Correspondence VLMK Consulting Engineers December 13, 1996
3933 S.W. KELLY AVENUE, PORTLAND, OREGON 97201 -4393 PRINCIPALS
(503) 222 -4453 / FAX (503) 248 -9263 ALFRED VAN DOMELEN, P.E.
JAMES E. KNAUF, P.E.
ASSOCIATES
FAX TRANSMITTAL GARY J. LEWIS, P.E.
GREG BLEFGEN, P.E.
HAVLIN G. KEMP P.E.
/00Z S 5 5 ` � JOHN BROOKS
To: JOHNSON CONTROLS From: HAVLIN KEMP
Attn: ALAN KOLKEMO Pages Following: 0
Project: METZGAR ELENTARY SCHOOL Copy in mail: X
ADDITION OF HVAC UNITS
Re: FIELD REVIEW OF IN PLACE HVAC UNITS AT METZGAR SCHOOL
Following our meeting at Metzgar School on Wednesday, 12/11/96, I reviewed our
recommendations for strengthening the structure. The HVAC units have not been placed at the
center of each classroom as shown on your layout drawings, rather they have been placed within
10 feet of the classroom sidewall. The columns supporting the roof structure are located in the
classroom walls. This location places less bending stress on the roof girder. Consequently:
1. No additional reinforcement is required at the glulam girders. The 1 %" micro -lam is not
required to be added at the glu -lam beam spanning the classrooms.
2. At the "Front" classrooms, the 4" x 5' /z' T &G roof sheathing is adequate to support the new
HVAC Units without any additional structure.
3. At the "Back" classrooms, the 3 1/4" x 8" purlins are adequate to support the new HVAC units
without any additional structural reinforcement. The 2 x 8 is not required to be added along
side the existing purlins. Note: The new HVAC units are shown to be 45" wide and the 3'/4" x
8" purlins are at 48" on center. If the new HVAC unit curbs bear directly on the purlins, no
additional structure is required between the purlins, below the roof sheathing.
If you have any additional questions, please give me a call at 222 -4453.
Best regards,
VLMK Consulting Engineers v 0 �O,IME F sx 'o
,352 9 y .
OREGON
9 A
( �
Havlin G. Kemp ti .471, 1 G ,9 � � Q
Project Manager
EXP. 6 -30 -97
Documentl
Johnson Controls, Inc.
Controls Group
Suite 605
4011 S.E. International Way
Milwaukie, OR 97222
Tel. 503/654 8422
- City of Tigard
JOHNSON 13125 SW Hall Blvd.
CON I TISO" LS Tigard, OR 97223
September 1 1, 1996
Subject: Metzger Elementary Mechanic I Plan Review
PC #: 7 -90c Mec. # 96 -025
We submit the following as responses to said comments outlined in your letter dated
August 19, 1996 (attached) for your review and approval.
1. Provided in packet
'Provided in packet see drawings 6 & 7
t3 Provided in packet
Provided in packet
A y. Provided in packet see drawings 6 & 7
If you have any further question please feel free to call.
Sincerely,
HNSON CONTROLS, INC.
Dick Petrich
Project Manager
t -i
RFCEl
IUG 2 0 199 C
August 19, 1996 � :H � S i'N CU J CLS, Ii C. of TIGAR®
Johnson Controls, Inc. OREGON
4011 SE International
Milwaukie, OR 97222
RE: Metzger Elementary Mechanical Plan Review
10255 SW 90th Avenue
PC #: 7 -90c MEC #: 96 -0251
Submittal documents for the above referenced project have been reviewed for conformance with
the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The
following comments are noted:
�j Submit completed applicable Forms 4a through 4j, and required duct insulation Form 4a
YV through 4c of the Energy Code Compliance Manual (Revised April 1996).
Air moving systems (combination of units) supplying air in excess of 2000 CFM to
enclosed spaces shall be equipped with an automatic shut -off. The smoke detectors
shall be supervised when a fire detection or alarm system is provided [OSSC, Section
' 608].
U�
Provide an engineer's analysis of each structural member supporting the additional HVAC
units [OSSC, Section 106.3.2].
A The attachment of permanent equipment (HVAC) supported by the building's structural
U "` components shall be designed to resist the total design seismic forces prescribed in
ec Section 1603.2 of the Structural Specialty Code. Provide an engineer's design specifying
attachment requirements [SSC Section 160.3.2 and OMSC, Section 304.4].
The heat/ventilation system shall provide outside air per occupant in all portions of the
building [UBC Section 1202.2.1 and Table 12 -P].
A.�/ Provide outside air specifications on the revised plans.
Please submit three copies of revised submittal documents and a letter indicating your response
to the above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely, /
Ykj
( Jim Funk
/ PLANS EXAMINER
i:\citywide\pc7-90c.doc
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
•
RICEIVED
AUG 1 E 199E m �
August 16, 1996 JOHNSON CONTROLS, INC. CI
PORTLAND, �IGI�R®
PORTLAND, OR.
Johnson Controls, Inc.
4011 SE International OREGON
Milwaukie, OR 97222
RE: Tigard Swim Center Mechanical Plan Review
8680 SW Durham Road
PC #: 7 -88c MEC#: 96 -0251
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
ask, °x's:�",'_.::...t u;a''. 4' �t ' s� .: _.. x ,
1. Is this a replacement of existing equipment or a new installation?
2. Is the supply air tempered and, if it is, how is it done?
3. Provide the manufacturer's installation instructions for our review.
A. What is the weight of the unit?
B. How is the unit supported?
1. Provide an engineer's analysis of each structural member
supporting the additional HVAC units [OSSC, Section 106.3.2].
2. The attachment of permanent equipment (HVAC) supported by
the building's structural components shall be designed to resist
the total design seismic forces prescribed in Section 1603.2 of the
Structural Specialty Code. Provide an engineer's design
specifying attachment requirements [SSC Section 160.3.2 and
OiviSC, Section 304.4].
Please submit three copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
'Jim Funk
PLANS EXAMINER