Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
iF'l Ex.$PtIVICL.ER. w =aI.. ., 3.,; ° n
t1`'� Side -wall spray - sprinklers shall be installed in accordance with UBC, Std.
G.. t y)
e, There are rooms wider than 12 feet where you have specified a single
branch line. Provide protection in accordance with Table 4- 4.2.1.
B. The sprinkler layout in many rooms does not meet requirements for
spacing, staggering, and distance to end wall specifications [UBC, Std.
9-1-4-4.2.1]. (See Typical C -23, C -26).
Provide the sprinkler identification, specifications, and - number of sprinklers in the
���'�� sprinkler schedule on the plan.
Pd. if [/3 • Protect all concealed combustible construction such as, but not limited to, soffits,
� shafts, etc.
r ‘ ', v , , i de prote ct i on fo • oo C- 5 and F -16.
TO' ‘Lt y o ( U ; / 7 ( y
I
A Please sub three cope s of revis s documents and a letter indicating your
V U' ' r response to th omments for review. Please call me at (503) 639 -4171 if you
_
1161 have any questions.
c_ --L ....xi...A <
Sincer lye, y
Jim Funk` - -- `_.-
'PLANS EXAMINER , ,:
is \cilywide\pc7- 47c .doc �y'��� •
G A " �` j
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
MASTER FIRE CONTROL, INC.
FIRE PROTECTION SPECIALISTS
January 16. 1997
11995 S.E. HWY. 212
CLACKAMAS, ORE. 97015
Jim Funk PH.655 -6992
Plans Examiner
City of Tigard
13125 SW Hall Blvd.
Tigard, Oregon 97223
RE: Fire Sprinkler Plan Review
of Twality Middle School
Permit No. 96 -0416
This letter is in response to your plan review letter for
Fire Sprinkler System remodel and addition dated August 12, 1996
and addresses the issues you brought up in your letter.
1.A. • ■ t_ e• for these rooms are in accordance with Table 4-
` 7.2 NFPA 13 1996 Edi' ion. e /
us � y
1.B. The existing and new nstallation of sidewall sprinklers are
in accordance with NFPA 13 1996 edition 4- 9.3.1.1 Exception No.2
and 4 -9.3.2 along with Table 4 -9.2 and Manufacturer Product Data
sheets for Extended Coverage Horz S ewall (Included with this
letter.). �yI
2. See attached copy of Title Block with list of all new
sprinklers install in this remodel. We reused existing sidewalls
that where removed from remodeled areas in the new additions.
3. Have complied.
4. These are existing rooms and at the time of the field servey I
was unable to access these rooms. I have since been able to get
into them and found them to be sprinklered.
Please call if you have any questions.
R- - •ec full
1/ / 0 40 K 4
lex Romno
cc: Michael J. Watt, INC.
•
.Zittik
CITY OF TIGARD
OREGON
January 21, 1997
Master Fire Control, Inc.
11995 S.E. Highway 212
Clackamas, OR 97015
RE: Twality Middle School Building Plan Review
14650 SW 97th
PC #: 7 -47c B U P #: 96 -0416
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
In response to your letter of January 16, 1997, the following items need to be
addressed:
4
The Oregon Revised Uniform Building Code Standard 9 -1 is based on NFPA 13,
1994, not 1996. Correct reference to the Standard.
2 Submit three (3) revised sets of plans, each containing the correct information in
the title block.
Please call m---a (503) 639 -4171 if you h. - any questions. )
Sincerely, 1 '� r s i- 1 ^' • ,
3�
' fl Ai Id
r
Jim Funk
il .4 U � e ' A,
72,j,e
PLANS EXAMINER 3
o
T: IPRMSYSDOCUMENT \BUP96_04.16TC7 -47C2 • •
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Mar -16 -98 07:07A M J Watt Inc. 503 236 0558 P.01
03/13/98 FRI 17:24 FAX 503 598 1980 CITY OF TIGARD [6001
•
SkT tiNG TIE STANDARD FOR SER l<I E EXCELLENCE
•I1' Facsimile
To: Mike Kurilo, Project Manager
Company: Michael J. Watt, Inc.
Phone: 238 -0866
Fax: 236 -0558
From: Jean Heitschmidt, email: jean@ci.tigard.or.us
Company: City of Tigard Building Division
Phone: (503) 639 -4172, ext. 420 (5 :00 -11:00 pm)
Fax: (503) 684 -7297
Date: March 13,1998
Pages including this page: 5
COMMENTS:
I have received a copy of the inspection report for Twality Middle School that you faxed to on
Hudson today. As you know, final approvals are not valid until the plans and permits are approved
and issued by the Building Official. Your designer has not responded to the plan review letter; the
plans have not been approved; the permit for fire protection (BUP96-0416) has not been issued; and
the fee has not been paid ($128.63). In a conversation with you several months ago, you told me
that the school district was picking up that permit and that it was not part of your contract. I have
enclosed the leading edge of the plans for That work. It looks like you are the applicant rather than
the school district. Without the fire protection permit, the related structural permits can't be
approved. Please contact your subcontractor and resolve these issues as soon as possible. The
School District is in violation of UBC standards and has been notified that the City and the
Construction Contractor's Board have no choice but to penalize the applicants if final approvals are
not received by March 31,1998.
cc: Ron Hudson 15
V V6PccV
City of Tigard, 13125 SW Hall Blvd
h .r
_ v�
Mar -16 -98 07:O8A M J Watt Inc. 503 236 0558 P -04
03/13/98 FRI 17:26 FAX 503 598 1a8U
Page No. 1. LOG NOTES FOR CASE NO.: BUP96 -0416
TIGARD TUALATIN SCHOOL DIST
14650 SW 97TH AVE
03/13/98
By Date Text of log note
JT 12/02/97 The following information was data entered into description by
Jim Funk April, 1997. It has been transferred to log notes for
ease in reading:;; NOTE: continue this information throughout
permits issued to Twality. Years ago, TVFR agreed to an
alternate to requirements for fire protection of chases for
mechanical installations, but unprotected voids were still
allowed as density of .10 over 3,000 sq.ft. was provided. See
NFPA 13. Most current is the understanding reached with Gene
Birchill TVFR on 4/9/97 and Allen Crisanaz, PE for MRE & Assoc
doing a mechanical up grade on the school. when opening a
concealed comb void, draft and or fire stops will be installed.
If the area is enlarged, it will be protected by the buildings
fire suppression system.
JT 12/02/97 a conversation i had with Jim Funk today. Jim stated
hth tl for
came into his office (some time ago) g if Jim
this fire suppression permit. Jim stated yes, but permit had not
been issued, Tom looked at plans and then went out and did an
inspection. Jeanne T.
•
[\
03/18/98 09:39 $`503 684 7297 CITY OF TIGARD 1J001
:1: :x: *: : :x : :$::::x ;$ :1:u :m:I::x *$x:I :$
*:s: ACTIVITY REPORT :s **
*********411-1.1.$1.1.1 ' ' 1 ' ' 1 ' ' ' ' ' ' '.k h: %f:
TRANSMISSION OK
TX/RX NO. 0549
CONNECTION TEL 503 656 0782
CONNECTION ID
START TIME 03/18 09:37
USAGE TIME 02'01
PAGES 3
RESULT OK
Post -it Fax Note 7671 Dale I f,d'Ify 1pagoes .
To r//nv7[A From m / M
CoJDept /T /� Av. Co. 7/ tr /q n
Phone # Phone # f
Fax #3--(/ ^ 6 3 _ 4 , C ; : 2 2 _ Fax # cS 4'4 "7 )` 1 -1.. .,
CITY OF TIGARD
OREGON .
January 21, 1997
Master Fire Control, Inc.
11995 S.E. Highway 212
Clackamas, OR 97015
RE: Twality Middle School Building Plan Review
14650 SW 97th
PC #: 7-47e BUP #: 96 -0416
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
In response to your letter of January 16, 1997, the following items need to be
addressed:
42 The Oregon Revised Uniform Building Code Standard 9 -1 is based on NFPA 13,
1994, not 1996. Correct reference to the Standard.
fip Submit three (3) revised sets of plans, each containing the correct information in
the title block
Please call m - (503) 639 -4171 if you h any questions.
Sincerely, 1 )1 t t
. _.,�_ . ,,/, Ai ,.
03/17/98 TUE 13:26 FAX 503 598 1960 CITY OF TIGARD U001
**** * ** *.* *** *** * ** * **
* ** TX REPORT * **
* * * * * * * * * * * * * * * * * * * **
TRANSMISSION OK
TX /RX NO 0721
CONNECTION TEL 6560782
CONNECTION ID
ST. TIME 03/17 13:25
USAGE T 00'41
PGS. SENT 1
RESULT OK
CITY OF TIGARD
OREGON
January 21, 1997
Master Fire Control, Inc.
11995 S.E. Highway 212
Clackamas, OR 97015
RE: Twality Middle School Building Plan Review
14650 SW 97th
PC #: 7 -47c BUP #: 96 -0416
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
In response to your letter of January 16, 1997, the following items need to be
addressed:
1. The Oregon Revised Uniform Building Code Standard 9 -1 is based on NFPA 13,
1994, not 1996. Correct reference to the Standard.
2. Submit three (3) revised sets of plans, each containing the correct information in
the title block.
Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Jim Funk
p
`, ,S IN �qZ
P
n F T UALATIN VALLEY FIRE & RESCUE
FIRE PREVENTION
V ;` 4755 S.W. Griffith Drive . P.O. Box 4755 . Beaverton, OR 97076 . (503) 526 -2469 . FAX 526 -2538
u
'RF
April 30, 1997
Jim Funk, Senior Plans Examiner i ) e
City of Tigard Y g
13125 S.W. Hall Blvd. 9n
T arcs, Oregon 97223
Re: Twality Junior High
14650 S.W. 97 Avenue
6189A- 003 -000
Dear Jim:
Because of the history of sprinkling the above captioned facility, the fire district is
willing to support a policy of not extending automatic sprinkler protection into
existing void areas and concealed spaces unless those void areas and concealed
spaces are made larger. This decision is based on the fact that the existing
automatic sprinkler protection that is installed in the school is based on a .10
density with an application area of 3,000 square feet as prescribed in National Fire
Protection Association Standard 13 when combustible concealed spaces are not
provided with automatic sprinkler protection.
The fire district is in support of providing automatic sprinkler protection in void
and concealed spaces when void and concealed spaces are made larger or when
extensive modifications are made to the building.
This building was provided with automatic sprinkler protection during an
extensive remodel where it was found that large continuous non -draft stopped/fire
blocked void spaces were found running through the building. At that time a
decision was made to ask the school district to provide automatic sprinkler
protection in the building and the design criteria was chosen at that time.
"Working" Smoke Detectors Save Lives
Jim Funk
April 30, 1997
Page 2
If there are any further questions, please call me at 526 -2469.
Sincerely,
Gene Birchill, DFM
Plans Examiner
GB:kw
cc Ron Hudson
Tigard School District
Allen Crisanaz