Specifications 0 I 5 7 Sti/ q e/--vE ar d (44 Church of God Existing Church & New Administration Building 15670 Southwest 98th Avenue Tigard, Oregon 97223 I Sprinkler Monitor & Alarm System k; Data Sheets, Battery and Voltage -Drop Calculations, with Fire Alarm System Drawings. PIG G1TY OF T1GAA� BUI� \NG p\V1S\�N •144.4 DTS SNstenrs, Inc. LDTS Systems, Inc. 7905 Southwest Nimbus Avenue, Beaverton, Oregon 97008 Phone (503) 643 -3127 Facsimile (503) 643 -6194 - Features FIQV 405 • Five programmable Initiating Device Circuits (zones). Each zone may be programmed for: Fire Alarm Control Panel with built -in DACT two -wire smoke detectors, normally open contact devices (pull stations, heat and remote -site upload /download capability waterflow operation, supervisory operation, auto -reset supervisory operation. • Two built -in, Class A or B (Style Z or Y) Notification Appliance Circuits (NACs). NACs may be programmed: silenceable, Descr iption non-silenceable (a strobe circuit can keep p flashing after the panel is silenced), auto- . Gamewell Flex 405 is a 24 -volt, silence (program 5 to 30 minutes), silence five -zone Fire Alarm Control Panel inhibit (60 seconds), coding (march time FACP) with built -in communicator temporal, California). and remote -site upload/download • 3.0 amps of notification appliance power, capability. The integral communica expandable to 5.0 amps (meets the critical ) P Y g power requirements for ADA and UL -1971 AtEi for transmits event information devices). ' (alarms, troubles, supervisories, • Two built-in Form -C Alarm and Trouble relays. faults, etc.) to a UL- Listed central • Supervisory and communication fail outputs. Gamewelln , station. The Flex 405 may be used • Dual -line rotary- or Touch - Tone® -dial DACT in a variety of cost - effective applica- interfaces to public telephone network tions, including: local fire alarm (leased phone lines are not required). _ control panel (communicator dis • 24 Volt operation. abled), fire alarm control panel/ •Built in voltmeter measures: zone voltage; primary AC line voltage; battery voltage; communicator, stand -alone sprin NAC(s) voltage; resettable 24-volt power. kler supervisory communicator, or • Surface Mount Technology (SMT). slave communicator to a UL- Listed • Fully programmable via built -in keypad (no host fire alarm panel (requires normally -open dry contacts to trigger five costly external programmers necessary). channels). Selectable transmission formats allow the Flex 405 to communi- • Complies with NFPA 72 (Local, Central cate to virtually all central stations. Station and Remote Station [DACT only - not polarity reversa /l Fire Alarm Systems). Remote -Site UploadlDownload • Reporting +, 4+1, formats include: 4 +1, 4 +2 Standard + Expanded; 4 +1, 4 +2, Ademco Express. The Flex 405 may be downloaded or uploaded without affecting the system • Integral battery charger for up to 60 hours fire protection. Download system programming, and upload key system of standby power. information such as: current system status, history and walk test files; • Fuseless, power - limited technology meets zone, AC line, NAC 1 and NAC 2, resettable power and battery voltages; UL power - limiting requirements. and system programming. Upload or download within one minute without • Programmable alarm presignal timer, alarm affecting normal fire panel functions. The upload /download function also verification timer, and optional trouble features multiple security techniques. The Flex 405 requires the PK -CD reminder. programming kit, which works with most Hayes - compatible modems • Single person walk test. Fire drill function. (consult factory for listing). • Zone disable capability (software). • 32 -Event history buffer with time - and -date stamp. Accurate real -time clocklcalendar. • Extensive built -in transient protection. • Electronics and operational controls fully enclosed in a lockable cabinet capable of housing up to 7 AH batteries. • Optional: contact- by-zone module, remote annunciator, printer interface for on- or off - line printing. Listings • UL Listed. Gamewell Flex 405 CS -2405 11/25/03 Page 1 of 4 A 150 -Year Tradition Specifications Ordering Information • Single PC board design using Surface Mount Technology (SMT). • Two modular telephone jacks for connec- F405 Five -zone, 24 -volt fire alarm control communicator. tion to RJ31XImodules. Includes backbox, transformer, technical manual, and AC power frame - and -post operating instruction sheet. • 120 VAC, 50160 Hz, 2.3 A. • Wire size: minimum 14 AWG (2.0 mmz) with XRM -24 120 VAC, 100 VA transformer expands NAC power from 600 -volt insulation. 3.0 to 5.0 amps. • Built -in brownout circuitry, built-in voltmeter. SAN -405 Five -zone remote annunciator (RZA -5F), mounts to a Communicator single -gang box (requires ADM -24). ▪ One line-active ho nli indicator for each of two phone lines. • ADM -24 Annunciator driver module (supports SAN -405). • Dual "Kiss-Off" "loow w telephone " signal LED. ne voltage detect" circuitry. RM -5F Five -zone relay module, provides contact -by -zone. • Programmable event codes per each format. • Up to 62 transmitted eventslmessages. CAC -5F Class A converter module. Converts all Class B initiating a eveents. nts. leldeselectable transmissions of 62 device circuits (zones) to Class A. • Five zones may he configured to five channels as a slave communicator (channels PRT -24 Printer interface module, provides an EIA -232 printer are auto - resettable. output. Includes cable, DB9F and DB25 adapter. Communication formats PK -CD Contains programming software for Windows® -based PC Express formats allow d emplete e conaction to P g g be communicated in under five seconds. computer (cable not included). • 20 PPS, 3 +1 standard and expanded. MCBL-7 DACT phone cord, 7 feet (2.134 m) long (two required). • 20 PPS, 4 +1 standard and expanded. • 20 PPS, 4 +2 standard and expanded. BB -17F Battery backbox, required for batteries over 7 AH. • 4 +1 and 4 +2 Ademco Express. Initiating device circuits (zones) TR -3 -R Trim ring. • The Flex 405 includes five programmable initiating device circuits (zones). Circuits 1, 2, 52223 Flex 405 Installation and Maintenance Manual. 4, and 5 are Style B (Class B). Circuit 3 is Style D (Class A). Use the Class A converter module (PIN CAC -5F) to convert all Class B IDCs to Class A. • Each zone may support two -wire smoke detectors. Programming options include: waterflow (silenceablelnon- silenceable), supervisory (standardlauto- reset), pull station, normally- open- contact device. • All circuits are power - limited and fully supervised. • All circuits allow up to 100 ohms of line resistance. Use 12 to 18 AWG wire (3.1 to 0.78 mm Notification appliance circuits • Two Style ZIY (Class AIB) @ 2.5 A each. • All circuits are fully power - limited and meet UL power - limiting requirements. Auxiliary outputs • Resettable four -wire smoke detector power @ 300 mA. Non - resettable power @ 300 mA. • Integral Form -C Alarm and Trouble relays. • Relay drivers for supervisory and communi- cation fail. Cabinet specifications • The compact cabinet can be surface- or semi- flush - mounted. • Knockouts on the top, sides, and back provide ease of wire entry. • Dimensions, Door: 15.219" high x 14.219" wide (38.655 cm H x 36.115 cm W). Backbox: 15.0" high x 14.5" wide x 3.0" deep (38.1 cm H x 36.83 cm W x 7.62 cm D). Trim ring (P /N -R): 18.125 "highx 17.62" wide (46.038 cm H x 44.755 cm W). Page 2 of 4 Flex 405 CS -2405 11/25/03 Data ! Sheet Gameweli WORLDWIDE 615 ...fie.;`«'s„ ..:,..; :;' >st ,:... Series 60 E Conventional Smoke �� Detector :- - �� A Heads /Bases/ Tester %x i :;. x Features , - ". • Compatible with all Gamewell 4 ' conventional systems �° ®°` • Full range of detectors including: external alarm indication is by means of a sufficient amplitude to turn on the SCR that light emitting (red) diode (LED) mounted on sends the alarm signal. - Ionization the printed circuit board within the housing Gamewell's Series 60 Thermal Detector - Photoelectric and p rotruding through the housing to be operates as a combination Rate of Rise/ easily visible. The Ion Detector is Fixed Temperature detector (71035 0 135°F, - Combination Photo /Heat distinguishable from the Photoelectric 71035 -160 @ 160°F, 71035 -210 @ 210°F). It Detector by the color of the alarm indicating contains a pair of matched negative - Rate of Rise /Fixed LED; the Ion's LED appears red versus the temperature coefficient thermistors mounted Temperature Photo's clear color during normal operation. on a printed circuit board within a white poly- p Thermal detectors are readily distinguished carbonate housing. One thermistor is from smoke detectors by having open webs exposed and is therefore in good thermal • Full range of bases, including: to allow the free movement of air around the contact with the surrounding air and responds - Standard 4 °, 6° or 6" low exposed thermistor quickly to changes in air temperature. The Operation other thermistor is insulated from the p rofile Gamewell 's71034 Ionization Smoke Detector surrounding air and responds more slowly. 6° base with flashing operates on the Ionization Chamber principle The detector responds as a Rate of Rise detector when a temperature difference red or green LED utilizing twin compensating chambers with develops rapidly, causing the ratio of the one single -sided ionizing radiation source. resistances of the thermistors to exceed the - 6" base with sounder The ionization chamber system is an inner factory preset level. The detector responds reference chamber contained inside an outer as a Fixed Temperature detector when the - 6° base with relay and smoke chamber. The outer smoke chamber sum of the resistances of the insulated flashing green LED has smoke inlet apertures which are fitted thermistor resistor fixed f and retor compared to the with an insect resistant mesh. At the junction resistance of and fixed sis thermistor reaches Description between the reference and smoke chambers a preset level. Gamewell's Series 60 conventional Smoke is the sensing electrode which is used to a pr e ll's 71041 Combination Photo /Heat Detectors provide a range of detectors convert variations in the chamber currents to designed for the highest effectiveness by a voltage. This voltage is monitored and Detector incorporates the principles of the utilizing the latest technology. The series is produces a signal which latches the detector the Fixed Temperature characteristics u re r to found comprised of an Ionization, Photoelectric, into alarm when a preset threshold level is in the ed Te Thermal acr. Combination Photo /Heat, and Rate of Rise/ reached. Fixed Temperature thermal detectors (135°F, Gamewell's 71033 Photoelectric Smoke The Series 60 Conventional Detector Bases 160 °F, 210 °F). These detectors have been Detector operates on the forward light will accept any of the Series 60 detector carefully researched and have undergone scattering principle. It utilizes a horizontal heads. The bases have a wide interior rigorous testing to ensure that they meet not optical bench which houses an infra -red diameter for ease of access to wire and only existing standards and codes but also emitter and sensor arranged radially to detect terminals. The design of the base is such that the demands of today's high technology forward scattered light. The sensing chamber the detector will fit in one way only and that a environments. is a black molding configured as a labyrinth simple clockwise motion without force is The detector is designed for two wire which prevents ambient light from penetrating required to plug in a detector. operation. All of the detectors in the Series into the chamber. The labyrinth has a fine The 71036 base (4') will mount directly to a 60 product line have the same external gauze cover to prevent insects from migrating 3.5 octagon box (Raco 110 or equal) or a 4' dimensions, with the housing of the Ionization into the chamber. The detector will change octagon box (Raco 125 or equal) with a and Photoelectric being identical. The to the alarm state when reflected light is of round cover /plaster ring (Raco 727 or equal). The other Series 60 bases (6') will mount TYPE/MODEL NUMBER: crimp style terminals and shall provide directly to a 3.5' octagon box (Raco 110 or • ionization (Dual Chamber)Smoke Detectors terminals for remote LED's. equal); to a 4' octagon box (Raco 125 or Gamewell Model 71034 Where indicated on the plans, the contractor equal); or to a 4° square backbox (Raco 190 • Photoelectric Smoke Detectors Gamewell shall furnish bases with a power indicating or equal). Model 71033 utilizing a horizontal optical flashing LED in the base (Gamewell Model Engineers Specifications bench housing the infra -red emitter and 71086 -RED or 71086- GREEN) which shall sensor arranged radially to detect forward use standard screw /crimp style terminals General Specification: The contractor shall scattering light and shall provide terminals for remote LED's. furnish and install where indicated on plans, • Combination Photoelectric /Heat Detector When required, the contractor shall furnish (Insert TYPE /MODEL NUMBER below). The Gamewell Model 71443 utilizing a Gamewell Model 71393 bases with a power combination detector head and twist lock horizontal optical bench along with Fixed indicating flashing green LED in the base base shall be UL Listed and UL Listed as Temperature (135 ° F) capabilities plus a relay with two sets of voltage -free compatible with the alarm panel. The base • Fixed Temperature /Rate -of Rise Electronic changeover contacts (Form C) and may be shall permit interchange with Gamewell's Thermal Heat Detector Gamewell Model used as a 2 or 4 -wire base and shall use other Series 60 Detectors to simplify 71035 (135° F) or 71035-160 (160°F) or standard screw /crimp style terminals and modifications to the installation. The detector 71035 -210 (210°F) shall provide terminals for remote LED's. shall contain an integral LED that shall latch The contractor shall furnish and install where Where indicated on the plans, the contractor in when the unit goes into alarm. RFtransient indicated on plans bases which are shall furnish bases Gamewell Model 71086- techniques shall be employed to minimize compatible with all the Series 60 detectors SNDR with a separately powered (24 Volt) false alarms. available. internal sounder rated at 85 Db © 10 feet and Standard 4 °, 6' and 6' low profile bases shall use standard screw /crimp style (Gamewell Models 71036, 71086 and 71086- terminals and shall provide terminals for LOW, respectively) shall use standard screw/ remote LED's. Technical Specifications Quiescent Current: Photo, Comb. Photo /Heat and Ion 30 to 45 i A at 24 Volts Thermal 55 pA at 24 Volts Alarm Voltage: 6 to 28 Volts Normal Alarm Output: 52mA at 24 Volts Remote Alarm Output: 20 mA maximum, diode gated Temperature Range: Photo, Comb. Photo /Heat and Ion 32° F to 140° F Thermal -5° F to +195° F Humidity: 0% to 95% relative humidity (no condensation) Recommended Spacing: Per NFPA Codes Alarm Current: 6' Detector Base w /Relay 72 mA 41 24 Volts Contact Rating: 6° Detector Base w /Relay 1 Amp @ 24 Vdc / 120 Vac Decibel Rating: 6° Detector Base with Sounder 85 Db @ 10 feet Ordering Information Supplied Model Part Number Quantity Description ❑ 71033 55000 -350 4 Conventional Photoelectric Smoke Detector Head ❑ 71034 55000 -250 Conventional Ionization Smoke Detector Head ❑ 71443 55000 -380 Conventional Combination Photo/Heat Smoke Detector Head ❑ 71035 55000 -150 Conventional Thermal Heat Detector Head (135 °F) ❑ 71035 -160 55000 -151 Conventional Thermal Heat Detector Head (160 °F) ❑ 71035 -210 55000 -152 Conventional Thermal Heat Detector Head (210 °F) ❑ 71036 45681 -200 Conventional 4' Detector Base ❑ 71086 45681 -220 4111 Conventional 6' Detector Base ❑ 71086 -RED 45681 -230 Conventional 6' Detector Base w /Flashing power indicating Red LED ❑ 71086 -GREEN 45681 -231 Conventional 6' Detector Base w /Flashing power indicating Green LED ❑ 71086 -SNDR MB- 1721 -60 Conventional 6' Detector Base with Sounder ❑ 71393 45681 -227 Conventional 6° Detector Base w /Relay and Flashing power indicating Green LED ❑ 71086 -LOW 45681 -232 Conventional 6' Low Profile Detector Base • ❑ 71343 Aerosol for Detector Test ❑ ZNS -B6 ZNS -B6 Addressable base for use with INS -2 Addressable Circuit Specifications and wiring information are provided for information only and are believed to be GarrleT,,,eI I accurate. However, Gamewell assumes no responsibility for their use. Specifications are subject to change without notice; installation and wiring instructions shipped with the product WORLDWIDE should always be used for actual installation. Data and design subject to change. Supply subject to availability GW 8/99 (revised) Printed in 60 Pleasant Street Ashland, Massachusetts 01721 (508) 231 -1400 FAX (508) 231 -0900 UL, CSFM, FM _ Data o Sheet Gamewell 700 WORLDWIDE Non Coded Century - PU .ice 6 ,. �: �� Features • Durable construction. - ..f� � = -` • Compact design, blends with surroundings. '`iii• • Recessed pull lever prevents accidental operation. FIR • Self clearing breakglass design. F F L. It . ,: • • Shock and vibration resistant, �, it � . ! 4 • Available with wire leads or R 5 screw terminals. Fr • Surface or semi -flush installation. • Optional general alarm keyswitch . Form C auxiliary contact. In addition, from broken particles of glass. Space Model M46 -30 provides a Form C is provided within the station housing • Double Action option. general alarm keyswitch which is for storage of one replacement glass • Key Reset option. mounted behind the pull lever. The rod. keyswitch is not accessible until the • Die cast aluminum construction. pu .Thegeneralalarm St Application • U.L. Listed keyswitch is provided with duplicate The Century Station provides a non- • CSFM terminals for in and out wiring. coded manual alarm initiating input to • ADA Approved Operation a Gamewell conventional fire alarm pP system; i.e., Flex 300/3000, Flex 500/ The station is essentially a switch, en- SimpliFire, Zans 400, INS -2 CZI's. Description closed in the fire alarm box shell. It is operated by the simple act of pulling Engineers Specification Of modern, compact design, the non- forward a readily identifiable bullseye The manual fire alarm station shall be a coded fire alarm Century Station alarm lever marked "Pull ". Upon Gamewell Century Station model satisfies architectural requirements for operation, this lever locks in the alarm number M -46 and shall be listed by a manual alarm initiating device which position and remains so until reset by U.L. Inc. does aspects of a building detract from decorative an authorized person. Resetting is P g inte yet accomplished by either releasing the The single /double action non -coded easily observed. screw at the top right hand edge of the station shall consist of a die -cast The Century Station is shock and station, or using the CAT60 key with the aluminum housing fitted with a pullout vibration resistant as no mercury Key Reset option. Both of these actions lever which, when operated, locks in element type contacts are used. A release the front of the station which is position after activating alarm initiating toggle switch of rugged construction hinged at the bottom, thereby exposing contact. provides exceptionally high resistance the toggle switch which can then be The body of the manual station shall be to accidental operation from sudden manually reset, permitting the cover to hinged to a backplate assembly which shock. Accidental operation from be replaced in its normal position. is locked by a slot head screw. contact with moving objects also is An optional breakglass rod may be Resetting the station after operation virtually impossible as the pull lever used with all stations; however it does shall require opening the front cover does not protrude. not detract from the station's for access to the alarm switch. The Century Stations are available in appearance when it is not used. The The manual fire alarm station shall be three models which can be used for breakglass type station is frequently adaptable for surface or semi flush both surface or semi -flush installation. specified for its psychological value in installation. In addition, there shall be Model M46- 28 has a N/O alarm contact the prevention of malicious false alarms. provisions for a self-clearing breakglass with 4 -wire leads for in and out It also provides additional protection connections. Model M46 -29 and M46- against tampering. The self - clearing mechanism and a key operated general 30 use screw terminals for in and out design prevents jamming of the station alarm switch accessible only after the alarm connections and an extra and there is no danger to the operator pull out lever has been activated. Technical Specifications Installation must be at least 1/2" deep, A single - Material: Box face, pull lever, target The Century Station should be installed gang switch box cannot be used. background, and backbox for surface approximatelyfivefeetfromthefinished Breakglass Option mounting are die -cast aluminum. floor level. For surface type stations, a Place the glass rod in the slots on the (backbox sold seperately) die -cast backbox p/n 28762 must be hinged front. Be sure the "PULL" lever is Finish: Fire alarm red, smooth gloss ordered separately. This backbox has always behind the glass rod. Return the enamel. Raised cast lettering is high- tapped holes top and bottom for 3!4° hinged front to the station and tighten lighted, Target background for pull lever conduit. Conduit bushings must be used the slot head screwsecurelytoassure is white gloss enamel. to avoid abrasion of the incoming wires. proper engagement of the station Dimensions: M- 46 -4 - /8 high by The unused conduit entrance should assembly. be closed with a 3/4 "flush pipe plug, not tion Double Action O 3 '/ wide by • 15 / 16 deep. furnished. Also 1/2" or 1 ° conduit can be p M -46 with key reset option -6 - high used with proper bushings. Requires lifting double action lever by 3 - wide by 75/16` dee Weatherproof Gasket: Neoprene before pulling down "PULL" lever. Surface backbox pin 28762, 4 - /8 high gasket pin 50397 with adhesive backing Key Reset Option by 3 - wide by 2 - deep. provides for weatherproof installation Requires turning a standard CAT60 key Contact Rating: on surface backbox p/n 28762. (included) to reset station. Key reset SPST, DPDT For semi -flush installation, a standard 4" option for flush mounted installations 6 amps at 125 VACNDC or 4- 11/16" square box with single gang only. 3 amps at 250 VACNDC plaster ring is recommended. The total SPDT (keyswitch) depth between the back of the wall box and face of the plaster ring must be at 3 amps at 125 VAC least 2-1/2". If a 1-1/2" deep box is used, KEY OPERATED Shipping Weights: All flush stations 1 the plaster ring must be at least 1° deep. "GENERAL ALARM SWITCH" lb., surface backbox 1 lb. If a 2" deep box is used, the plaster ring " "' K GA r 4 o "ED NC C J L ALARM } GA 0 NORMAL r0 0 [ NO l IN u IN�t Le NO • "ED "ED LL C OUT C { } OUT OUT { NORMAL NC eLK BLK 0 NORMAL NC INIT. CCT AUX. CC1 M46 -28 INIT. CCT. M46 -29 AUX. CCT- M46-30 i ' Ordering Information ! Supplied Quantity Part Number Description PULL ❑� M46 SPST Switch with in and out leads on 4%" initiating circuit ❑ M46 -28T SPST Switch with terminals IVA kia , u M46 -29 DPDT Switch with in and out terminals on initiating circuit • ❑ M46 -30 DPDT Switch with in and out 3y � .; • terminals on initiating circuit and it SPDT general alarm keyswitch with 15/16 in and out terminals Options for above stations: ❑ 30653 Double Action ❑ 30653 -01 Key Reset ❑ 30653 -02 Key Reset/Double Action ❑ 28762 Backbox, surface mounting - ❑ 50397 Weatherproof Gasket ❑ 27060 Glass Rod Gartieviel i Specifications and wiring information are provided for information only and are believed to be ( accurate. However, Gamewell assumes no responsibility for their use. Specifications are subject to change without notice; installation and wiring instructions shipped with the product WORLDWIDE should always be used for actual installation. 60 Pleasant Street Data and design subject to change. Supply subject to availability GW 1/99 (revised) Printed in U.S.A. Ashland, Massachusetts 01721 U.L., CSFM (508) 231 -1400 FAX (508) 231 -0900 I • L MEA FIRE ALARM SYSTEMS Helping People Take Actions"° N o SERIES NS SINGLE & MULTI - CANDELA • HORN STROBE APPLIANCES SERIES NH HORNS A Family of Multi - Candela Appliances" Description R The Series NS Horn Strobe Appliances will satisfy virtually -� all requirements for indoor, wall mount applications. VA* ,,'�' The Series NH Horn and the horn portion of the Series Series NH Series NS NS include a selectable continuous horn tone or temporal pattern (Code 3) with selectable dBA settings of 90 or 95 __ dBA- kv _ °.f 1 _ ' ,� ' _ Strobe options include 1575cd or Wheelock's patented , Multi - Candela strobe with field selectable candela settings • of 15/30/75/110cd. Multi - Candela Indicator These versatile Horn Strobe Appliances may be (bottom of Strobe Lens) synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or Wheelock's PS- 12/24 -8MP Power Supply with patented Sync Features Protocol. Additionally, the audible may be silenced while Approvals include: UL Standard 1971, UL Standard 464, maintaining strobe activation. New York City (MEA), California State Fire Marshal All models of the Series NS and NH are designed for (CSFM) and Factory Mutual (FM) Pending: Chicago (BFP) maximum performance, reliability and cost - effectiveness while meeting or exceeding the latest requirements of • ADA/NFPA/UFC /ANSI compliant NFPA 72 /ANSI 117.1/UFC and UL Standards 1971 and • Complies with OSHA 29, Part 1910.165 464 as well as meeting ADA requirements concerning • Field Selectable Candela Settings 15/30/75/110cd photosensitive epilepsy. (24 VDC Multi - Candela models) or 1575cd in 12 or 24 VDC • Wheelock's patented 2 -Wire Series NS Horn Strobes and Selectable Continuous Horn or Temporal (Code 3) Series NH Horns offer more features with low current draw. • 2 Selectable dBA settings of 90 and 95 dBA in both tones • Patented Universal Mounting Plate • 12 and 24 VDC models with UL "Regulated Voltage" using filtered DC or unfiltered VRMS input voltage • Wall Mount • NH horn is selectable 12 or 24 VDC in 1 unit • Synchronize with Wheelock SM, DSM Sync Module or Wheelock PS- 12/24 -8MP Power Supply with built -in • sync protocol • Fast installation with IN /OUT screw terminals using #12 to #18 AWG wires Copyright 2003 Wheelock Inc. All rights reserved ARCHITECTS AND ENGINEERS SPECIFICATIONS The audible /visual notification appliances shall be Wheelock Series NS Horn Strobe appliances and Series NH Horn appli- ances or approved equals. The Series NS appliances shall meet and be listed for UL Standard 1971(Emergency Devices for the Hearing- Impaired for Indoor Fire Protection Service): The Series NH Horn shall be UL Listed under Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of two (2) field selectable settings for dBA levels (90 and 95 dBA) and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/110 candela. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules or Wheelock's PS- 12/24 -8MP Power Supply with built -in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non - synchronized flash -rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation. The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single -gang, double -gang, 4 -inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. SPECIFICATION & ORDERING INFORMATION Order Non- Sync w/ SM, DSM 24 12 2 Agency Approvals Model Code Strobe Candela Sync or PS- 12124 8MP VDC VDC WIRE Mounting Options# S y UL MEA CSFM FM BFP NS- 24MCW -FR 9404 15/30/75/110 X X X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 24MCW -FW 9405 15/30/75/110 X X X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 241575W -FR 7806 15 (75 on Axis) X X X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 241575W -FW 7811 15 (75 on Axis) X X X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 121575W -FR 7816 15 (75 on Axis) X X - X X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 121575W -FW 7818 15 (75 on Axis) X X - X X B,D,E,F,G,H,J,N,O,R,X X X X X X NH- 12/24 -R 7449 - X X X X X B,D,E,F,G,H,J,N,O,R,X X X X X X NH- 12/24 -W 7500 - X X X X X B,D,E,F,G,H,J,N,O,R,X X X I X X X Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA Distributed By: National Sales Office 800- 631 -2148 Canada 800-397-5777 in c.co E- Mail: re � A o wheelocinm http: / /www.wheelockinc.com Member e 273 Branchport Avenue • Long Branch, NJ 07740 • TEL: 732 - 222 - 6880 • FAX: 732 - 222 - 2588 S2100 12103 at mot r:- "-", welccoc MEA 1 M h, - I . I i FIRE ALARM SYSTEMS Helping People Take Actions"" DESCRIPTION: SERIES RSSWP, ASWP, AHWP, MTWP Wheelock's Weatherproof Strobe, Audible Strobe, Audible and MT -12/24 Horn and Multitone Strobe appliances have an extended temperature range of -31 °F to 150°F ( -35 ° C to 66 °C) that WEATHERPROOF STROBE will satisfy virtually all outdoor and severe environment WEATHERPROOF AUDIBLE STROBE applications. All strobes are Indoor /Outdoor UL Standard AND WEATHERPROOF AUDIBLES 1638 Listed and rated for 180 candela on axis @ 78 °F (25 °C) and 75 candela at -31°F (35 °C) with low current draw. • The Wheelock Weatherproof Appliances are designed for F( i ta SERIES MTWP maximum performance, reliability, and cost effectiveness 4 '" Mounted to lOB -R • while meeting or exceeding the latest requirements of �' R E, NFPA 72 (National Fire Alarm Code), UL Standard 1638 (Standard for Visual Signaling Appliances), and UL . •• ,. Standard 464 (Standard for Audible Signaling Appliances). '!�-' F I R E Series RSSWP Strobes, SeriesASWP Audible Strobes and SERIES RSSWP l Series AHWP Audibles may be synchronized when used Mounted to WPSBB -R ++' in conjunction with the Wheelock SM and DSM Sync T e EIRE Modules or the PS- 12/24 -8MP Power Supply with Wheelock's Patented Sync Protocol. The Series MTWP is a true 4 -wire appliance. The strobe portion can be SERIES AHWP synchronized as stated above. The multitone portion Mounted to WBB -R cannot, but it can be connected to a coded fire alarm system. Weatherproof Strobe Series RSSWP Is UL Standard 1638 approved for Indoor /Outdoor use. The appliances use a Xenon flashtube with solid state F circuitry enclosed in a rugged Lexan® lens to provide SERIES ASWP t Mounted to WPBB -R R --� ; maximum visibility and reliability for effective visual E - :_ signaling. The Series RSSWP mounts to a Series WPSBB Weatherproof Backbox. Features Weatherproof Audible Strobe and Audible Series • Approvals include: UL Standard 1971, California State ASWP and AHWP Fire Marshal (CSFM) and New York City (MEA), Factory Is UL Standard 1638 and UL Standard 464 approved for Mutual (FM) and Chicago (BFP) See approvals by model Indoor /Outdoor use and offer a field selectable choice of in Table 8 continuous horn or temporal pattern (Code 3) when • Designed to meet or exceed NFPA, /UFC /ANSI 117.1/ constant voltage from the Fire Alarm Control Panel (FACP) OSHA Part 29, 1910.165, and ADA requirements is applied. Additionally, the audible has three (3) selectable dBA settings of 99, 95, and 90 dBA in both tones and, • UL Standard 1638 and UL Standard 464 listed with when synchronized, may be silenced while maintaining extended temperature range of -31° to 150 °F ( -35 °C to strobe activation. The Series ASWP mounts to a WPBB 66 °C) Weatherproof Backbox while the Series AH mounts to a • 24 VDC with new UL "Regulated" Voltage Range: of WBB Weatherproof Backbox. 16 -33 VDC using filtered DC or unfiltered FWR voltage Weatherproof Multitone Strobe and Multitone Horn Note: The Series MT -12/24 voltage range is 10.5 - 15.6 Series MTWP and MT -12/24 VDC (for 12V) and 20 -31 VDC (for 24V) Is UL Standard 1638 and UL Standard 464 approved for • Sync/Non -Sync in each product. Note: The audible Indoor /Outdoor use and offers a field selectable choice portion of the Series MTWP and MT -12/24 is non sync of 8 nationally and internationally recognized alerting only signals. Additionally, the audible has 2 installer selectable • Synchronize with Series SM, DSM Sync Modules or sound output levels: Standard and high covering a range PS- 12/24 -8MP Power Supply with built -in patented sync (depending on selected signal) of 76 -94 dBA reverberant. protocol The Series MTWP is a true 4 wire appliance. The Strobe portion can be synchronized or non - synchronized. The • Selectable dBA settings multitone (audible) portion cannot be synchronized, but it • Selectable alert signals can be connected to a coded fire alarm system. The Series • IN and OUT wiring termination that accepts two #12 -18 MTWP and the MT -12/24 mount to a series IOB Backbox. AWG wires at each terminal • Inputs are polarized for compatibility with Copyright 2003 Wheelock, Inc. All tights reserved. industry standard reverse polarity supervision AWARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THE INSTALLATION INSTRUCTIONS ARE AS FOLLOWS: P84135 FOR SERIES RSSWP, P83957 FOR SERIES ASWP, P83641 FOR SERIES AH -WP, P84150 FOR SEREIS MTWP AND P824671 FOR SERIES MT- 12/24 -R. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING, REPLACING OR CHANGING APPLIANCES WILL EFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ". • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. SPECIFICATIONS AND ORDERING INFORMATION Sync w/ SM, Strobe cd Strobe cd Outdoor Model Order Non- DSM @ -31 °F a@ 77 °F dBA Input Mounting Code Sync or PS- 12/24 -8MP ( -35 °C) (25 °C) Voltage Options* Strobe RSSWP- 2475W -FR 9013 Yes Yes 75cd 180cd - 24 VDC T RSSWP - 2475W -FW 3034 Yes Yes 75cd 180cd - 24 VDC T Audible Strobe ASWP - 2475W -FR 9012 Yes Yes 75cd 180cd 90/95/99 24 VDC 1 Multitone Strobe MTWP- 2475W -FR 8420 Yes Yes, Strobe Only 75cd 180cd 76 -94 24 VDC M Homs /Audibles AH- 24WP -R 7416 Yes Yes N/A N/A 90/95/99 24 VDC K AH- 12WP -R 7415 Yes Yes N/A N/A 90/95/99 12 VDC K MT 1224 -R 5023 Yes No N/A N/A 76 -94 12/24 VDC M Back Boxes USE WITH WPSBB -R 9751 RSSWP WPBB -R 9014 ASWP 10B-R 5046 MTWP & MT- 1224 -R WBB -R 2959 AHWP Sync Modules and Power Supply SM- 12/24 -R 6369 - - - 12 or 24 VDC W DSM-12/24-R 6374 - - - - - 12 or 24 VDC W PS- 1224 -8MP 3046 - - - - - 120220 VAC *Refer to data sheet S7000 for mounting options ARCHITECTS AND ENGINEERS SPECIFICATIONS The Weatherproof Strobe appliances shall be Wheelock Series RSSWP -2475W strobes or approved equals. The Series RSSWP shall meet and be listed for UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor/ Outdoor use. The strobe appliances shall produce a flash rate of 30 -62 flashes per minute over the Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be rated at 75cd and shall operate over an extended temperature range of -31°F to 150 °F ( -35 °C to 66 °C). All inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel. When synchronization is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Modules or the Wheelock PS- 12/24 -8MP Power Supply with built -in, patented sync protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The Series RSSWP shall be mounted only to the WPSBB -R Backbox. The Weatherproof Audible Strobe and Audible appliances shall be Wheelock Series ASWP -2475W Audible Strobes and Wheelock Series AHWP Audible Horns or approved equals. The Series ASWP and Series AHWP shall meet and be listed for UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor /Outdoor use. The strobe appliances shall produce a flash rate of 30 -62 flashes per minute over the Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be rated 180cd @ 77 °F (25 °C) and 75cd at -31°F ( -35 °C) and shall operate over an extended temperature range at -31°F to 150 °F ( -35 °C to 66 °C) and be listed for maximum humidity at 95% RH. All inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). The Series ASWP shall be mounted only to the WPBB -R Backbox while the Series AHWP shall only be mounted to the WBB -R Backbox. The weatherproof audible strobe appliances shall be designed for two -wire operation and shall provide either a continuous or temporal (Code 3) tone when constant voltage from a Notification Appliance Circuit (NAC) of the Fire Alarm Control Panel (FACP) is applied. They shall be designed so that the audible signal may be silenced while maintaining strobe activation. When synchronization is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Modules or the Wheelock PS- 12/24 -8MP Power Supply with built -in, patented sync protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync fails to operate. (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The Weatherproof Multitone Strobe and Multitone Audible appliances shall be a Wheelock Series MTWP and MT -12/24 or equivalent. The Series MTWP shall meet and be listed for UL Standard 1638 (Standard for Visual Signaling Appliances) for indoor /outdoor use. The strobe portion of the appliance shall produce a flash rate of 30-62 flashes per minute over the listed voltage range of 20 -31 VDC and shall incorporate a Xenon flash tube enclosed in a rugged Lexan® lens. TThe strobe shall be rated 180cd @ 77 °F (25 °C) and 75cd at -31 °F ( -35 °C) and shall operate over an extended temperature range at -31 °F to 150 °F ( -35 °C to 66 °C) and be listed for maximum humidity at 95% RH. All inputs shall be polarized for compatibility with industry standard reverse polarity of circuit wiring by a Fire Alarm Control Panel. The audible portion of the Series MTWP as well as the Series MT -12/24 shall provide eight field selectable alarm signals. The signals shall consists of: Horn. Bell, March Time, Code 3 Horn, Code 3 Tone, Slow Whoop, Siren and Hi /Lo. Tone selection shall be by a durable dip switch assembly. Clips or Jumpers are not acceptable. The appliance shall provide two output sound levels: Standard and High dBA. The range of dBA shall be 75 to 94 dBA. The Series MTWP shall have an operating voltage of 24 VDC (nominal) while the Series MT -12/24 shall operate at either 12 or 24 VDC (nominal) using filtered power or unfiltered power (full wave rectified). Both models shall have provisions for In/ Out field wiring using terminals that accept #12 to #18 AWG wiring. When synchronization is required, the Series MTWP shall be compatible with the Series SM and DSM Sync Modules or with the Series PS- 12/24 -8MP Power Supply with built -in, patented sync protocol. Note: The Strobe portion of the Series MTWP may be synchronized. The audible portion of the appliance cannot. The audible portion of the appliance can be connected to a coded fire alarm system. The Series MTWP and the Series MT -12/24 shall be mounted only to the IOB -R Backbox. Due to continuous development of our products. specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY Distributed By: NATIONAL SALES OFFICE 800 -631 -2148 �� Canada 800 - 397 -5777 rte. 11 all re E -Mail: Info @wheelockinc.com .. . http://www.wheelockinc.com 273 BRANCHPORT AVENUE • LONG BRANCH. NJ 07740 • TEL: 732 - 222 -6880 • FAX: 732 - 222 -2588 S9004 12/03