April 21, 1993
John H. Romish
2216 S.E. 24th Avenue
Portland, Oregon 97214
Re: Precision Interconnect
16640 S.W. 72nd Avenue
7290B- 048 -003
Dear Mr. Romish:
This is a Fire and Life Safety Plan Review and is based
on the 1991 editions of the Uniform Fire Code (UFC) and
those sections of the Uniform Building Code (UBC) and
Uniform Mechanical Code (UMC) specifically referencing
the fire department, and other local ordinances and
regulations.
Plans are conditionally approved subject to Tigard
Building Department requirements and the following items:
1. The tenant space number must be prominently
displayed on the street front where it is readily
visible to drivers and officers of responding fire
apparatus and other emergency vehicles. UFC Sec.
10.208
2. Not less than one (1) approved fire extinguisher(s)
with a rating of not less than ( *) shall be provided
for each ( * *) square foot of floor area or fraction
thereof. The travel distance to an extinguisher
from any portion of the building, shall not exceed
75 feet. UFC Sec. 10.303
( *) 2A10B:C - Light and Ordinary Hazard
4A10B:C - Extra Hazard
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
"Working" Smoke Detectors Save Lives
John H. Romish
April 21, 1993
Page 2
Note: Where flammable or combustible liquids are
used, "B" ratings of extinguishers may need to be
higher and travel distances shorter. See
requirements in National Fire Protection Association
Standard 10 -1.
3. Plans referred to and examined by this office
contain no provisions for the alteration or
installation of automatic sprinkler system. Not
less than three sets of plans for the installation
shall be submitted to this office for approval prior
to installation. UBC 302(b)
Approval of submitted plans is not an approval of
omissions or oversights by this office or of non-
compliance with any applicable regulations of local
government.
If I can be of any further assistance to you, please feel
free to contact me at 562 -2469.
Sincerely,
1 . ..J`
Bradley Wanamaker
Deputy Fire Marshal
BNW:kw `