Correspondence OFFICE COPY
March 15, 2004 �i��U�n�iVuypupf�l +�
Michael Boumann
CITY OF TIGARD
Sanderson Safety OREGON
1101 SE 3`
Portland, OR 97214
RE: FIRE SUPPRESSION SYSTEM @ COOK PARK
Building Permit: BUP2004 -00104 Construction Type: VN
Tenant Name: Concession Stand Occupancy Type: B
Address: 17005 SW 92 Avenue Occupant Load: 6
The plan review was performed under the State of Oregon Mechanical Specialty Code •
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
• The automatic fire suppression system shall be interconnected to the fuel or current
supply for the cooking equipment and arranged to automatically shut off all •
equipment under the hood when the suppression system is activated. Shut off valves
or switches shall be of a type that requires manual operation to reset. 509.5 OMSC
• A readily accessible manual activation device shall be located at or near a means of
egress from the cooking area, a minimum of 10 feet and a maximum of 20 feet from
the kitchen exhaust system. The manual activation device shall be located a minimum
of 4 1 /2 feet and a maximum of 5 feet above the finished floor. Instructions for
operating the fire suppression system shall be posted adjacent to manual activation
device. 509.4 OMSC
• An approved K -type portable fire extinguisher shall be installed within 30 feet of the
cooking equipment, as measured along an unobstructed path of travel. 1006.2.7
TVFR99 -01
• Extinguishing systems shall be serviced at least every six months. 1006.2.8 TVFR99-
01
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construct'. - : 106.4.2 OSSC
Respectfully
City of Tigard
Approved Plans
rian Bl..ck, By 1 Date 3'/S -04
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772