Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 August 23, 2007 • rr RE: FIRE ALARM SYSTEM T I GARD Project Information Building Permit: BUP2007 -00416 Construction Type: 3B Tenant Name: Westgate Baptist Occupancy Type: E Address: 10730 SW 130th Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition the Oregon Fire Code 2007 edition and NFPA 72. The submitted plans are approved subject to the following. General requirements A key box for building access may be required. Please contact the local Fire Marshal's Office for an order form and instructions regarding installation and placement. (OFC 506) A separate low- voltage electrical permit is required for installation and inspection of alarm wiring. A completed inspection and testing form is required at the time of final inspection containing the information as outlined in NFPA section 10.6.2.3. TESTING — NFPA 72 Chapter 10, OFC 901.2.1, 901.5, 903.5 1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building inspector. All functions of the system or alteration shall be tested. 2. A record of completion in accordance with NFPD 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided. 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4, OSSC chapter 9 & 11 4. When required; Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal. MANUAL ALARM - 1109.2.3.5, 1109.2.3.6 OSSC Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 5. Manual Fire Alarm activation devices when installed shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. • Side Reach — 9 inches to 54 inches above the floor. ALARM SIGNALS — OFC 903.4 6. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the fire code official, shall sound an audible signal at a constantly attended location. 7. Duct smoke detectors shall be connected to the building's fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open -area detection. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. espectfully 074 • an Nelson, Senior Plans Examiner Advanced Security & Fire RECEi�/E'D 2218 NE Sunrise Lane, Hillsboro OR 97124 (503) 519 -4550 Fax (503) 640 -8311 CI 0 .9 2007 OF T/GARD July 14, 2007 BoLDING D IVISION Fire Alarm Operational Matrix General Overview The fire alarm system will have battery back up to sustain it in the case of an AC power failure. Alarm system will have dual phone lines, a primary and secondary, if the primary fails the secondary will transmit signals to central station. All functions of the fire alarm system are supervised, (AC power, low battery, phone line integrity, and all alarm circuits. ) Fire alarm troubles and alarms are both transmitted to the central station and annunciated locally at the keypad and horn / strobes. Specific Operation • Troubles are annunciated at keypad in English text, at the same time they are transmitted to the central station. Operator at central station will call a predetermined response list to notify of trouble. Advanced Security & Fire will be notified of system troubles at the same time. • Alarms will be transmitted to the central station as well as annunciated locally. Central station will notify 911 of fire alarm, and then call premises to try and verify alarm. Response list will be called to notify users of alarm. • Alarms can be silenced at the keypad by pressing fire silence button. • Fire system will be in trouble until fire alarm system is reset by pressing the fire reset button. • Common area smoke detectors, HVAC duct smoke detectors, and sprinkler water flow monitor for smoke and trigger a fire alarm. • Upon trigger of fire alarm by any smoke detector, sprinkler water flow, or manual fire pull station alarm will be annunciated locally via horn / strobe devices, central station will be signaled, HVAC units and fire smoke dampers will be shut down by the fire alarm panel. Company Information Advanced Security & Fire is located in Hillsboro, Oregon and is owned and operated by David Moravik. I have been in the alarm industry since 1981 and licensed as a journeyman low voltage electrician since 1984, ( license # 611LEA ). My state of Oregon electrical license is ( CLE -8 ). Advanced Security & Fire is registered with the state of Oregon contractor's board (contractor's board # 166176). We are a member of the NFPA, and the local fire and burglary alarm association. Central Station Information Advanced Security & Fire monitors its alarm systems through Central Station Monitoring in Estacada, Oregon. They are certified to monitor all alarm system types. Phone # is ( 503- 630 -2896 ). Sincerely, Advanced Security & Fire - Global Project Values: SILENT Project Name: I Westgate Baptist Church Ph #3 I Standby Hours: I 60 I KNIGHT Project ID:I I Alarm Mins: I 5 I Prepared By:IAdvanced Securtiy & Fire I Derating Factor:I 1.2 I SK - 5208 Ca;cuatUons Date:I5 /24/2007 I Voltage Drop Warning Threshold % :I 10 Panel ID: (SK -5208 I Model: SK -5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: ISecurity Closet I Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts (di %Drop Circuit Name Qty /oDrop Standb ry Alarm & Type 1000 Ft. One -Way Ohms EOL SK - 5208 SK -5208 Main Control 1 0.140 0.160 NAC - CKT SK -5208 Prgm'd NAC's 4 0.000 0.160 ALM - RLY SK -5208 Pgm Alm Rly 0.000 0.000 SK - 5217 SK -5217 Zone Expdr 1 0.060 0.260 SK - 5235 SK -5235 LCD Remote 1 0.035 0.050 SK - 5280 SK - 5280 Display Mod 0.000 0.000 SK - 5220 SK - 5220 Dir Con Mod 0.000 0.000 SK - 7181 SK -7181 Zn Cnvtr 0.000 0.000 5824 Serial /Parallel Cnvtr 0.000 0.000 IDC - Initiating Device Ckt 1 0.001 0.095 IDC - 2 Initiating Device Ckt 2 0.001 0.095 IDC - Initiating Device Ckt 3 0.000 0.095 IDC Initiating Device Ckt 4 0.000 0.000 IDC - Initiating Device Ckt 5 0.000 0.000 IDC - Initiating Device Ckt 6 0.000 0.000 IDC - Initiating Device Ckt 7 0.000 0.000 IDC - Initiating Device Ckt 8 0.000 0.000 IDC - Initiating Device Ckt 9 0.000 0.000 IDC - Initiating Device Ckt 10 0.000 0.000 IDC - Initiating Device Ckt 11 0.000 0.000 IDC - Initiating Device Ckt 12 l 0.000 0.000 IDC - Initiating Device Ckt 13 0.000 0.000 IDC - Initiating Device Ckt 14 0.000 0.000 IDC - Initiating Device Ckt 15 0.000 0.000 IDC - Initiating Device Ckt 16 0.000 0.000 IDC - Initiating Device Ckt 17 0.000 0.000 IDC - Initiating Device Ckt 18 0.000 0.000 IDC - Initiating Device Ckt 19 0.000 0.000 IDC - Initiating Device Ckt 20 0.000 0.000 IDC -21 Inactive, Add SK -5217 0.000 0.000 IDC -22 Inactive, Add SK -5217 0.000 0.000 IDC -23 Inactive, Add SK -5217 0.000 0.000 IDC -24 Inactive, Add SK -5217 0.000 0.000 IDC -25 Inactive, Add SK - 5217 0.000 0.000 IDC -26 Inactive, Add SK -5217 0.000 0.000 IDC -27 Inactive, Add SK -5217 0.000 0.000 IDC -28 Inactive, Add SK -5217 0.000 0.000 IDC -29 Inactive, Add SK -5217 0.000 0.000 IDC -30 Inactive, Add SK -5217 0.000 0.000 NAC -1 1st Floor S Side 0.000 0.750 #16 Solid 4.02 100 0.80 19.80 2.96% NAC -2 1st Floor S Side 0.000 0.875 #16 Solid 4.02 179 1.44 19.14 6.17% NAC -3 1st Floor N Side 0.000 0.750 #16 Solid 4.02 260 2.09 18.83 7.69% NAC-4 1st Floor N Side 0.000 0.750 #16 Solid 4.02 290 2.33 18.65 8.57% Aux Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 _ 20.40 0.00% Total Standby Current (Amps) 0.237 4.040 Total Alarm Current (Amps) Standby Time In Hours 60 0.083 Alarm Time In Minutes / 60 (5 Mins) • Total Standby AH Required 14.196 0.337 Total Alarm AH Required Total Combined AH Required 14.53 Command Shortcuts Multiply By The Derating Factor 1.20 - - Minimum Battery AmpHours Required 17.44 me Configure Circuits Print Page Circuit Configuration Project Information Project Name: Westgate Baptist Church Ph#3 Project ID: 0 Prepared By: Advanced Securtiy & Fire Date: 5/24/2007 Ckt. Number: IDC -1 Panel ID: SK -5208 Ckt. Name: Initiating Device Ckt 1 Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 15 System Sensor 2W -B 0.000 0.100 0.001 1.500 #N /A 0.000 0.000 0.000 0.000 #N /A 0.000 0.000 0.000 0.000 #NIA 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.001 0.095 Ckt. Number: IDC -2 Panel ID: SK -5208 Ckt. Name: Initiating Device Ckt 2 Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 10 System Sensor 2W -B 0.000 0.100 0.001 1.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.001 0.095 Ckt. Number: IDC -3 Panel ID: SK -5208 Ckt. Name: Initiating Device Ckt 3 Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 7 System Sensor 2W -B 0.000 0.100 0.000 0.700 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.095 } ... FIRE r "1 Wh22IOGJC i. FIRE ,���,cs.. Fire & r`':"...;•41 Life ' Safety ■ Systems NAC Tool Design Report I Design Name: Design 1 Page 1 of 2 File Name 5/24/2007 See disclaimer below * Design Thresholds: Voltage: 15 % of Panel / Booster Voltage Current: 90 % of Circuit Size Power: 85% of Amplifier Wattage PANEL: Panel 2 (PWR Booster - Silent Knight 5495) Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier Voltage (feet) Class lym Size (Watts) Panel 2 (PWR 24VDC Santuary - Project 280.00 16 Class B AudibleNisual 1.50 A Booster - Silent Knight Phase #3 5495) Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options 10Ft (f Current Voltage NS- 24MCW -FR 109404 110cd 88 - 97 60.00 0.248 A 0.802 V 19.598 V Std B,D,E,F,G,J,N NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.253 A 0.325 V 19.272 V Std B,D,E,F,G,J,N NS- 24MCW -FR 109404 110cd 88 - 97 130.00 0.269 A 1.075 V 18.197 V Std B,D,E,F,G,J,N NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.272 A 0.166 V 18.031 V Std B,D,E,F,G,J,N NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.273 A 0.083 V 17.948 V Std B,D,E,F,G,J,N Circuit Totals: 280.00 1.316 A 2.452 V Voltage Drop: 10.22 % Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier Voltage (feet) Class Type Size (Watts) Panel 2 (PWR 24VDC Circuit B 4/ 0.00 16 Class B AudibleNisual 1.50 A Booster - Silent Knight � S . 5495) Model Number Order Code Candela dBA Distance Actual Voltage Drop Applied Settings Mounting Options 10Ft (feet) Current Voltage 0.00 0.000 A 0.000 V 0.000 V Circuit Totals: 0.00 0.000 A 0.000 V Voltage Drop: 0.00 % Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier Voltage (feet) Class Type Size (Watts) • wheelock Fire & Life Safety Systems NAC Tool Design Report I • Design Name: Design 1 Page 2 of 2 File Name 5/24/2007 See disclaimer below * Design Thresholds: Voltage: 15 % of Panel / Booster Voltage Current: 90 % of Circuit Size Power: 85% of Amplifier Wattage Panel 2 (PWR 24VDC Circuit C 4' 0.00 16 Class B AudibleNisual 1.50A Booster - Silent Knight .S 5495) Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options IOFt (feet) Current Voltage 0.00 0.000 A 0.000 V 0.000 V Circuit Totals: 0.00 0.000 A 0.000 V Voltage Drop: 0.00 % Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier Voltage (feet) Class Type Size (Watts) Panel 2 (PWR 24VDC Circuit D / 0.00 16 Class B AudibleNisual 1.50 A Booster - Silent Knight 5495) Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options IOFt (f Current Voltage 0.00 0.000 A 0.000 V 0.000 V Circuit Totals: 0.00 0.000 A 0.000 V Voltage Drop: 0.00 % . * This document provides information on an as -is basis to assist users and their technical advisors in selecting elements for notification circuits and/or facility communication systems. Wheelock Inc. does not hold itself out as providing design or engineering services. Users of this program are solely responsible for their own selection and use of products based on values supplied by users, and . Wheelock Inc. shall have no liability therefor. ALL WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. � F B� IRE ' - ''�yy wheelock— Fire & Life Safety Systems NAC Tool Battery Calculations I Date 5/24/200 Page 1 of 1 See disclaimer below* Total Current Draw For Design 1 1.31 Minimum aH Required 0.109 Order Code Model Number Qty Current (Amps) 109404 NS- 24MCW -FR 5 1.316 * This document provides information on an as -is basis to assist users and their technical advisors in selecting elements for notification circuits and/or facility communication systems. Wheelock Inc. does not hold itself out as providing design or engineering services. Users of this program are solely responsible for their own selection and use of products based on values • supplied by users, and Wheelock Inc. shall have no liability therefor. ALL WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.