Correspondence December 20, 2005
CN. :OF. TIG t: D
A dvance Security & Fire s
. ®REG O
David Moravik
r. 2218 NE Sunrise Ln
Hi
.
llsboro' OR 97124 RE: FIRE ALARM SYSTEM - 2" PHASE
Project Information :'
Building Permit: - BUP2005- 00646 Construction Type: 5 -A
Tenant Name: Westgate Baptist Church Occupancy ,Type: - E •
Address: ; . '10730 SW -.130 Ave `OccupantLoad UK
Area UK sq ft Stones : '2
Sprinklers: Yes
The on, Ore l on Fire Code 2004 edition and NFPA 7, The bin tted are a sub t
edition; Oregon plans PP I
the following.��
General , , .. •
requirements -'
A key box for buildin access ma ber'ired Please contact the local Fire Marshal's Office for' an
instructions re ardin install
ation and lac
1. Upon completion of the insttallafion, asatisfactory test of the entire system shall be made in the
presence of the building'official and fire code official. All functions of the ',System or alteration
shall be tested_. 901 5:OSSC and NFPA "7
2
apter
h 10 .
sting -final a roy
2. Before re ue pp al of the installation, the installing contractor shall furnish a
official that the
Written statement to�the fire code
lane and has been tested in accordance dance hag been •
. y
installed in accordance with'approv p th`
manufacturers specifications and the appropriate installation standard. Any deviations
from the design standards shall be noted and copies of the approvals for such deviations
sh be attached to the written statement. 901.2.1 OFC
3. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and
connections shall be mechanically protected. The circuit disconnecting means shall be accessible
only to authorized personnel and shall be clearly and permanently marked FIRE ALARM
CIRCUIT CONTROL. NFPA 72 4.4.1.4, 907.5 OFC
4. The emergency voice /alarm communication system shall be designed and installed in accordance
with NFPA 72. 907.2.12.2.3 OFC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
5 Manual Fire Alarm activation devices when installed shall be 'mounted in the following reach
ranges: «
Forwar t,„ ,• to
• , the floor. 1109.2.3.5 > S S_ C
O
• d Reach -15 inch to48 inches above th �; •
to 54 inches above' the floor. ° � Side Reach —�9 inches t � or. 1109.2.3.6 OSSC
• Y , r
6. All ower su`' lies shall b •
p pp � conformity with NFPA 70. NFPA
... e installed m co .
7. All primary and secondary power supplies shall be monitored for the presence of voltagetat -the •
Y
either Supply shall result in a troubl
" point
accordance with 14.4.3.5 The trouble s gnal also shall be visuall and audibly indicated at the
g
:protected premises. NFPA 72, 4.4:73 Y Y
8. im alarm g pp ces shall be provided in buildings and facilities in each of the
Visual alar m s i gl al signal a les shall be integrated into the building or facility alarm system. At a
signal appliances shall
minimum, � PP P •. g � following areas° 1109.14 OSSC „�
* *
restroom *
s and any other general usage areas meeting roof classrooms
* hallways, lobbies, and any other area for common use
9. Visible notification appliances shall be located not morethan 15 feet from the end of the corridor
with a separation not greater than 100 feet between..appliances. NFPA 72, 7:5:4.2.5
10. Visual alarms shall be located not less than 801inches and not more than 96 inches above
floor level. When a low ceiling exists, the sual alarm shall be mounted within the
i
dimensions stated above and at least 6aches below the ceiling. 11 OSSC, NFPA 72, 7.5.4
Approved Plans: 1 set of approvedplans, bearing the City of Tigard approval stamp, shall be .
', Building . ' .
maintained on the �obsite. The plans shall be available to the
throughout all phases of const Division inspectors ruction. 106.3.1 OSSC ,
Premises Identification . Approved - numbers or addresses shall be provided for all new buildings in
such a position as to 12e plainly visible and legible from the street or road fronting the property.
• additional
When submitting-revised drawings o r ditio information, please e attach a copy of the enclosed J, ,
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking processing the documents.
Respecffiilly •
Val H nzel, Senior Plans Examiner