Loading...
Correspondence December 20, 2005 CN. :OF. TIG t: D A dvance Security & Fire s . ®REG O David Moravik r. 2218 NE Sunrise Ln Hi . llsboro' OR 97124 RE: FIRE ALARM SYSTEM - 2" PHASE Project Information :' Building Permit: - BUP2005- 00646 Construction Type: 5 -A Tenant Name: Westgate Baptist Church Occupancy ,Type: - E • Address: ; . '10730 SW -.130 Ave `OccupantLoad UK Area UK sq ft Stones : '2 Sprinklers: Yes The on, Ore l on Fire Code 2004 edition and NFPA 7, The bin tted are a sub t edition; Oregon plans PP I the following.�� General , , .. • requirements -' A key box for buildin access ma ber'ired Please contact the local Fire Marshal's Office for' an instructions re ardin install ation and lac 1. Upon completion of the insttallafion, asatisfactory test of the entire system shall be made in the presence of the building'official and fire code official. All functions of the ',System or alteration shall be tested_. 901 5:OSSC and NFPA "7 2 apter h 10 . sting -final a roy 2. Before re ue pp al of the installation, the installing contractor shall furnish a official that the Written statement to�the fire code lane and has been tested in accordance dance hag been • . y installed in accordance with'approv p th` manufacturers specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations sh be attached to the written statement. 901.2.1 OFC 3. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. NFPA 72 4.4.1.4, 907.5 OFC 4. The emergency voice /alarm communication system shall be designed and installed in accordance with NFPA 72. 907.2.12.2.3 OFC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5 Manual Fire Alarm activation devices when installed shall be 'mounted in the following reach ranges: « Forwar t,„ ,• to • , the floor. 1109.2.3.5 > S S_ C O • d Reach -15 inch to48 inches above th �; • to 54 inches above' the floor. ° � Side Reach —�9 inches t � or. 1109.2.3.6 OSSC • Y , r 6. All ower su`' lies shall b • p pp � conformity with NFPA 70. NFPA ... e installed m co . 7. All primary and secondary power supplies shall be monitored for the presence of voltagetat -the • Y either Supply shall result in a troubl " point accordance with 14.4.3.5 The trouble s gnal also shall be visuall and audibly indicated at the g :protected premises. NFPA 72, 4.4:73 Y Y 8. im alarm g pp ces shall be provided in buildings and facilities in each of the Visual alar m s i gl al signal a les shall be integrated into the building or facility alarm system. At a signal appliances shall minimum, � PP P •. g � following areas° 1109.14 OSSC „� * * restroom * s and any other general usage areas meeting roof classrooms * hallways, lobbies, and any other area for common use 9. Visible notification appliances shall be located not morethan 15 feet from the end of the corridor with a separation not greater than 100 feet between..appliances. NFPA 72, 7:5:4.2.5 10. Visual alarms shall be located not less than 801inches and not more than 96 inches above floor level. When a low ceiling exists, the sual alarm shall be mounted within the i dimensions stated above and at least 6aches below the ceiling. 11 OSSC, NFPA 72, 7.5.4 Approved Plans: 1 set of approvedplans, bearing the City of Tigard approval stamp, shall be . ', Building . ' . maintained on the �obsite. The plans shall be available to the throughout all phases of const Division inspectors ruction. 106.3.1 OSSC , Premises Identification . Approved - numbers or addresses shall be provided for all new buildings in such a position as to 12e plainly visible and legible from the street or road fronting the property. • additional When submitting-revised drawings o r ditio information, please e attach a copy of the enclosed J, , City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking processing the documents. Respecffiilly • Val H nzel, Senior Plans Examiner