Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
August 23, 2007
•
rr
RE: FIRE ALARM SYSTEM T I GARD
Project Information
Building Permit: BUP2007 -00416 Construction Type: 3B
Tenant Name: Westgate Baptist Occupancy Type: E
Address: 10730 SW 130th Hazard: Light
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
2007 edition the Oregon Fire Code 2007 edition and NFPA 72. The submitted plans are
approved subject to the following.
General requirements
A key box for building access may be required. Please contact the local Fire Marshal's Office
for an order form and instructions regarding installation and placement. (OFC 506)
A separate low- voltage electrical permit is required for installation and inspection of alarm
wiring.
A completed inspection and testing form is required at the time of final inspection containing
the information as outlined in NFPA section 10.6.2.3.
TESTING — NFPA 72 Chapter 10, OFC 901.2.1, 901.5, 903.5
1. Upon completion of the installation, a satisfactory test of the entire system shall be made in
the presence of the building inspector. All functions of the system or alteration shall be tested.
2. A record of completion in accordance with NFPD 72 verifying that the system has been
installed in accordance with the approved plans and specifications shall be provided.
3. The permittee shall provide written certification to the Fire Chief that the system has been
installed in accordance with the approved plans and specifications. A copy of the completed
form shall be maintained on the premises and made available to the Fire Chief.
VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4, OSSC chapter 9 & 11
4. When required; Visual alarms shall be located not less than 80 inches and not more than
96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted
within the dimensions stated above and at least 6 inches below the ceiling. No place in a
room shall be more than 50 feet from a visual signal.
MANUAL ALARM - 1109.2.3.5, 1109.2.3.6 OSSC
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
5. Manual Fire Alarm activation devices when installed shall be mounted in the following
reach ranges:
• Forward Reach - 15 inches to 48 inches above the floor.
• Side Reach — 9 inches to 54 inches above the floor.
ALARM SIGNALS — OFC 903.4
6. Alarm, supervisory and trouble signals shall be distinctly different and shall be
automatically transmitted to an approved central station, remote supervising station or
proprietary supervising station as defined in NFPA 72 or, when approved by the fire code
official, shall sound an audible signal at a constantly attended location.
7. Duct smoke detectors shall be connected to the building's fire alarm control panel when a
fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and
audible supervisory signal at a constantly attended location. Duct smoke detectors shall not
be used as a substitute for required open -area detection.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road fronting
the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
espectfully
074
• an Nelson,
Senior Plans Examiner
Advanced Security & Fire RECEi�/E'D
2218 NE Sunrise Lane, Hillsboro OR 97124
(503) 519 -4550 Fax (503) 640 -8311 CI 0 .9 2007
OF T/GARD
July 14, 2007 BoLDING D IVISION
Fire Alarm Operational Matrix
General Overview
The fire alarm system will have battery back up to sustain it in the case of an AC power
failure. Alarm system will have dual phone lines, a primary and secondary, if the primary
fails the secondary will transmit signals to central station. All functions of the fire alarm
system are supervised, (AC power, low battery, phone line integrity, and all alarm
circuits. ) Fire alarm troubles and alarms are both transmitted to the central station and
annunciated locally at the keypad and horn / strobes.
Specific Operation
• Troubles are annunciated at keypad in English text, at the same time they are
transmitted to the central station. Operator at central station will call a
predetermined response list to notify of trouble. Advanced Security & Fire will be
notified of system troubles at the same time.
• Alarms will be transmitted to the central station as well as annunciated locally.
Central station will notify 911 of fire alarm, and then call premises to try and
verify alarm. Response list will be called to notify users of alarm.
• Alarms can be silenced at the keypad by pressing fire silence button.
• Fire system will be in trouble until fire alarm system is reset by pressing the fire
reset button.
• Common area smoke detectors, HVAC duct smoke detectors, and sprinkler water
flow monitor for smoke and trigger a fire alarm.
• Upon trigger of fire alarm by any smoke detector, sprinkler water flow, or manual
fire pull station alarm will be annunciated locally via horn / strobe devices, central
station will be signaled, HVAC units and fire smoke dampers will be shut down
by the fire alarm panel.
Company Information
Advanced Security & Fire is located in Hillsboro, Oregon and is owned and operated by
David Moravik. I have been in the alarm industry since 1981 and licensed as a
journeyman low voltage electrician since 1984, ( license # 611LEA ). My state of Oregon
electrical license is ( CLE -8 ). Advanced Security & Fire is registered with the state of
Oregon contractor's board (contractor's board # 166176). We are a member of the NFPA,
and the local fire and burglary alarm association.
Central Station Information
Advanced Security & Fire monitors its alarm systems through Central Station Monitoring
in Estacada, Oregon. They are certified to monitor all alarm system types. Phone # is (
503- 630 -2896 ).
Sincerely,
Advanced Security & Fire
- Global Project Values:
SILENT Project Name: I Westgate Baptist Church Ph #3 I Standby Hours: I 60 I
KNIGHT Project ID:I I Alarm Mins: I 5 I
Prepared By:IAdvanced Securtiy & Fire I Derating Factor:I 1.2 I
SK - 5208 Ca;cuatUons Date:I5 /24/2007 I Voltage Drop Warning
Threshold % :I 10
Panel ID: (SK -5208 I Model: SK -5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps
Location: ISecurity Closet I Volts: 24 VDC Max Panel Current: 6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts (di %Drop
Circuit Name Qty /oDrop
Standb ry Alarm & Type 1000 Ft. One -Way Ohms EOL
SK - 5208 SK -5208 Main Control 1 0.140 0.160
NAC - CKT SK -5208 Prgm'd NAC's 4 0.000 0.160
ALM - RLY SK -5208 Pgm Alm Rly 0.000 0.000
SK - 5217 SK -5217 Zone Expdr 1 0.060 0.260
SK - 5235 SK -5235 LCD Remote 1 0.035 0.050
SK - 5280 SK - 5280 Display Mod 0.000 0.000
SK - 5220 SK - 5220 Dir Con Mod 0.000 0.000
SK - 7181 SK -7181 Zn Cnvtr 0.000 0.000
5824 Serial /Parallel Cnvtr 0.000 0.000
IDC - Initiating Device Ckt 1 0.001 0.095
IDC - 2 Initiating Device Ckt 2 0.001 0.095
IDC - Initiating Device Ckt 3 0.000 0.095
IDC Initiating Device Ckt 4 0.000 0.000
IDC - Initiating Device Ckt 5 0.000 0.000
IDC - Initiating Device Ckt 6 0.000 0.000
IDC - Initiating Device Ckt 7 0.000 0.000
IDC - Initiating Device Ckt 8 0.000 0.000
IDC - Initiating Device Ckt 9 0.000 0.000
IDC - Initiating Device Ckt 10 0.000 0.000
IDC - Initiating Device Ckt 11 0.000 0.000
IDC - Initiating Device Ckt 12 l 0.000 0.000
IDC - Initiating Device Ckt 13 0.000 0.000
IDC - Initiating Device Ckt 14 0.000 0.000
IDC - Initiating Device Ckt 15 0.000 0.000
IDC - Initiating Device Ckt 16 0.000 0.000
IDC - Initiating Device Ckt 17 0.000 0.000
IDC - Initiating Device Ckt 18 0.000 0.000
IDC - Initiating Device Ckt 19 0.000 0.000
IDC - Initiating Device Ckt 20 0.000 0.000
IDC -21 Inactive, Add SK -5217 0.000 0.000
IDC -22 Inactive, Add SK -5217 0.000 0.000
IDC -23 Inactive, Add SK -5217 0.000 0.000
IDC -24 Inactive, Add SK -5217 0.000 0.000
IDC -25 Inactive, Add SK - 5217 0.000 0.000
IDC -26 Inactive, Add SK -5217 0.000 0.000
IDC -27 Inactive, Add SK -5217 0.000 0.000
IDC -28 Inactive, Add SK -5217 0.000 0.000
IDC -29 Inactive, Add SK -5217 0.000 0.000
IDC -30 Inactive, Add SK -5217 0.000 0.000
NAC -1 1st Floor S Side 0.000 0.750 #16 Solid 4.02 100 0.80 19.80 2.96%
NAC -2 1st Floor S Side 0.000 0.875 #16 Solid 4.02 179 1.44 19.14 6.17%
NAC -3 1st Floor N Side 0.000 0.750 #16 Solid 4.02 260 2.09 18.83 7.69%
NAC-4 1st Floor N Side 0.000 0.750 #16 Solid 4.02 290 2.33 18.65 8.57%
Aux Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 _ 20.40 0.00%
Total Standby Current (Amps) 0.237 4.040 Total Alarm Current (Amps)
Standby Time In Hours 60 0.083 Alarm Time In Minutes / 60 (5 Mins)
• Total Standby AH Required 14.196 0.337 Total Alarm AH Required
Total Combined AH Required 14.53 Command Shortcuts
Multiply By The Derating Factor 1.20 - -
Minimum Battery AmpHours Required 17.44 me Configure Circuits Print Page
Circuit Configuration
Project Information
Project Name: Westgate Baptist Church Ph#3 Project ID: 0
Prepared By: Advanced Securtiy & Fire Date: 5/24/2007
Ckt. Number: IDC -1 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 1
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
15 System Sensor 2W -B 0.000 0.100 0.001 1.500
#N /A 0.000 0.000 0.000 0.000
#N /A 0.000 0.000 0.000 0.000
#NIA 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.001 0.095
Ckt. Number: IDC -2 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 2
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
10 System Sensor 2W -B 0.000 0.100 0.001 1.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.001 0.095
Ckt. Number: IDC -3 Panel ID: SK -5208
Ckt. Name: Initiating Device Ckt 3
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
7 System Sensor 2W -B 0.000 0.100 0.000 0.700
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.095
} ... FIRE
r "1 Wh22IOGJC i.
FIRE
,���,cs.. Fire &
r`':"...;•41 Life
' Safety
■ Systems
NAC Tool Design Report I
Design Name: Design 1 Page 1 of 2
File Name
5/24/2007 See disclaimer below *
Design Thresholds: Voltage: 15 % of Panel / Booster Voltage
Current: 90 % of Circuit Size
Power: 85% of Amplifier Wattage
PANEL: Panel 2 (PWR Booster - Silent Knight 5495)
Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier
Voltage (feet) Class lym Size (Watts)
Panel 2 (PWR 24VDC Santuary - Project 280.00 16 Class B AudibleNisual 1.50 A
Booster - Silent Knight Phase #3
5495)
Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options
10Ft (f Current Voltage
NS- 24MCW -FR 109404 110cd 88 - 97 60.00 0.248 A 0.802 V 19.598 V Std B,D,E,F,G,J,N
NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.253 A 0.325 V 19.272 V Std B,D,E,F,G,J,N
NS- 24MCW -FR 109404 110cd 88 - 97 130.00 0.269 A 1.075 V 18.197 V Std B,D,E,F,G,J,N
NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.272 A 0.166 V 18.031 V Std B,D,E,F,G,J,N
NS- 24MCW -FR 109404 110cd 88 - 97 30.00 0.273 A 0.083 V 17.948 V Std B,D,E,F,G,J,N
Circuit Totals: 280.00 1.316 A 2.452 V
Voltage Drop: 10.22 %
Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier
Voltage (feet) Class Type Size (Watts)
Panel 2 (PWR 24VDC Circuit B 4/ 0.00 16 Class B AudibleNisual 1.50 A
Booster - Silent Knight � S .
5495)
Model Number Order Code Candela dBA Distance Actual Voltage Drop Applied Settings Mounting Options
10Ft (feet) Current Voltage
0.00 0.000 A 0.000 V 0.000 V
Circuit Totals: 0.00 0.000 A 0.000 V
Voltage Drop: 0.00 %
Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier
Voltage (feet) Class Type Size (Watts)
•
wheelock
Fire &
Life
Safety
Systems
NAC Tool Design Report I
•
Design Name: Design 1 Page 2 of 2
File Name
5/24/2007 See disclaimer below *
Design Thresholds: Voltage: 15 % of Panel / Booster Voltage
Current: 90 % of Circuit Size
Power: 85% of Amplifier Wattage
Panel 2 (PWR 24VDC Circuit C 4' 0.00 16 Class B AudibleNisual 1.50A
Booster - Silent Knight .S
5495)
Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options
IOFt (feet) Current Voltage
0.00 0.000 A 0.000 V 0.000 V
Circuit Totals: 0.00 0.000 A 0.000 V
Voltage Drop: 0.00 %
Panel / Booster Panel Circuit Name Length AWG Wiring Circuit Circuit Amplifier
Voltage (feet) Class Type Size (Watts)
Panel 2 (PWR 24VDC Circuit D / 0.00 16 Class B AudibleNisual 1.50 A
Booster - Silent Knight
5495)
Model Number Order Code Candela dBA @ Distance Actual Voltage Drop Applied Settings Mounting Options
IOFt (f Current Voltage
0.00 0.000 A 0.000 V 0.000 V
Circuit Totals: 0.00 0.000 A 0.000 V
Voltage Drop: 0.00 %
. * This document provides information on an as -is basis to assist users and their technical advisors in selecting elements for notification
circuits and/or facility communication systems. Wheelock Inc. does not hold itself out as providing design or engineering services.
Users of this program are solely responsible for their own selection and use of products based on values supplied by users, and
. Wheelock Inc. shall have no liability therefor. ALL WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.
� F B� IRE ' - ''�yy wheelock—
Fire &
Life
Safety
Systems
NAC Tool Battery Calculations I
Date 5/24/200
Page 1 of 1
See disclaimer below*
Total Current Draw For Design 1 1.31
Minimum aH Required 0.109
Order Code Model Number Qty Current
(Amps)
109404 NS- 24MCW -FR 5 1.316
* This document provides information on an as -is basis to assist users and their technical advisors in selecting elements for
notification circuits and/or facility communication systems. Wheelock Inc. does not hold itself out as providing design or
engineering services. Users of this program are solely responsible for their own selection and use of products based on values
• supplied by users, and Wheelock Inc. shall have no liability therefor. ALL WARRANTIES INCLUDING THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.