTM D2665. 3. Fittings: Provide fittings of the type indicated, matching piping manufacture. Where not otherwise indicated, provide fittings produced and recommended for the service indicated by the piping manufacturer. G. Direct Bury Domestic Hot Water Pipe: 1. Carrier Pipe: Type (K) Hard Drawn Copper Tubing conforming to ASTM B -88 in 20 foot lengths. I _. 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -2 Printed 04/30/04 I SECTION 15060 PIPES AND PIPE FITTINGS 2. Insulation: Polyurethane foam with the following minimum characteristics: a. K factor, .13 b. Density 2 pcf c. Closed Cell Content d. 90 -95% in conformance with MIL -I -24172 and ASTM C -591 completely filling the annular space between carrier pipe and jacketing. e. 1.1" thick. I 3. Jacketing Material: High impact, seamless Polyvinylchloride (PVC) Class 12454 -B compound conforming to ASTM 1784, Type 1, Grade 1. 60 mill jacket. 4. Joining Method: Straight lengths of pipe will be joined by solder connection. 5. Fittings and Field Joints: All fittin will be wrought copper in conformance with job I specifications and will be insulated and jacketed with materials supplied by the system supplier and as per manufacturers standard procedures. 6. Anchors: All pipe shall be anchored per system supplier's recommendations. 7. Backfill: Should be tampered compactly in place so as to assure a stable surface. No I rock should be used in the first foot of backfill. 24 inches, top of pipe to grade, of compacted fill shall meet H -20 Highway Loading. 8. Approved Vendors: Insul-8 Copper Pipe System by Rovanco Corp. I H. Direct Bury Heating Water Pipe: 1. Carrier Pipe: A -53 Grade B ERW in Schedule (40). 2. Insulation: Polyurethane foam with the following minimum characteristics: I a. K factor, .13 b. Density 2 pcf c. Closed Cell Content d. 90 -95% in conformance with MIL -I -24172 and ASTM C -591 completely filling I the annular space between carrier pipe and jacketing. Insulation thickness of 1.2" minimum. . g Material: High impact, seamless Polyvinylchloride (PVC) Class 12454 -B compound conforming to ASTM 1784, Type 1, Grade 1. 80 mills thick. I 4. 5. Joining Method: Straight lengths of pipe will be joined by welding. Fittings: All fittings will conform to pipe type and will be insulated and jacketed with materials supplied by the system suppliers and as per manufacturers' standard procedures. 6. Insulation of Straight Joints: After welding and testing, all joints shall be insulated and I sealed as per manufacturer's standard procedures. 7. Anchors: ''/2" thick steel anchor plate is attached to internal pipe and sealed to pipe jacketing as per system supplier's recommendations. 8. Backfill: Should be tamped compactly in place so as to assure a stable surface. No rock should be used in the first foot of backfill. 24 inches, top of pipe to grade, of compacted I fill shall meet H -20 Highway Loading. 9. Approved Vendors: Insul -8 Copper Pipe System by Rovanco Corp. 2.02 MISCELLANEOUS PIPING MATERIALS /PRODUCTS I A. Insulating (Dielectric) Fittings: Provide standard products recommended by the manufacturer for use in the service indicated, and which effectively isolate ferrous from non- ferrous piping (electrical conductance), prevent galvanic action, and reduce corrosion. Victaulic "Clear Flow." I B. Soldering and Brazing Materials: Provide soldering materials as determined by the installer to comply with installation requirements. 1. Tin - Antimony Solder: ASTM B32, Grade 95TA. • I 2. 3. Lead -Free Solder: ASTM B32, Grade HB. Harris "Bridgit" approved. Silver Solder: ASTM B32, Grade 96.5TS. C. Sleeve Seal: Rubber -link pipe wall and casing closure. Thunderline Link -Seal. For fire rated I wall, floor or ceiling penetrations, 3 -M "CP -25" caulk, "No. 303" putty and /or "PSS 7904" sealing system. D. Tracer Wire: 14 gauge, single strand, copper wire with blue insulation for water, green for sanitary I and storm sewers, and yellow for gas. 3M "DBY" direct bury splice kit required at all splices. E. Flex Connection: T -316L stainless steel corrugated inner with T -321 outer braid. Fleronics 400 /H or approved. AGA approved for gas equipment I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -3 Printed 04/30/04 SECTION 15060 PIPES AND PIPE FITTINGS 2,03 BACK FILL MATERIALS ' A. Subbase Materials: A graded mixture of gravel, sand, crushed stone or crushed slag. B. Finely- Graded Subbase Material: Well graded sand, gravel, crushed stone or crushed slag, with 100% passing a 3/8" sieve. C. Backfill Material: Soil material suitable for compacting to the required densities, and complying with AASHTO designation M145, Group A -1, A -2 -4, A -2 -5. or A -3. PART 3 - EXECUTION 3.01 PIPE INSTALLATION A. General: Install pipe, tube and fittings in accordance with recognized industry practices. Install each run accurately aligned with a minimum of joints and couplings, but with adequate and accessible unions and flanges for disassembly, maintenance and /or replacement of valves and equipment. Reduce sizes (where indicated) by use of reducing fittings. B. Tracer Wire: Install tracer wire as close to underground non - metallic water, sanitary and storm sewers and gas pipe in the trench as possible. Tracer wire shall be accessible at grade via all services, valve and meter boxes, curb cocks, cleanouts at the building, manholes (inside the cover near the top), etc. Locate all points on the record as- installed drawings. Splice into utility tracer system where available. Comply with code requirements. 3.02 PIPING JOINTS A. General: Provide joints of the type indicated in each piping system, and where piping and joint as manufactured form a system, utilize only that manufacturer's material. B. Cast Iron "No- Hub ": All joints in accordance with the Cast Iron Soil Pipe Institute (CISPI) Designation No. 310 -90 "Installation Procedures for Hubless Cast Iron Soil Pipe and Fittings For Sanitary and Storm Drain, Waste and Vent Piping Applications." Horizontal runs of 5" and greater shall he braced as indicated in Figure 4 for "rodding" restraints. C. Ferrous Threaded Piping: Thread pipe in accordance with ANSI 82.1; cut threads full and clean using sharp dies. Ream threaded ends to remove burrs and restore full inside diameter. Apply pipe joint compound or pipe joint tape (Teflon) where recommended by pipe /fitting manufacturer, on male threads at each joint and tighten joint to leave no more than 3 threads exposed. D. Solder Copper Tube and Fitting Joints: In accordance with recognized industry practice. Cut tube ends squarely, ream to full inside diameter, and clean outside of tube ends and inside of fittings. Apply solder flux to joint areas of both tubes and fittings. Insert tube full depth into fitting, and solder in a manner which will draw solder full depth and circumference of joint. Wipe excess solder from joint before it hardens. "T- Drill" field formed tees may be utilized where the main is at least two pipe sizes larger than the branch. E. Braze Copper Tube and Fitting Joints: Where indicated, in accordance with ANSI /ASME B31.5. Pass a slow stream of dry nitrogen gas through the tubing at all times while brazing to eliminate formation of copper oxide. F. Plastic Pipe /Tube Joints: Comply with manufacturer's instructions and recommendations, and with applicable industry standards: 1. Making Solvent- Cemented Joints: ASTM D -2865 and ASTM F -402. G. Insulating (Dielectric) Fittings: Comply with manufacturer's instructions for installing unions or fittings. Install in a manner which will prevent galvanic action and stop corrosion where the "joining of ferrous and non- ferrous piping" is indicated. For connections at the main water line (3" in tunnel) provide brass valve or minimum of 12" brass pipe as coupling in place of di- electric union. Continuity of grounding at the main service shall be maintained. H. Changes in Direction: Use fittings for all changes in direction. Run lines parallel with building surfaces. 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -4 Printed 04/30/04 I SECTION 15060 PIPES AND PIPE FITTINGS I I. Line Grades: 1. Drainage Lines: Run at maximum possible grade and in no case less than 1/4" per foot I within building. 2. Vents: Pitch for drainage 1/4" per 10'. 3. Water: Pitch to low points and install hose bib drains. 3' minimum depth of ground cover for all lines outside building unless otherwise noted. I 4. Heating Piping: Pitch 1" to 40' minimum to low point drips or drains. J. Unions and Flanges: At all equipment to permit dismantling and elsewhere as consistent with good installation practice. I K. Expansion: Provide loops, swing joints, anchors, runouts and spring pieces to prevent damage to piping or equipment. I 3.03 MISCELLANEOUS PIPING EQUIPMENT A. Floor, Wall and Ceiling Plates: Chrome plated pressed steel or brass screw locked split plates on all pipe penetrations in finished spaces. I B. Sleeves: At all penetrations of concrete or masonry construction. PVC, 24 gauge galvanized steel or Schedule 40 galvanized steel pipe. Use steel pipe sleeves through beams, footings, girders or columns and for all penetrations of walls or floors below grade. Where floor finish is ceramic tile, I terrazzo, or similar material extend standard steel pipe sleeves 1 -1/2" above finished floor. Fabricate sleeves 1" diameter larger than pipe or insulation. PVC and sheet metal sleeves at non- structural penetrations only. I C. Sleeve Caulking: Caulk insulated pipe with rubber link seal. Grout uninsulated pipe with cement mortar or approved waterproof mastic. All caulking or grouting shall extend full depth of sleeve. Utilize rubber sealing links in lieu of caulking. Install UL sealing caulk, putty and /or system at all penetrations of fire rated walls, floors and ceiling. 3.04 EXCAVATING A. General: Do not excavate for mechanical work until the work is ready to proceed without delay, to I minimize the total time lapse from excavation to completion of backfilling. Comply with all applicable Federal and state safety regulations. B. Width: Excavate for piping with 6" to 9" clearance on both sides of pipe, except where otherwise shown or required for proper installation of pipe joints, fittings, valves and other work. Excavate I for other mechanical work to provide minimum practical but adequate working clearances. C. Depth for Direct Support: For work to be supported directly on undisturbed soil, do not excavate beyond indicated depths, and hand - excavate the bottom cut to accurate elevations. Support the I following work on undisturbed soil at the bottom of the excavations: 1. Piping of 5" and less pipe /tube size. 2. Cast -in -place concrete. I D. Depth for Subbase Support: For large piping (6" pipe size and larger), tanks and where indicated for other mechanical work, excavate for installation of subbase material in the depth indicated, or, if not otherwise indicated, 6" below bottom of work to be supported. I E. Depth for Exterior Piping: Excavate for exterior water - bearing piping (water, drainage) so that the top of piping will not be less than 3' vertical distance below finished grade. F. Depth for Unsatisfactory Soil Conditions: Where unsatisfactory soil condition at the bottom of I excavation exists, excavate additional depth as directed to reach satisfactory soil - bearing condition. Backfill with subbase material, compacted as directed, to indicated excavation depth. I 02054 TIGA.RD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -5 Printed 04/30/04 SECTION 15060 1 PIPES AND PIPE FITTINGS 3.05 DEWATERING A. Maintain dry excavation for mechanical work, by removing water. Protect excavations from inflow of surface water. Pump minor inflow of ground water from excavations; protect excavations from major inflow of ground water, by installing temporary sheeting and waterproofing. Provide adequate barriers which will protect other excavations and below -grade property from being damaged by water, sediment or erosion from or through mechanical work excavations. Comply with local erosion control regulations where applicable. 3.06 BASE PREPARATION A. Subbase Installation: Where indicated, install subbase material to receive mechanical work, and compact by tamping to form a firm base for the work. For 4" and larger piping, horizontal cylindrical tanks and similar work, shape and subbase to fit the shape of the bottom 90 degrees of the cylinder, for uniform continuous support. Provide finely- graded subbase material for wrapped, coated and plastic pipe and tank. Shape subbases and bottoms of excavation with recesses to receive pipe bells, flanged connections, valves and similar enlargements in the piping systems and set bottom of trench at proper pitch and correct elevations with subbase material. B. Concrete Encasement: Where piping under roadways is less than 2' -6" below surface of roadway, provide 4" base slab of concrete to support piping. After piping is installed and tested, provide 4" thick encasement (sides and top) of concrete before backfilling. Provide Class 250 concrete for encasement and slab. 3.07 BACKFILLING , A. Do not backfill until installed mechanical work has been tested and accepted wherever testing is indicated. Install drainage fill where indicated, and tamp to a uniform firm density. Backfill with finely- graded subbase material to 6" above wrapped, coated and plastic piping and tanks, and to center line of other tanks (where recommended by tank manufacturer, use "pea gravel" backfill). Condition backfill material by either drying or adding water uniformly, to whatever extent may be necessary to facilitate compaction to the required densities. Do not backfill with frozen materials. 3.08 CLEANING A. General: Clean all dirt and construction dust and debris from all mechanical piping systems and leave in a new condition. Touch up paint where necessary. B. Domestic Water System: Flush with clean water to eliminate grease, cuttings and foreign matter; run water until clear and free of oil. Chlorinate domestic water as per procedure outlined by Board of Health. • C. Sanitary and Storm Drainage System: 1. Remove construction debris from cleanouts, drains, strainers, baskets, traps, etc., and leave same accessible and operable. Place plugs in the end of uncompleted conduit at the end of the day or whenever work stops. 2. Before final acceptance of completed sewer system, flush and clean the entire system with water. Trap and remove solid material obtained from flushing and cleaning from the new system. Do not allow debris to enter the existing sewer system. , D. Gas and Compressed Air Piping: Blow clear of debris with nitrogen or oil free air. Clean all low point strainers and pockets. E. Heating Water Systems: 1. Use one pound of trisodium phosphate per 50 gallons in the system, or one pound of sodium carbonate for each 30 gallons in the system or one pound of sodium hydroxide (lye) for each 50 gallons in the system. 2. Fill, vent and circulate the system with this solution at design operating temperature. After circulatin for four hours, drain and fill with fresh water. 3. Test for pH and add sufficient amount of the cleaning chemical to obtain a pH between 7 and 8. 4. Clean all strainers and remove start -up strainers (from suction diffusers) after the system has operated for one week. 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -6 Printed 04/30/04 I SECTION 15060 PIPES AND PIPE FITTINGS I F. Refrigeration System Piping: If, for any reason, sanitized and sealed -at- the -mill tubing is not used, clean the tubing as follows: 1. Wipe each tube internally with a dry, lintless cloth followed with a clean lintless cloth I saturated with recommended refrigerant. 2. Repeat until the saturated cloth is not discolored by dirt. 3. Wipe with a clean cloth saturated with compressor oil and squeezed dry. 4. Wipe with a dry, lintless cloth. 1 3.09 TEST A. General: I 1. Minimum duration of two hours or longer, as directed for all tests. Furnish report of test observation signed by qualified inspector. Make all tests before applying insulation, backfilling, or otherwise concealing piping or connecting fixtures or equipment. Where part of the system must be tested to avoid concealment before the entire system is I complete, test that portion separately, same as for entire system. 2. Provide all necessary temporary equipment for testing, including pump and gauges. Remove control devices before testing and do not use piping system valves to isolate sections where test pressure exceeds valve pressure rating. Fill each section with water I 3. and pressurize for the indicated pressure and time. Observe each test section for leakage at end of test period. Test fails if leakage is observed or if pressure drop exceeds 5% of test pressure. I B. Repair: . 1. Repair piping system sections which fail the required piping test by disassembly and re- installation, using new materials to the extent required to overcome leakage. Do not use chemical stop -leak compounds, solder, mastics, or other temporary repair methods. 2. Drain test water from piping systems after testing and repair work has been completed. I C. Sewer: Furnish all facilities and personnel for conducting the test. Test in accord with the requirements of the State Plumbing Inspector and local authorities. D. Plumbing Waste and Vent Piping: Hydrostatic test by filling to highest point, but not less than 10' water column on major horizontal portion. E. Water Piping: Hydrostatic pressure of 100 psig without loss for four hours. I F. Natural Gas Piping: One half hour minimum air at 60 psig for 2 psig gas, and 15 minutes at 10 psig for 7" water gauge natural gas or as approved and certified by serving utility. I G. Heating Water Piping: 75 psig hydrostatic for 30 psig systems without loss for four hours. H. Tanks and Equipment: Hydrostatic pressure to 1.5 times operating pressure. I. Refrigerant System: 1. When the refrigerant connections have been completed, close the compressor suction and discharge valves (or receiver outlet valve in the case of condensing unit) and test the balance of the system to near operating pressure with a dry nitrogen. I 2. Carefully test all joints, using soap and water or other sudsing solution. After all joints are tested, discharge the gas and repair all leaks, then repeat the test with a mixture of nitrogen and HCFC -22 and a halide torch or an electronic leak detector. 3. Evacuate the system to remove moisture and non - condensables. Lower the absolute I pressure with a vacuum pump to 1000 microns of mercury. Apply external heat as required to vaporize moisture. 4. Dehydrate each refrigerant circuit by satisfactory use of a vacuum pump before charging with refrigerant. Furnish all necessary refrigerant and oil for complete operating charge I of the system. Upon completion of the work of construction, test all refrigeration equipment under normal operating conditions and leave in operating order. Adjust automatic temperature controls. 5. After the first 24 hours of operation, measure the pressure drop across the suction filter. I If the pressure drop exceeds 5 pounds per square inch, replace the cartridge with a new one, retesting and replacing the cartridge and/or adjusting the system as necessary to achieve a pressure drop of less than 5 pounds per square inch in 24 hours. I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15060 -7 Printed 04/30/04 SECTION 15060 , PIPES AND PIPE FITTINGS END OF SECTION ' • I 1 e 1 I I I t 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD - TUALATIN SCHOOL DISTRICT 23J 15060 -8 Printed 04/30/04 I SECTION 15090 I SUPPORTS AND ANCHORS I PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS I A. Drawings and general provisions of the.Contract, including General and other Conditions and other Division 1 — General Requirements sections, apply to the work specified in this Section. I 1.02 DESCRIPTION A. The requirements of this section apply to the mechanical piping and equipment systems specified elsewhere in these specifications. I B. Provide pipe and equipment hangers, supports, anchors and related items for complete anchor, hanger and support systems. I 1.03 QUALITY ASSURANCE A. Standards: The Manufacturers Standardization Society (MSS) of the Valve and Fittings Industry Practice SP -58 and SP -69 are referenced in this section. I B. Provide factory - fabricated horizontal piping hangers, clamps, hanger rod, shields, supports, etc., of the indicated MSS type and size. I C. Seismic Requirements: Provide seismic restraints in accordance with UBC Section 1632. Design restraint systems in accordance with "Seismic Restraint Manual: Guidelines for Mechanical Systems," Second Edition, 1998, SMACNA, or "A Practical Guide to Seismic Restraint" ASHRAE RP -812, 1999. I PART 2 - PRODUCTS I 2.01 ACCEPTABLE MANUFACTURERS A. Manufacturers: B -Line, Carpenter & Paterson, Grinnell, Michigan, Superstrut or accepted substitute. 1 B. Listed Types: MSS Piping Types listed with Grinnell figure numbers in parentheses where applicable (or other manufacturers as noted). I 2.02 SUPPORTS A. Horizontal Piping Hangers and Supports: I. Adjustable Clevis Hanger: MSS Type 1 (Fig. 260). I 2. Adjustable Band Hanger: MSS Type 7 (Fig. 97), fabricated from steel. 3. Adjustable Swivel -Band Hanger: MSS Type I0 (Fig. 70). 4. Clamp: MSS Type 4 (Fi 212, 216). 5. Double -Bolt Clamp: MSS Type 3 (Fig. 295A, 295H), including pipe spacers. I B. Equipment and Piping Supports: I. Channel Support System: Galvanized, 12 gauge channel and bracket support systems, single or double channel as indicated on the Drawings or as required by piping and I equipment weights. Grinnell "Power Strut" channel. Acceptable manufacturers: Super Strut, Globestrut, Bee, Kindorf or Unistrut. 2. Steel Brackets: Welded structural steel shapes complying with one of the following: a. Light Duty: MSS Type 31 (Fig. 194). b. Medium Duty: MSS Type 32 (Fig. 195). I 3. c. Heavy Duty: MSS Type 33 (Fig. 199). Rooftop Pipe Stands: MIRO Industries model 24 -R or accepted substitute. Vertical.Pipe Clamps: I C. 1. Two -Bolt Riser Clamp: MSS Type 8 (Fig. 261). 2. Four -Bolt Riser Clamp: MSS Type 42 include pipe spacers at inner bolt- holes. I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15090- I I SECTION 15090 SUPPORTS AND ANCHORS I D. Hanger Rod Attachment: I I . Hanger Rod: Grinnell Fig. 140 or 146 for all sizes. Right hand threaded. 2. Turnbuckles: MSS Type 13 (Fig. 230). 3. Weldless Eye -Nut: MSS Type 17 (Fig. 290). 4. Malleable Eye- Socket: MSS Type 16 (Fig. 110R). I 5. Clevises: MSS Type 14 (Fig. 299). E. Building Attachments: I. Concrete Inserts: MSS Type 18 (Fig. 282), steel or Grinnell Power -Strut PS349 I continuous channel. Acceptable Manufacturers: Michigan Hanger, Globestrut, Unistrut, Super Strut. 2. Clamps: MSS Type 19 (Fig. 285, 281), Type 20, 21 (Fig. 225, 226, 131), Type 23 (Fig. 86, 87, 88), Type 25 (Fig. 227), Type 27 through 30 where applicable. I F. Saddles and Shields: 1. Protection Saddles: MSS Type 39 (Fig. 160). 2. Protection Shields: MSS Type 40 (Fig. 167). I 3. Preinsulated Pipe Supports: Pipe Shields Inc. or accepted substitute. a. Pipe supported on rods - Models A1000, A2000, A3000, A4000 and A9000. b. Pipe supported on flat surfaces - Models A1000, A2000, A5000, A6000 and A7000. c. Pipe supported on pipe rolls - Models A3000, A4000, A5000, A6000 and I A8000. G. Miscellaneous Hanger Materials: 1. Metal Framing: Provide products complying with NEMA STD ML 1. 2. Steel Plates, Shapes and Bars: ASTM A -36. 3. Cement Grout: Portland cement (ASTM C -150, Type I or Type III) and clean uniformly graded, natural sand (ASTM C -404, Size No. 2). Mix at a ratio of 1.0 part cement to 3.0 parts sand, by volume with only the minimum amount of water required for placement and hydration. 4. Heavy Duty Steel Trapezes: Fabricate from steel shapes selected for the loads required; weld steel in accordance with AWS Standards. 5. Pipe Guides: Provide factory - fabricated guides, of cast semi -steel or heavy fabricated I steel, consisting of a bolted two- section outer cylinder and base with a two- section guiding spider bolted tight to the pipe. Size guide and spiders to clear pipe and insulation (if any), and cylinder. Provide guides of the length recommended by the manufacturer to allow indicated travel. I 6. Standard Bolts and Nuts: ASTM A 307, Grade A. 7. Concrete Anchors: Rawl Lok/Bolt, Hilti "HSL," ITT Phillips, Red Head Wedge Anchors, Ramset Trubolt or Dynabolt or accepted substitute. . 8. Shop Primer: Manufacturer's standard rust inhibitive primer. I PART 3 - EXECUTION . 3.01 INSTALLATION . I A. General: Proceed with the installation of hangers, supports and anchors only after the required building structural work has been completed in areas where the work is to be installed. Correct I inadequacies including (but not limited to) the proper placement of inserts, anchors and other building structural attachments. 1. Install hangers, supports, clamps, and attachments to support piping and equipment properly from the building structure. Use no wire or perforated metal to support piping, I and no supports from other piping or equipment. For exposed continuous pipe runs, install hangers and supports of the same type and style as installed for adjacent similar piping. 2. Prevent electrolysis in the support of copper tubing by the use of hangers and supports I which are copper plated or by other recognized industry methods. 3. Support fire sprinkler piping independently of other piping and in accordance with NFPA Pamphlet 13. 4. Arrange supports to prevent eccentric loading of joists and joist girders. Locate supports I at panel points only. 02(154 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II I MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15090 -2 I SECTION 15090 I SUPPORTS AND ANCHORS I B. Provisions for Movement: 1. Install hangers and supports to allow controlled movement of piping systems and to permit freedom of movement between pipe anchors, and to facilitate the action of expansion joints, expansion loops, expansion bends and similar units. I 2. Install hangers and supports so that equipment and piping live and dead loading and stresses from movement will not be transmitted to connected equipment. 3. Install hangers and supports to provide the indicated pipe slopes, and so that maximum pipe deflections allowed by ANSI B31 are not exceeded. Comply with the following I installation requirements: a. Clamps: Attach clamps, including spacers (if any), to piping outside the insulated piping support. Do not exceed pipe stresses allowed by ANSI B31. b. Insulated Pipe Supports: Insulated pipe supports shall be supplied and installed I on all insulated pipe and tubing. c. Load Rating: All insulated pipe supports shall be load rated by the manufacturer based upon testing and analysis in conformance with ASME B31.1, MSS SP -58, MSS SP -69 and MSS SP -89. I d. Support Type: Manufacturer's recommendations, hanger style and load shall determine support type. e. Insulated Piping Supports: Where insulated piping with continuous vapor barrier or where exposed to view in finished areas is specified, install hard maple I wood insulation shields (Elcen Fig. 216) or steel pipe covering protection shields (MSS type 39) at each hanger. C. Pipe Support: I I. Vertical Spacing: Support at base, at equivalent of every floor height (maximum 10' as required by Code) and just below roof line. 2. Screwed or Welded Steel or Copper Piping: Maximum hanger spacing shall be as follows: Steel Copper I 1 -1 /4" and smaller 7' span 6' span I-1/2" pipe 9' span 6' span 2" pipe 10' span 10' span 2-1/2" & larger 12' span 10' span I 3. Cast Iron Soil Pipe: a. Hubless and Compression Joint: At every other joint except when developed length exceeds 4', then at each joint. I b. Additional Support: Provide at each horizontal branch and /or at concentrated loads to maintain alignment and prevent sagging. 4. Install additional hangers or supports at concentrated loads such as pumps, valves, etc. to maintain alignment and prevent sagging. I 5. Support Rod: Hanger support rods sized as follows: Pipe and Tube Size Rod Size Inches mm Inches mm I 1/2" to 4" 12.7 to 101.6 3/8" 9.5 5" to 8" 127.0 to 203.2 1/2" 12.7 10" to 12" 254.0 to 304.8 5/8" 15.9 I D. Adjust hangers and supports to bring piping to proper levels and elevations. E. Provide all necessary structural attachments such as anchors, beam clamps, hanger flanges and brackets in accordance with MSS SP -69. Attachments to beams wherever possible. Supports I suspended from other piping, equipment, metal decking, etc., are not acceptable. F. Horizontal banks of piping may be supported on common steel channel member spaced not more than the shortest allowable span required on the individual pipe. Maintain piping at its relative I lateral position using clamps or clips. Allow lines subject to thermal expansion to roll axially or slide. Size channel struts for piping weights. I 112054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15090 -3 SECTION 15090 SUPPORTS AND ANCHORS 3.02 INSTALLATION OF ANCHORS A. Install anchors at the proper locations to prevent stresses from exceeding those permitted by ANSI B31, where recommended in SMACNA "Seismic Restraint Manual" or exceeding manufacturer's recommended loading, and to prevent the transfer of loading and stresses to connected equipment. B. Fabricate and install anchor by welding steel shapes, plates and bars to the piping and /or equipment and to the structure. Comply with ANSI B31 and AWS standards and SMACNA "Seismic Restraint Manual." C. Bolting: Provide standard plate washers under heads and nuts of bolts bearing on wood. Soap threads of lag bolts prior to installing. D. Structural Blocking: Locate as indicated and as required to support mechanical piping and equipment. E. Where expansion compensators are indicated, install anchors in accordance with the expansion unit manufacturer's written instructions, to limit movement of piping and forces to the maximums recommended by the manufacturer of each unit. F. Anchor Spacings: Install anchors at the ends of principal pipe runs, at intermediate points in pipe runs between expansion loops and bends. Make provisions for presetting of anchors as required to accommodate both expansion and contraction of piping. G. Painting: Refer to Section 15050. 3.03 EQUIPMENT RESTRAINTS A. Systems and equipment shall be anchored to resist displacement, including sliding, swinging, and overturning due to seismic forces. Friction due to equipment weight shall not be considered as anchorage. B. The contractor shall retain a consulting engineer or equipment manufacturer to design the seismic restraint systems. C. Contractor shall submit calculations and shop drawings, sealed and signed by a professional engineer, showing seismic restraint design for all equipment weighing 400 lbs. or more and for all piping and ductwork required to be braced. Design shall show analysis of supporting structure, anchorages, and restraints in accordance with UBC Section 1632. D. Seismic restraint system components shall be approved by the California Office of Statewide Health Planning and Development (OSHPD) for fixed equipment anchorages. Acceptable manufacturers: Mason Industries, Tolco, or approved. 1 END OF SECTION • r 1 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 1 5090 -4 in led 114/26/114 I SECTION 15100 I VALVES I PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS I A. Drawings and general provisions of the Contract, including General and other Conditions and other Division 1 — General Requirements sections, apply to the work specified in this Section. I 1.02 DESCRIPTION A. The requirements of this section apply to the valving for the piping system specified elsewhere in these specifications. I B. Provide valves where shown on the Drawings and specified herein. 1.03 QUALITY ASSURANCE A. Provide factory fabricated valves of the type, body material and pressure class indicated and service indicated. I B. Valve Sizes: Same as connecting pipe size. C. Bronze valves shall comply with MSS- SP -80. Iron gate and globe valves shall comply with MSS- SP -70. I . PART 2 - PRODUCTS 2.01 VALVE TYPES A. General: Where possible, provide valves from a single manufacturer. I B. Acceptable Manufacturers: Milwaukee, Crane, Grinnell, Nibco, Hammond, Stockham, Watts, and Walworth. Grinnell numbers are given except as noted. C. Domestic Water Systems: I . 1. Valves 2" and Smaller: a. Ball: Two - piece, bronze body, standard port, 400 psi WOG, Fig. 3500. b. Check: Bronze body, swing check, 200 psi WOG, Fig. 3300. 2. Valves 2" through 12 ": I a. b. Ball: Three- piece, cast bronze body, full port, 600 psi WOG, T /S -595Y. Butterfly: Ductile iron body, aluminum bronze disc, 200 psi WOG, Lugged body — LD -2000, Wafer body — WD -2000, Grooved body — GD -4765. c. Gate (to 3 "): Bronze body, non- rising stem, 200 psi WOG, T/S -133. Gate (4" to 12 "): Iron body, bronze trim, non - rising stem, solid wedge, bolted I d. bonnet, 200 psi WOG, F -6I9. D. Heating Water: Valves up to 12 ": I I. a. Ball: Two- piece, bronze body, standard port, 400 psi WOG, Fig. 3500. b. Butterfly: Iron body, aluminum bronze disc, 200 psi WOG, series 8000. c. Check: Bronze or iron body swing check, 200 psi WOG, Figs. 3300 and 6300. I E. Steam Systems: 1. Systems up to 125 psi or 350 Deg. F: a. Ball: Two - piece, bronze body, full port, 150 psi WSP, Fig. 3810. b. Gate (to 3 "): Bronze body, union bonnet, rising stem, solid wedge, 150 psi I WSP, Fig. 3080. c. Gate (2" to 12 "): Iron body, bronze trim, bolted bonnet, solid wedge, outside screw and yoke, 125 psi WSP, Fig. 6020A. I F. Natural Gas: UL listed or AGA approved valves. 1. 10 psig or Less: • I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15100 -1 i SECTION 15100 VALVES a. Ball: Watts FBV -1. G. Butterfly Valve Operators: Locking lever for shut -off service; "Memory Stop" for lever handle and slotted index plate for infinite number of settings for throttling service; gear operator with babbitt sprocket rim for chain- operated valves and gear operators on all 6" or larger valves. H. Butterfly Valve Style: Lug -type with cap screws for all valves utilized for equipment isolation for servicing. PART 3 - EXECUTION 3.01 INSTALLATION A. General: Comply with the following requirements: 1. Install valves where required for proper operation of piping and equipment, including valves in branch lines where necessary to isolate sections of piping. 2. Locate valves in accessible spaces (or behind access panels) and so that separate support can be provided when necessary. 3. Install valves with stems pointed up, in the vertical position where possible, but in no case with stems pointed downward from a horizontal plane. B. Insulated Valves: Install extended -stem valves in all piping specified as insulated, and arrange in the proper manner to receive insulation. C. Selection of Valve Ends (Pipe Connections): Select and install valves with ends matching the types of pipe /tube connections. D. Valve Access: Provide access panels to all valves installed behind walls, in furring or otherwise inaccessible. - E. Fluid Control: Install gate, ball, globe, plug, and butterfly valves to comply with ANSI B31. Install check valves where indicated and where flow reversal is obviously not desirable and can be reasonably expected to occur, including piping at the discharge of pumps. Install silent check valves where necessary to eliminate water hammer occurring from reversal of flow. END OF SECTION 1 1 • .I 1 „2054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II 111 MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15100 -2 I SECTION 15240 I MECHANICAL SOUND AND VIBRATION CONTROL I PART 1 - GENERAL 1.01 DESCRIPTION I A. The requirements of this section apply to the vibration isolation for mechanical equipment specified elsewhere. I 1.02 QUALITY ASSURANCE A. Isolator Engineering: Selected and furnished by the equipment manufacturer. Select isolators for 98% efficiency unless indicated otherwise on the Drawings. I B. Manufacturer: Provide field installed isolation required from a single manufacturer where possible. 1.03 SUBMITTALS I A. Provide product data sheets on all vibration isolators and seismic restraints. B. Provide itemized list showing the items of equipment or piping to he isolated, isolator type and I model number selected, isolator loading and deflection, and reference to specified drawings showing frame and construction. C. Provide manufacturer's drawings showing equipment frame construction for each item including I dimensions, structural member sizes and support locations. PART 2 - PRODUCTS I 2.01 EQUIPMENT FRAMES Roof Curb Mounted Vibration Isolation Bases: I A. 1. Mount rooftop equipment on factory fabricated vibration isolation curbs that fit under the • isolated equipment. Construct the lower member of rectangular steel tube containing adjustable and removable steel springs that support the upper floating member. The I upper frame shall provide continuous support for the equipment and shall be captive so as to resiliently resist wind and seismic forces. A continuous flexible aluminum seal joined at the corners with EPDM bellows shall be nailed to the wooden port frame to weatherproof the assembly. Hardware shall be cadmium plated or galvanized with I springs plated or provided with an approved rust - resistant finish. Mason Industries "RSC" sized to fit equipment furnished. Acceptable equivalents: Vibrex, Thycurb, Amber Booth, Micrometl. I 2. Provide perimeter angle and cross members to support two layers of 5/8" sheet rock. See Part 3 for acoustical protection. Mason Industries RSCA or approved. I 2.02 VIBRATION ISOLATORS A. Flexible Pipe Connectors: All stainless steel hose and braid with carbon steel connections. Male thread ends on flexible connectors 2" and smaller, and flanged connections on 1 -1/2" and larger O connectors. Amber BoothType SS or equal Flexonics PART 3 - EXECUTION I 3.01 INSTALLATION A. General: Install vibration isolators and flexible connectors as specified herein, as shown on the I Drawings and as recommended by manufacturer. I u2ns4 _ TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15240-1 Primed 04/26/04 SECTION 15240 MECHANICAL SOUND AND VIBRATION CONTROL B. Flexible Pipe Connections: 1. Provide flexible connections on all piping to spring isolated equipment, where indicated on Drawings and for all coils mounted in spring isolated air handling units or plenums. Coils in rigid units and plenums do not require flexible connectors. Provide a flexible connection in both the supply and return connections to the coil as near the coil as possible. 2. Install connectors in a straight line as recommended by the manufacturer without offsets or twists and support pipe without any load on flexible connectors. Minimum live length shall be as follows: Pipe Size Minimum Live Length 1" through 1-1/2" 8" 2" through 2-1/2" 10" 3" through 4" 12" Over 4" 18" E. Anchorage: Anchor all isolators to the floor, wall or ceiling structure and anchor points reinforced where necessary. Anchor bolts, cap screws, etc., shall not be continuous through the isolator such that vibrations are transmitted to the structure. F. Rooftop HVAC Unit Acoustical Protection: 1. All roof mounted HVAC units shall be supported and anchored on leveled, flashed and counterflashed vibration isolated curbs anchored to resist seismic forces and suitable for the roof construction. Minimum curb height shall be 12" above the roof unless indicated otherwise on the Drawings. Flashing into the roof is specified in another Section. 2. Install two layers of 5/8" weatherproof sheet rock with staggered joints on the perimeter angle and cross members provided with the vibration isolator bases. Apply sheet rock around all ductwork above the roof and caulk all joints and seams. Provide additional acoustical materials as recommended by acoustical engineer. G. Adjustment: Adjustable during and after installation, to ensure sufficient clearance between vibration isolation element and rigid restraining device. Do not install isolators until they have been loaded and adjusted to achieve the specified static deflection and clearances. 3.02 . EQUIPMENT RESTRAINTS A. All equipment shall be anchored to resist displacement including sliding, swinging, and overturning due to seismic forces. Friction due to equipment weight shall not be considered as anchorage. B. Contractor shall submit shop drawings showing seismic restraint design for all equipment weighing 400 lbs. or more. Design shall show analysis of supporting structure, anchorages, and restraints in accordance with UBC Section 1630. END OF SECTION • • 1 1 1 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15240 -2 Printed (14/25/04 I SECTION 15250 • I MECHANICAL INSULATION 1 PART 1 — GENERAL 1.01 DESCRIPTION I A. The requirements of this section apply to the insulation of mechanical equipment specified elsewhere in these specifications. 1.02 QUALITY ASSURANCE I A. Insulation. Thickness and Thermal Performance: Comply with Chapter 13 provisions of the State of Oregon Structural Specialty Code. I B. Composite (Insulation, Jacket or Facing and Adhesives) Fire and Smoke Hazard Ratings: Not to exceed a flame spread of 25 or smoke development of 50. C. Component Ratings of Accessories (Adhesives, Mastics, Cements, Tapes, Finishing Cloth for I Fittings): Same as "B" requirements above and permanently treated. No water soluble treatments. • 1.03 PRODUCT DELIVERY, STORAGE AND HANDLING I A. General: In addition to the requirements specified in Section 15050, the following apply: 1. Deliver insulation, coverings, cements, adhesives and coatings to the site in factory - fabricated containers with the manufacturer's stamp or label affixed showing fire hazard ratings of the products. Store insulation in original wrappings and protect from weather I 2. and construction traffic. Protect insulation against dirt, water, chemical and mechanical damage. Do not install damaged insulation. Remove such insulation from project site. I 1.04 SUBMITTALS A. Submit catalog data and performance characteristics for each product specified. 1 PART 2 — PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS I A. Insulating Manufacturers: Schuller, Knauf, Armstrong, Owens - Corning, Pittsburgh Corning, Pabco, Imcoa or Certain Teed. Schuller products are listed unless indicated otherwise. I B. Adhesive Manufacturers: Benjamin Foster, 3M, Insul - Coustic, Borden, Kingco or Armstrong. 2.02 PIPING INSULATION I A. Interior Piping Systems 40 to 850 Deg. F: Glass fiber preformed pipe insulation with a minimum K -value of 0.23 at 75 Deg. F, a minimum density of 3.5 pounds per cubic foot within all - service vapor harrier jacket, vinyl or pre -sized finish and pressure sensitive seal. Schuller "Micro -Lok." I B. Exterior Installations: Same as for interior installations except 0.016" aluminum finish jacket. Schuller "Micro -Lok." C. Pipe Temperatures Minus 30 to 180 Deg. F: Flexible, preformed, pre -slit, self - sealing elastomeric I pipe insulation up to 2 -1/8" ID, thermal conductivity of 0.27 BTU /hr. sq. ft. /in. at 75 deg. F and vapor transmission rating of 0.2 perms /inch. Apply in thickness necessary to prevent condensation on the surface at 85 deg. F and 70% RH. Armstrong "Armatlex 2000" or, in • concealed locations, Imcoa or Nomaco also approved. I 2.03 DUCT INSULATION A. Interior Above Grade Ductwork: Glass fiber blanket with "FSK" facing, k value = 0.31 at 75 deg. F, and UL 25/50 surface burning rating. Schuller "Microlite." 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15250- I Primed )4/261U4 I SECTION 15250 MECHANICAL INSULATION I 2.04 EQUIPMENT INSULATION . A. Equipment Temperatures From 70 to 450 Deg. F: Glass fiber 3 pound density insulation with a I 0.23 thermal conductivity at 75 deg. F. Schuller "814 Spin -Glas" with "FSK" jacket or finished as recommended by manufacturer. 2.05 INSULATION ACCESSORIES II A. Insulation Compounds and Materials: Provide rivets, bands, adhesives, cements, coatings, sealers, welded studs, etc., as recommended by the manufacturers for the insulation and conditions specified. No stapled jacket fastenings are acceptable. B. Interior Tanks and Equipment Insulation Covering: Finished metal jacket or as recommended by the manufacturer for insulation material specified. • C. PVC Protective Jacketing and Valve and Pipe Fitting Covers: Schuller Zeston 2000, Proto I LoSmoke, or Ceel -Co Ceel -Tite 100 Series with precut fitting fiberglass insulation or approved. D. Jacket Lap Sealing Adhesives: Foster Drion 85 -75 contact cement or approved substitute. I PART 3 — EXECUTION 3.01 PIPING INSULATION I A. General: Do not insulate underground piping except at joints and fittings on preinsulated piping unless indicated otherwise. e B. Domestic Water Piping: 1. Insulate with glass fiber pipe covering, 1" thick for cold water piping and for 1" and smaller hot water piping; 1 -1/2" for 1 -1/4" and larger hot water piping. 2. At contractor's option and in accordance with Part 2 of this section, elastomeric insulation may be installed on domestic water piping in thicknesses equivalent to the . glass fiber insulation. Installation shall comply with the manufacturer's recommendation with joints and seams completely sealed. Insulate hot water return piping same as cold water piping. 3. Do not insulate emergency shower supply line. C. Heating Water Piping: Insulate with glass fiber pipe covering: Size Thickness 1/2" to 1 -1/2" 1 -1/2" 2" to 3" 2" I 4" and larger 2 -1/2" Runouts up to 1" and 12' length 1/2" D. Refrigerant Piping Insulation: Insulate suction piping with minimum 1/2" thick foamed plastic or I of thickness necessary to prevent condensation at 85 deg. F and 70% RH. Where possible, slip insulation over the piping as it is installed. Seal all joint and seams. E. Pipe Fittings: I 1. Insulate and finish all fittings including valve bodies, bonnets, unions, flanges and expansion joints with precut fiberglass insulation and preformed PVC covers sealed to adjacent insulation jacket for continuous vapor barrier covering over all fittings. 2. Use 1/2" thick Armaflex or Aerotube foamed plastic at flexible pipe connections on chilled and /or cold water lines. No insulation on other flexible pipe connections. 3. Provide removable /reusable insulation covers on 4" and larger valves, unions, flanges; pump casings, strainers and similar fittings or equipment requiring periodic service. F. Protective Covering: Install continuous protective PVC or metal covering on all piping and I fittings in mechanical rooms below 8', or outside where insulation may be subject to damage. Install with rivets or cement seams and joints. I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15250 -2 Vrinirrl 114/96 /I I4 I SECTION 15250 MECHANICAL INSULATION I G. Piping Insulation Lap Seams and Butt Joints: Install insulation jacket in accordance with manufacturer's recommendation. Where jacket joint and lap seams have not adhered, remove I affected section of insulation and reinstall or apply lap sealing adhesive in accordance with manufacturer's instructions. H. Interior Rain Drains: I I. Concealed: Insulate with 1" thick one pound density glass fiber blanket and continous vapor barrier jacket I. Steam Piping: Insulate above ground steam piping with glass fiber pipe covering; thickness as I follows: 1. Under 15 prig: Size Thickness 1 -1/2" or smaller 1 -1/2" I 2" or larger 2" 2. Wire insulation in place with 16 gauge stainless steel wire on 12" centers in half - round, split tile or other underground conduit. I J. Condensate Return: Insulate same as steam supply. Do not insulate pumped condensate return lines unless indicated otherwise. 1 3.02 DUCTWORK INSULATION A. Ductwork: Insulate the following: .. I. All supply ductwork. 2. All supply and return ductwork in systems routed in unconditioned spaces or exposed to the outside conditions. 3. All outside air intake ducts. I 4. All ductwork required to be insulated by code. B. Insulation Thickness: Select board and blanket insulation of thickness required to provide the following installed R- value. I 1. All heating or cooling system supply and return ducts located on the exterior of the insulated building envelope and all outside air intake ducts. a. R -8: Zone t b. R -l2: Zone 2 I 2. 3. Ducts located within or below concrete slabs on grade, R -4. All heating and cooling system return ducts located in unconditioned spaces, R -3.5. C. Fittings: Wire and duct adhesive as required. To prevent sagging on all rectangular or square ducts over 24" wide, install Gramweld or equal welding pins on the bottom. Maximum spacing I 18" on center in both directions. D. Installation: Applied with butt joints, all seams sealed with vapor seal mastic or taped with 2" wide vapor - proof, pressure- sensitive tape. Seal all penetrations with vapor barrier adhesive. I E. Internally Lined Ductwork: Where internally lined ductwork is indicated on the Drawings and /or specified, no exterior insulation is required. Select duct lining to provide the required R- value. I Carefully lap the ends of the exterior insulation a minimum of 6" past the interior insulation unless otherwise shown. Seal the end of vapor barrier jacket to the duct with mastic where the vapor barrier is required. Duct lining is specified in Section 15880. END OF SECTION I I I 021154 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15250 -3 Printed 04/26/04 I SECTION 15300 FIRE PROTECTION I PART 1 - GENERAL 1.01 DESCRIPTION I A. The requirements of this section apply to the fire protection system. B. Provide all labor and material and perform such other services necessary and reasonably incidental the design and installation of an automatic sprinkler and standpipe system for all areas indicated I to on the Drawings and as required by the Governing Agency. I .02 QUALITY ASSURANCE I A. Contractor Qualifications: I. Established fire protection contractor regularly engaged in the design and installation of automatic fire sprinkler systems. I 2. 3. Employ workers experienced and skilled in this trade. System designer: Qualified and certified for the design of fire protection sprinkler systems. NICET level III or IV technician or Professional Engineer experienced in the design of sprinkler systems. I B. Governing Agency: All work in accordance with and accepted by the following hereafter referred to Governing Agencies: I1. Fire Marshal State of Oregon. 2. Fire Marshal City of Tigard, Oregon. C. Design Requirements: I 1. Comply with the latest issue of NFPA Standard 13. 2. Design, lay out and install a hydraulically calculated wet pipe system utilizing code approved automatic devices designed particularly for use in this type of system. I 3. Fire Sprinkler Coverage: As required by the Governing Agency and including fire protection of all areas noted. 4. Occupancy Hazard: Final Occupancy Hazard designation in accordance with the Governing Agency requirements. I S. Revisions to the Contractor's design required by the Governing Agency shall be at the Contractor's expense. 6. Coordinate and pay for all flow tests required for design. 7. Provide complete flow calculations from point of known flow and pressure. I 8. See drawings for areas served and systems to be modified. D. Acceptable Manufacturers: All sprinkler specialty material Grinnell /Gem, Central, Reliable, Globe, Star, Viking, Automatic Sprinkler Corp. of America with UL or FM approval for use in I automatic sprinkler systems. All materials and equipment suitable for 175 psi working pressure. E. Field Wiring: Comply with requirements of Section 15050. IF. Work of Other Trades: Comply with requirements of Section 15050. 1.03 SUBMITTALS O A. Working Drawings: I. Prepare fire protection system working drawing showing locations and types of head or outlets, alarm valves and devices, pipe sizes and cutting lengths, test tees and valves, drain valves, and other related items. Plans shall comply with the requirements of I Chapter 8, 1999 NFPA 13, irregardless of the edition adopted by the Governing Agencies and used for design. 2. Provide 3 sets of drawings showing sprinkler head locations and layout coordinated with architectural ceiling details to the Architect for review prior to submitting details to the I Governing Agencies. I 021I54 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15300-1 I'rinmd 04/2(/14 I SECTION 15300 FIRE PROTECTION I 3. Provide 6 sets of drawings to the Architect to be provided to Insurance Underwriter for approval. I 4. Provide 6 sets of drawings to designated representatives of the Fire Marshal for approval. 5. Then provide 6 sets of approved Drawings to the Architect for final review. B. Submittals: I I. Sprinkler Heads: Product Data for each type of head. 2. Alarm flow or pressure switches. 3. Fire department connection. I 4. System control valves. 5. Piping materials. 6. Alarm bell. 7. Miscellaneous Equipment. C. Test Reports: Submit certificates of completion of tests and inspections. I 1.04 EXTRA STOCK A. Additional Heads: Provide number, type and temperature rating installed as required to meet I NFPA 13 requirements. B. Storage Cabinet: Provide as required to receive reserve sprinkler heads and special installation I tools required. C. Index Label: Provide for each head indicating manufacturer, model, orifice, size or K- factor, and temperature rating. Also provide, inside cabinet, a list of heads stored within and brief description of where installed. PART 2 - PRODUCTS 2.01 MATERIALS AND EQUIPMENT . A. Miscellaneous Sprinkler Specialties: Complete system including all items required by the I Governing Agency including but not limited to: 1. Electric alarm switch and indoor and outdoor alarm bell or water motor gong. 2. Double check assembly. I 3. Valve monitoring switches. 4. Fire department hose connections. 5. Wiring from the alarm switches to the point of connection in the Fire Alarm Control Panel. Coordinate with the Electrical Work specified in Division 16. I B. Sprinkler Heads: Approved heads with temperature ratings required for service indicated. 1. Unfinished Areas: Upright, pendent or sidewall spray type, plain bronze. Provide with I head guards. 2. Finished Areas: Chrome plated recessed and sidewall heads in finished ceilings and where piping is exposed use chrome plated upright heads. C. Escutcheons: Provide polished chrome escutcheons on pipe extending through finished walls and I ceilings. D. Above Ground Water Piping: Use standard weight (schedule 40) black steel pipe ASTM A53, I A135, or A795, and cast iron screwed or mechanical joint fittings especially adapted and approved for sprinkler work. Use reducing fittings where changes in pipe size occur. Bushings are prohibited. E. At Contractor's option, Schedule 10 black steel pipe ASTM A135 or ASTM A795, and mechanical I joint fittings specifically approved for sprinkler use, may be substituted for the black steel pipe specified above. Pipe shall he UL listed and FM approved for 300 psi working pressure. Pipe must have a CRR of 1.00 or greater. I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15300 -2 I SECTION 15300 I FIRE PROTECTION F. At contractor' option, thin wall threadable steel pipe, ASTM A135 or A795, and cast iron or malleable iron screwed fittings 11/2" and smaller, approved for sprinkler work. I G. Valves: UL and /or FM listed for fire protection service. 1. Iron body OS &Y pattern, bronze mounted double disc, parallel seat. I 2. Iron body butterfly style with EPDM liner, bronze disc with lever or indicating type gear operator. 3. Bronze body ball valve, three -piece design, with approved operator. 4. Where required by Governing Agency, provide wall or post style indicating valves. I H. Valve Monitoring Switches: Provide approved monitoring switches where shown on the Drawings or required by Governing Agency. I I. Guards: Standard manufacture. PART 3 - EXECUTION I 3.01 INSTALLATION A. Connect to water supply source as shown on Drawings, check adequacy and call any deficiency to I attention of Architect. Coordinate with work in Section 15050: B. Install all piping in a true and even manner with lines pitched for drainage and system arranged so that it can be entirely emptied of water. Install hangers at all branch line connections to cross , I mains and at all other points as required in herein before specified Underwriters Laboratories, Inc. and NFPA standards. C. Support all pipe work from building construction with mild steel hangers spaced not more than 12 I feet on centers. Support mains independently of branches and in no case shall branch hangers assume any portion of the weight of mains. D. Locate sprinkler heads in repeating, modular pattern, centered and accurately coordinated with ceiling grid as indicated. Conceal all piping unless indicated otherwise. Coordinate design with lighting and exposed HVAC duct layout in areas without ceilings. I E. Locate and install the required fire sprinkler alarm, flow, and test and drain valves where required by the Governing Agency. F. Where sprinkler lines penetrate fire rated partitions, provide fire stopping system in accordance I with Section 15050. 3.02 TEST A. Test all pipes to a hydrostatic pressure of 200 psi and maintain for four hours minimum. Perform other tests as directed by Governing Agency. 3.03 PAINT I A. Paint all exposed piping and hangers in accordance with Section 09900. Do not paint heads. 3.04 CERTIFICATE OF COMPLETION I A. Obtain and deliver to Owner a certificate, in duplicate, stating that system as installed has been inspected and accepted by authorities and /or agencies having jurisdiction, and that all regulations affecting work have been satisfied. Submit an acceptable certificate to the Owner before final I payment is requested. B. Certificate: Minimum NFPA Form 8 -1 information per NFPA 13. I I 112054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15300 -3 Printed 04/26/114 SECTION 15300 FIRE PROTECTION END OF SECTION 1 1 1 1 I 1 1 1 I2O$4 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD - TUALATIN SCHOOL DISTRICT 23J 15300 -4 in1,11 )4/7(/04 I SECTION 15400 PLUMBING I PART 1-GENERAL • I.0I DESCRIPTION I A. The requirements of this section apply to the plumbing system. B. Provide fixtures specified and shown on the Drawings. ' 1.02 QUALITY ASSURANCE A. Code: Comply with requirements of the Oregon State Plumbing Specialty Code. I B. Fixture color: White unless indicated otherwise. C. Utility Connections: Make utility and equipment connections and install distribution piping as shown on the Drawings and specified herein. Verify size, location, depth, elevation and I arrangement of connection points before bidding or starting work. • D. Potable Water Valves: Potable water valves not limited to faucets, mixing valves, or pressure reducing valves. Valves shall meet NSF Standard 61, Section 9, for drinking water faucets and I shall be brass construction. Brass components which contact water within the faucet shall be from brass which contains no more than 3 percent lead by dry weight. E. Field Wiring: Comply with requirements of Section 15050, Article 1.2, paragraph D. I PART 2 - PRODUCTS I 2.01 PIPING A. Piping, fittings, and related items as specified in related Sections 15060, 15100 and 15250. I 2.02 INTERIOR PLUMBING MATERIALS A. Cleanouts: II. Manufacturer: J.R. Smith, Zurn, Wade, Ancon, or approved substitute. 2. Types: a. Tile Floor Cleanouts: Smith 4053 -U with square heavy -duty nickel bronze top, taper thread, bronze plug, and vandalproof screws. I b. Carpeted Floor Cleanout: Smith 4023 -U -X with round heavy -duty nickel bronze top, taper thread, bronze plug, carpet clamping device, and vandalproof screws. c. Concrete Floor Cleanout: Smith 4023 with round heavy -duty nickel bronze top. d. Wall Cleanouts: Smith 4472 -U, bronze ferrule with raised head bronze plug, I e. stainless steel shallow cover and vandalproof screws. Outside Area Walks and Drives: Smith 4253 -U -G with galvanized cast iron body, top secured with vandalproof screws, taper thread and bronze plug. Install in 18" x 18" x 6" deep concrete pad flush with grade. I A. Flashing: Minimum 4# sheet lead; to extend horizontally 10" from edge of vent penetrations or rain drain body and vertically 12" minimum up from roof turned over and down into hub of vent or finished with bronze cap providing counterflashing for screwed pipe. C. Air Chambers and Shock Arrester: Precharged bellows or sealed piston type manufactured to meet PDI WH -201 and ASSE 1010 Standards. Size in accordance with PDI procedures. J. R. Smith, PPP, Sioux Chief, Wade, Zurn, Ancon, or approved substitute. . I D. Priming Valves: Smith 2699, Wade W8800T, Zurn Z1022, Ancon MS8I0 or equivalent Precision Plumbing. Locate in closets, under counters or in walls behind Milcor or access panels as specified in Section 15050. Use copper specified in Section 15060, Pipe & Pipe Fittings, for all I underground priming lines. )2ft64 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -1 SECTION 15400 PLUMBING E. Traps: Except chrome plated fixture traps. Recessed drainage pattern for threaded pipe and same grade as pipe for cast iron pipe; with cleanout plugs in trap body in all above grade locations. F. Water Heater and Tank Seismic Restraints: For water heaters and tanks, Spacemaker, Holdrite 1' "Quickstrap ", or approved. G. Pressure Reducing Valve: Single seat type with renewable stainless steel seat and valve. Size and capacity as shown on Drawings. Bronze bodies with screwed connections on valves 2 -1/2" and smaller and flanged steel bodies on valves 3" and larger. Install each PRV with strainer on inlet or internal strainer. Leslie, Spence, Fisher, Watts, Foster, Cash -Acme, Zurn - Wilkins, or approved substitute. H. Backflow Preventer: Where indicated on the Drawings, install a reduced pressure backflow preventer complete with strainer on inlet, shutoff valves, two separate check valves, differential • relief valve, and test cocks. USC Foundation for Cross Connection Control, State Health Officials, and serving utility approved. Bronze bodies on units 2" and smaller, and cast iron bodies with bronze trim on units 2 -1/2" and larger. I. Master Showing Mixing Valve: All brass or bronze body with stainless steel parts, thermostatic master control element to fail safe upon cold water or control element failure. Provide with external union angle check stops, strainers, volume control, shutoff valves, dial thermometer. Valve location, arrangement and capacity as shown on plans. Leonard, Lawler, Powers, or approved substitute. J. Gas Pressure Regulators: Size based on pressures indicated on the drawings and for 1.5 times connected load. Style and model as approved by Northwest Natural Gas Co. Maxitrol, Rockwell, Fisher, Reliance, or approved substitute. K. Backwater and Gate: Cast iron body with brass wedge gate, brass swing check, and separate handle. Provide with proper extension to set floor plate flush with finished floor. Smith 7150 or equivalent Wade, Ancon or Zurn. L. Domestic Water Balancing Valve: Balancing fitting with differential pressure taps, brass or bronze body and trim. B &G "Circuit Setter" or equivalent Taco, Armstrong, Thrush, Wheatley, Flow Design or approved substitute. At contractor's option, balancing valves 3" and larger may be butterfly style, Jenkins No. 222 EL or approved substitute as specified in Section 15100. M. Pressure - Temperature Test Plugs: 1. 'A" or 'h" NPT fitting of solid brass capable of receiving either an 1/8" OD pressure or temperature probe and rated for zero leakage from vacuum to 1000 psig. Neoprene valve core for temperatures to 200 deg. F., Nordel to 350 deg. F. 2. Provide for each test plug a pressure gauge adapter with 1/16" or 1/8" OD pressure probe. 3. Furnish a test kit containing one 2 -1/2" dial pressure test gauge of suitable range, one gauge adapter with 1/16" or 1/8" OD probe and two 5" stem pocket test thermometers — one 0 to 220 degrees F and one 50 to 550 degrees F. Turn the kit over to the Architect. 4. Cisco "PIT Plugs," Peterson "Pete's Plug" or approved substitute. N. Thermometers: Mercury -in- glass, adjustable stem, separable sockets, plus 40 to 240 degrees F range (unless indicated otherwise). Weiss numbers are listed. Equivalent Taylor, Trerice, Weksler or approved substitute. I . • Wide case (9 ") in equipment rooms and all major equipment items. Weiss "9VS" series. 2. Narrow case (7 ") in all other locations. Weiss "7VS" series. O. Pressure Gauges: Install on discharge of all pumps and where shown on Drawings 4 -1/2" dial, 0- 100 psig graduation pressure gauges with Ashcroft No. 1 106 pulsation dampers and stop cocks. Weiss UGE -1 or equivalent Ashcroft, Marsh, Trerice, Weksler. • 1 1 II 21)54 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -2 I'rintcd 114/26/114 1 SECTION 15400 l PLUMBING 2.04 PLUMBING FIXTURES I A. Stops: Furnish stop valves for all fixtures. Loose key style, in wall, angle or straight through pattern to fit installation. Stops to be all brass with full turn brass stem and replaceable washer, no plastic. Compression nuts to be high copper content brass. Finish to be copper nickel chrome plate. Product to carry manufacturer's name. Risers to be chrome plated copper. McGuire, I Chicago, Brasskraft, or approved substitute. B. Provide handicap piping protector kit on all exposed accessible fixture traps and supplies (I &S Insulation Co. Inc., Brocar Products Inc. kit 500R, McGuire "Prowrap ", Plumberex "Pro- 2000" or I approved substitute. C. 1.6 Gallon Flush Water Closet, Flush Valve, Vitreous China: Water closet bowl shall be designed for 1.6 gallon siphon jet flushing action. I 1. Install each listed water closet with the following: a. Flush Valve: Quiet acting, exposed chrome plated brass with ADA metal oscillating non - hold -open handle, screwdriver check/control stop with vandal I resistant cap, cast wall flange, synthetic rubber diaphragm, and vacuum breaker, as recommended by closet manufacturer. Sloan Royal. b. Seat: Solid white molded plastic seat; open front less cover for elongated bowl with check and self - sustaining hinge. Olsonite IOCC -SS, Beneke 523- SS /CH -B, I Bemis 1955 SS /C or Church 5334.171 (295 -SS). 2. Floor Mounted, top spud "WC -1 ": American Standard 2234.015, Kohler K -4350, or Eljer 111-2125. 3. Floor Mounted, top spud 18" High "WC -2 ": American Standard 3043.102, Kohler K- 1 4368, Eljer 111 -2145. D. Urinal, Flush Valve, Vitreous China, "UR -1 ": 1. Install each listed urinal with the following: Quiet acting, exposed chrome plated brass I flush valve with ADA metal oscillating non - hold -open handle screwdriver check/control stop with vandal resistant cap, cast wall flange, synthetic rubber diaphragm, and vacuum breaker, as recommended by fixture manufacturer. Sloan Royal. 2. Wall Hung, Blowout: Install with 1" cold water and plate type carrier with bearing plate. I Zurn, Jay R. Smith, Wade, Ancon. American Standard 6601.012, Kohler K- 4972 -T, or Eljer 161 -1060. 3. Set one urinal at height required by code for the handicapped in each restroom. E. Lavatory, Vitreous China, "LV -1 ": I 1. Faucet: Chrome plated brass body with handle for the handicapped, vandal resistant 0.5 gpm aerator with temporing valve and grid strainer waste. Chicago 807 -669 single hole metering faucet. Tempering valve to be under - counter mount design with integral I check/stops. Banks of up to 4 lavatories may be served by a single device. Watts LI 11 or approved. 2. Wall Hung, 20" x 18" Size: Provide with concealed arm hangers and wall hacking plate (J.R. Smith, Wade, Ancon, or Zurn). American Standard 0355.012, Kohler K -2005, or 1 Eljer 051 -2104. F. Lavatory, Vitreous China, "LV -2 ": I 1. Faucet: Chrome plated brass body with single mixing handle for the handicapped, vandal resistant 0.5 gpm aerator with temporing valve and grid strainer waste. Symmons S -20 -2 G faucet.. 2. Wall Hung, 20" x 18" Size: Provide with concealed arm hangers and wall hacking plate • i (J.R. Smith, Wade, Ancon, or Zurn). American Standard 0355.012, Kohler K -2005, or Eljer 051 -2104. • G. Drinking Fountain, "DF -1 ": Wall mounted, 14 gauge stainless steel, dual fountain with one I fountain equipped for the handicapped with dual side lever or push bar /button operator. Provide with vandal resistant bottom cover plates, wall mounting plate, stainless steel wall plate, extension • skirt on upper fountain. Haws 1 1 19.14 or equal Halsey Taylor, Elkay, Sunroc. 1 I I2054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -3 PI 111 „ d 04 /26/U4 111 SECTION 15400 PLUMBING H. Stainless Steel Sinks, (except S -4, S -5, S -6, S -7, these sinks are epoxy, see architectural '' specification section): 1. Type 304, 18 gauge, self - rimming stainless steel sink installed with stainless steel crumb ' cup strainer outlet unless noted otherwise, and flange tail piece. Elkay numbers are listed, Just approved. For faucets, Chicago numbers are listed; equal T &S approved except as noted. I 2. Prep Room "S-1": ADA, single compartment, Elkay LR2222 with 6 ' /" depth, Speakman faucet and eye wash combo, SEF -1800. 3. Music "S -2 ": ADA, single compartment, Elkay LR2222 with 61/2" depth, grid strainer, I Chicago 1100 faucet and Elkay LK 1141A bubbler. 4. Work Room "S -3 ": Single compartment, ADA, Elkay LR2222 with grid strainer, I Chicago 527 faucet with 8" swinging spout. 5. Epoxy Sink, "S -4 ": See Architectural, faucet Chicago 930, provide with acid resistant strainer outlet and tail piece. 6. Epoxy Sink, "S -5 ": ADA, see Architectural, faucet Chicago 895 -320 with E7 serrated I nozzle outlet and vacuum breaker gooseneck spout, provide with acid resistant strainer outlet and tail piece 7. Epoxy Sink, "S -6 ": See Architectural, faucet Chicago 930, provide with acid resistant I strainer outlet and tail piece 8. Epoxy Sink, "S -7 ": See Architectural, provide with two Chicago 930 faucets, provide with acid resistant strainer outlet and tail piece 9. Conference /Staff Sink, "S -8 ": Single compartment, Elkay LR 2222 with 6' " depth, Chicago 2300 -8 faucet. Provide with grid strainer outlet. I 10. Life Skills Sink, "S -9 ": Double compartment, ADA, Elkay LR 3322, Chicago 2300 -8 faucet. I. Clothes Washer Fitting, "CW -1 ": Guy Gray WB 200 / T 200 hot and cold water valve washing I machine waste outlet. J. Refrigerator Water Connection "RC-1": Guy gray BIM 875 or approved. I K. Single Shower, "SH -1 ": install with concealed piping and 2.5 gpm head and handheld shower head with 6' flex hose, vacuum breaker, and wall slide bar for ADA with diverter valve. Pressure equalizing mixing valve with combination strainer /check stops and temperature limit stop. I Symmons 96- 500- B30 -LV or equal Powers, Leonard, Lawler approved. Fiberglass shower stall for the handicapped with 3" grid strainer outlet, grab bars, fold -up seat and curtain rod. Fiberfab 60H 1 or equal Aquaglass, Lasco, or approved. L. Lab Outlets, "AGO-1": Air and gas outlet Chicago turret with serrated outlets model 982 -DS -909 ' index for air or gas. M. Service Sump (Mop Basin) "SS -1 ": I 1. Faucet exposed, rough plated, long spout, top brace, hose end spout with bucket hook, vacuum breaker and integral stops in shanks. Chicago 897 faucet mounted 24" above rim. Install with 18 gauge type 302, No. 4 finish stainless steel splash on the two walls. I Install with sill cock (Chicago 988 with hose outlet) at 24" AFF routed from 892 -G vacuum breaker mounted at 72" AFF feed by Chicago 1303 valve. See detail for more information. 2. Molded stone 24" x 24" x 10" deep room corner type with vinyl pumper guard and 3" I brass body strainer outlet. Fiat, Mustee, Swan or approved substitute. N. Drains: 1. Turn, Jay R. Smith, Wade and Mifah. Numbers scheduled on drawings represent I minimum acceptable standard for locations involved. 12U TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -4 I'r inlcd 04/26/04 1 SECTION 15400 1 PLUMBING 2. Install 4 pound sheet lead flashing, extending not less than 10" from and clamped to all drains not completely cast -in -place in a homogeneous material. I O. Fume Hood, "FH -I ": Specified in other division, provide acid waste `P'trap for chemistry areas, standard 11/2" chrome plated cast brass `P'trap for science units. Provide water and gas connection as specified. :1 P. Hose Bibs: 1. Outside "HB -1 ": Non - freeze type with vacuum breaker, bronze wall casing and wall I clamp. Zurn Z- 1310 -6, Wade W -8620, Woodford 67 series, Smith 5609 -PB, or Ancon HY420. 2.05 EMERGENCY FIXTURES . 1 A. Combination Shower /Eyewash, "ES-1": Wheelchair accessible combination shower and eye /facewash unit shall deliver 30 gpm at 30/70 psi of flowing pressure from the shower head and 8.0 gpm at 30/70 psi of flowing pressure from the eye /facewash. Unit shall provide a non- , injurious stream of water for 15 minutes or longer as required by ANSI Z358.1. Combination unit shall be supplied with chrome plated (CP) bronze single motion activation stay open ball valves with CP balls. Valve sizes: shower 1", eye /facewash' /z ". Unit shall include S/S actuators with actuation graphics, schedule 80 hot dip galvanized steel piping and 1 1 /4" supply /waste connection I with flanged floor mounting plate for free - standing installation. Shower head shall be supplied with self - adjusting 30 gpm regulator. Eye/Facewash heads to be supplied with self - adjusting 8.0 gpm regulator to assure a constant and even dual stream flow pattern under 30/70 psi hydraulic conditions. Shower head to be manufactured of UV resistant long lasting high visibility yellow I ABS plastic. Shower head must deliver a minimum of 20" diameter pattern to the target area 60" (152.4 cm) above standing level. Eye /Facewash heads with float off covers to be manufactured of UV resistant long lasting ABS plastic mounted on a chrome plated brass wye in a type 304 S/S bowl. Float off covers are secured with stainless steel bead chains and provided to inhibit dust I and /or contamination when not in use. Combination units that provide improper flow pattern or contain deteriorating screens /filters are not acceptable. Wheelchair accessible combination unit shall be Encon Safety Products Model 01050273 or equal Western, Guardian. • 1 PART 3 — EXECUTION 3.01 UTILITY SERVICE I A. Sanitary and Storm Sewers: Connect to sanitary and storm sewers as shown on the Drawings and as required by the serving utility. Verify depth, size and location prior to installation of the new sewer systems. I B. Water Service: Connect to water service. Verify serving utility requirements prior to beginning any installation. Verify water main size, depth, pressure and location prior to starting work. I 3.02 EXCAVATION AND BACKFILL A. As specified in Section 15060. I 3.03 PIPING A. Install in accordance with Section 15060, 15090, 15100 and 15250. I B. Shock Arrestors and Air Chambers: Install at end of mains, in a battery of three or more flush valve - operated fixtures water header, ahead of quick closing and solenoid operated valves. Size per PDI recommendations where size is not indicated. Provide access panels. I C. Trap Priming: Traps serving floor drains, floor sinks, catch basins, and similar fixtures shall be primed in accordance with Code requirements. 1 I 02054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -5 SECTION 15400 PLUMBING 3.04 CLEANOUTS A. Where required by code, at each change of sewer direction 45 degrees or greater and more than 10' long, at end of each branch or main and spaced not greater than 100' apart, as required by code and /or as shown on Drawings. 3.05 FIXTURE INSTALLATION AND CONNECTION A. All exposed fixture connections and piping shall be plated with polished chrome. Where chair carriers or special carrier design are not indicated, provide 3/16" thick by 6" wide steel to waste or vent piping and to available building construction. B. All fixtures in contact with finished walls shall be caulked with waterproof, white, non - hardening sealant which will not crack, shrink or change color with age. C. All fixtures and component parts shall conform to governing codes. 1 3.06 FIXTURE CLEANING A. Remove construction protection, tags and labels and thoroughly clean all plumbing equipment and trim I scour all fixtures just prior to building acceptance. 3.07 CHEMICAL WATER TREATMENT A. Analyze the water condition and determine chemicals required for treatment. Provide sufficient chemicals for the initial fill and provide a list of the chemicals required for the Operating and Maintenance Manuals specified in Section 15050. The list shall include probable quantities of each chemical required for one year, availability of each chemical and the name and address of the supplier. END OF SECTION 1 1 1 1 1 1 1 u2054 TIGARD HIGH SCHOOL ADDITION / REMODEL - PHASE II MAY 04 TIGARD — TUALATIN SCHOOL DISTRICT 23J 15400 -6 Printed 04 /26/04