Correspondence June 14, 2004' II CITY OF TIGARD) OREGON Brian Greenwood Dull Olson Weekes Architects 319 SW Washington Street #200 Portland, OR 97204 RE: REMODEL EXISTING MIDDLE SCHOOL Project Information Building Permit: BUP2003 -00701 Occupancy Type: A2.1 Tenant Name: Twality Construction Type: V -1HR Address: 14650 SW 97 Avenue Occupant Load: 656 Area: 5,305 Sq Ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following conditions. 1. Fire Sprinklers have been used in -lieu of 1 Hr Fire- resistive construction. 2. Exit doors shall be provided with panic hardware.1007.2.5 OSSC 3. Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 '/2 hours of illumination in case of primary power loss. 10012.8.5 OSSC 4. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. 1003.2.9.2 OSSC 5. Provide one 2 -A rated fire extinguisher in the new area. The extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguisher. Standard 10 -1, Chapter 3 TVFR99 -01. 1 FYI Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. Special Inspection: Special inspection is required for items listed on sheet S1.0 The special inspection agency of record shall furnish inspection reports to the Engineer of Record, 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 N + r. Nishkian, the General Contractor, and the City of Tigard, Building Division, attention Hap P 4 Watkins. All discrepancies shall be brought to the immediate attention of the general contractor for correction. The special inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the code. 1701.3 OSSC American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and proc- :.ing the documents. Respe ,■ !' gria o S- - Plans Examiner F ebruary 26, 2004 Brian Greenwood Dull Olson Weekes Architects 319 SW Washington Street #200 Portland, OR 97204 RE: REMODEL EXISTING MIDDLE SCHOOL Project Information Building Permit: BUP2003 -00701 Occupancy Type: A2.1 Tenant Name: Twality Construction Type: V -1 HR Address: 14650 SW 97 Avenue Occupant Load: 656 Area: 5,305 Sq Ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The following information is required prior to the approval of the submitted plans. FIRE- & LIFE - SAFETY 1. The new exterior canopy at the North side of the new Commons area has an assumed 0 property line at the South side. Openings are not permitted per Table 5 -A OSSC. Please provide a wall of 2 hour fire resistive along the assumed property line. 2. Clarify the continuation of the separation of the North end of the kitchen as it v),,5 continues through the bathroom, mop sink and along the edge of the storage room g � that opens to the existing gym. Doors A105A & A106A are not rated? QV 3. Provide documentation to clarify the flame spread of WSCT -1 in Commons area. 4. Clarify framing members and attachment to structure for the Gypsum Board ceilings indicated on sheet 1/A6.1. ACCESSIBILTY 5. The K sheets do not indicate the 34 inch high tray slide for the service line as required .7 by section1109.21.2.2. Please provide a detail. P V 6. Grab bar sizes are indicated in Spec10800. The extension from the back wall, as 11 required by section 1109.10.5.3 OSSC, is not indicated on detail 1 A15.3. A dimension should be incorporated on the detail. STRUCTURAL 7. Provide calculations for the design of the lintel indicated in detail 7/S3.1 8. A canopy is indicated in detail 4/A3.1. Provide structural calculations and construction details. 9. A bubble note, 1/S6.0, appears north of grid 4 on sheet S2.1. Revise plans to indicate accurate design. MECHANICAL 10. Review not included with this permit. Please provide an item by item response. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. Deferred items; • Fire Alarms • Fire Sprinklers • Roof Trusses When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner DULL OLSO WEEKES FILE COPY archi.iecls pc 1 ' March 11, 2004 RECEIVED Brian Blaylock Senior Plans Examiner MAR 11 2004 City of Tigard 13125 SW Hall Boulevard CITY OF TIGARD Tigard, OR 97223 BUILDING DIVISION Re: BUP2003 -00701 Twality Middle School Addition & Remodel Plan Review Comments dated February 26, 2004 Dear Brian, We received your comments last week. Following is the itemized reply as - e requested. Supplementary information is enclosed as noted in our reply to the comments. Also enclosed are copies of the two addenda which have been issued during the bid phase. I realize most of what is included in the addenda are not items you need to deal with, but I wanted you to have all of the project information for your files. If you read thru the addendum text I believe it will help determine which elements you would be interested in reviewing. There are not significant changes made to the project design by either addendum. Fire & Life Safety 01 1. We request that constructing a two -hour wall at the walkway canopy along the assumed property line not be required as referenced in comment No. o E 1. Based upon our several phone conversations with you, the last being on March 8, we understand the following will apply: c a. The canopy will not be considered a building due to the fact it meets the criteria of UBC Section 409.2 in that it is constructed of unprotected but non - combustible W construction, with no concealed spaces, and is legitimately intended for pedestrian use only (i.e. not for exterior storage or some other purpose). O m = N N 5, r 0 r 0 x ,,, 0 rn a : N ;tf e2k` FJ!T)rc9r,.s „3020 7,W tv 'AS - :rC?04'0.Profcr [ Ftl ovVo A ra >ss r,g�t Cetlo rn to rFPaylr,: k 0302_ o r Re. Iy.d M.. N a 0 M L ARCHITECTURE + INTERIORS + PLANNING , a D U L L O L S O N W E E K E S a r c h u i e n t s pc ' b. Opening protection at connections to buildings under the canopy will not be required because the portion of the canopy along the assumed property line is designed with openings in excess of 50% as described in 409.3. c. The interpretation given in the 1997 UBC Applications Manual allows a walkway structure which is not considered to be a building to be placed parallel and adjacent to an interior property line. 2. We will define the extent of the occupancy separation wall on an addendum drawing (copy attached) and note that the contractor is required to field verify that the existing wall between the kitchen and adjacent spaces continues to the roof deck to provide the 1 -hour occupancy separation. Infill if required will be using wood studs and 5/8- � 9 inch Type "X" gyp board on both sides of this wall. We feel the restroom G cG and mop sink are accessory use spaces to the kitchen, not facilities for MC' f'f o & 03 ::e: sc; and thus not requred to have 60 - minute rated door . �E of • RA" 3. Please see the attached product data information for the wainscot let material. The specifications require this to be a Class A material — please t ) (f see Section 06200 paragraph 2.02.B. I have clouded the product data which discusses flammability and flame spread. This is a product manufactured outside the US, so the technical specs are somewhat different. OK" d l 4. In rooms A102 and A103 the gyp board ceiling is attached directly to the 2x8 and 2x10 roof structure shown on S2.1. Larger soffits in the Commons A101 are detailed on 5/A9.2; smaller furred -down soffits as in the Kitchen are shown on 2x material on 3, 4, and 10/A9.1. The gyp board ceiling in Restroom A106 and Janitor A107 is installed on a manufactured suspended grid - see product information included with this letter. Accessibility 5. Sections #1 through #4 cut through the serving line counter on Sheet K1.7 sets the elevations of the individual cabinets at 34- inches. The serving line is not designed in the typical fashion of a continuous tray slide. It is made up of individual walk -up counter cabinets as shown on this drawing. O rn. 6. We will add dimensions for the grab bars to the enlarged plan 1/A4.2 and t issue by addendum. A copy of the plan is in the attached Addendum #2. o n"l.M ; I:vc +lityr,MS :_06-7;' - Pro '- ect +a:di ..., ays: r: c;;?,. ,oJ3. (•c lc;ck:..,C2uci cr.Itr� ✓i::wPf :rly.,04 o. o ARCHITECTURE + INTERIORS + PLANNING D U L L O L S O N W E E K E S architects pc Structural 7. Calculations for the lintel 7/S3.1 are attached (see Girt at Roll Grill). 8. Framing for the canopy is shown on S2.1; structural details (similar to the larger canopy) are shown on 2, 3, 4, and 7/S6.1; architectural details are shown on 18, 24/A8.10. Supplementary structural calculations are attached. We modified the canopy by addendum to include a built -in gutter. Please see details in Addendum #2. 9. The detail referenced 1/S6.0 is correct for this condition. See architectural details 13, 14/A8.10 for the roofing and flashing. Architectural details are cut reversed from structural, but show the same framing. Thanks for your review of this project, and for the subsequent conversation about the walkway canopy. If you have any questions about our reply or need further information, please give me a call. Sincerely, e Dull Olson Weekes Architects PC r Keith Johnson AIA Associate Principal /Project Manager O C O 0 c Z ti 0 o b, o S, ry ,^ ▪ O 0 z O x .n • O. 4 'O 3 3 iv v . ec is 30 T:vahtt MS 2OO4 % Project i "110 N;: a:Ans r \':., ,,,;J:; Par, ^ii's Blavlo(A 333204 ; ar Reply .um o ✓ o ARCHITECTURE + INTERIORS + PLANNING DULL- 0LS0 WEEK BECENEt architects inc. MAY 2 8 2004 CITY OF TIGARD May 28, 2004 BUILDING DIVISIOP Brian Blalock Senior Plans Examiner City of Tigard 13125 SW Hall Boulevard Tigard, OR 97223 Re: BUP2003 -00701 Twality Middle School Addition & Remodel Plan Review Comments dated April 14, 2004 Brian: Following is our itemized reply as requested. Note that because 5 of our 9 responses to your initial comments (letter dated February 26, 2004) were deemed "accepted ", our responses are for only those items not accepted in your " April 14, 2004 letter. Supplementary information is enclosed as noted in our reply to the comments. Fire & Life Safety 1. We have revised the 2 -hour area separation wall to continue along gridline `4' be •_ d the northwest corner of the Commons building. We have QQI the door at this location, Door A101 B, from a non -rated V �� ® lutnum storefront to 90- minute rated assembly with self - closing device. There will be no relites in the new pair of doors and the exit width will remain the same. A copy of PR 01, dated 5/24/2004, addresses this issue pY > and is attached. a,. ry 2. Accepted, 4/14/2004 3. The WSCT -1 in question is determined to have a Class 'C' Flame Spread, which is a classification found in IBC Ch. 8, Section 803. The classification for 'C' is exactly the same as for Class `III' in OSSC Table 8 -A. For an A -2 0. • 0. occupancy only Class 'II' is allowed in rooms according to UBC Table 8 -B. However, UBC 804.1 lists under "exceptions" that when a compliant fire • 0 1 ''�-r system is provided (Commons is fully sprinklered) the flame z1 s°‘1' classification may be reduced one classification. Therefore, Class Z • x : • ' ' \tFile2k` (— {, 3o o ', n:'y MS - 2GG4,1- Project File \, ^ror() P C:x!c Pem1i;c:B alocK U52804 TMS Plar+ Re,ew Rep! j.doc uz a o . �; ^ ARCHITECTURE + INTERIORS + PLANNING D U L L , - 0 L S 0 N W E E K E S architects ii c. `III' should be allowable. This topic was addressed fully and the conclusion agreed upon during our May 27, 2004 phone conversation. 4. Accepted, 4/14/2004 Accessibility 5. Accepted, 4/14/2004 6. . ,wave added dimensions for the grab bars to the enlarged plan 1/A4.2; ` ange was issued by addendum #2, dated 3/10/2004. A copy of the xy liq, " drawing is attached (note: refer to drawing "RA2.2"). Structural 7. Accepted, 4/14/2004 8. Accepted, 4/14/2004 9. ere were two detail tags referencing 1/S6.0. The tag along gridline `4' is 'rect. Per the Structural Engineer, the incorrect tag at the "GL 5 1/8" X 9 4 0 Z O N )-' /2" has been deleted and a note added to read "Simpson Post Cap f 1 / 218 ACE6 ". Thank you for your review of this project. If you have any questions about our reply or need further information, please give me a call. Sincerely, Dull Olson Weekes Architects Inc O r r i ,/ . i4 Brian G. L reen ,, ooi Project Arch' s0' ry' ,F, R1s '11'1 gl Z .Q. 2 u v1 'rn 4 3 ` l \File2k;ro ec s\03020 ? wa ,?t MS - 2Gr4.1 -Prolecl F !e\Wc d Proce, g 13 Code-PemilS'•B F1kOCK 0:,2.8C4 TMS Par Review Reply doc as to m - ARCHITECTURE + INTERIORS + PLANNING