ommercial Package Gas /Electric Units
Meets Ashrae 90.1 Standards
FEATURES:
- • Exclusive integrated gas control board with diagnostics
Indu ;,d-draft fan for gas combustion
aZ: • ,, bider, dimpled heat exchangers
■ Pre - painted galvanized steel cabinet for long life and quality
appearance
o o 0,,,.... • Commercial strength base rails with built -in rigging capability
• Convertible design for vertical or horizontal supply /return
• Non - corrosive, sloped condensate drain pan, meets ASHRAE 62
i a - °°
• Two-inch return -air filters
• High and low (loss -of- charge) pressure switches and freezestat
PGE090, 120, 150 • Direct -spark ignition systems
• Refrigerant filter drier
• Part load operation using two stages of cooling
• Quiet and efficient operation is provided by belt driven evaporator fans
• Thru- the -bottom utility connection capability allow power, control
wiring, and gas to be routed through unit base pan, minimizing roof
penetrations.
Warranty: 10 year Heat Exchanger, 5 year compressor, 1 year parts
7).-.14,... OF TIGARD
Approved f T
t tTnditlonally Approved
F 3r only the wgrk. described in: f 1
`� j P59MIT NO. — 7
See �-
y ee letter to: Follow
'rANnAg) 4 f I
,Q ,,,,00 To QT,,,,,, Attach
Job Address: 0.730 SI JSr�I i i
s ..„0 uq co, o` � S � , � ✓ - ----' A � /N. ,
Date: 0 1-2 -O 7
W j P '• ,
n C 1 )1. US i RAMst f C Arm-Crib t
® L � � f' _ E 'DWPMEN I • • .M 5 piCTd o NND vcRM.xT'
9r avr sci 3 '.
4
■
ND�P0 P / vC 0 I
RESIDENTIAL AND COMMERCIAL SYSTEMS • SPLIT SYSTEMS • PACKAGED AIR CONDITIONERS • COMBINATION GAS / ELECTRIC
UNITS • HEAT PUMPS • AIR HANDLERS • MANUFACTURED HOME AIR CONDITIONERS • GAS, OIL AND ELECTRIC FURNACES
International Comfort Products
650 Heil- Quaker Avenue, Lewisburg, TN 37091
509 71 2101 05 .
OFFICE 6/23/03
Table of Contents
Page
Features /Benefits 1
Model Number Nomenclature 2
Unit Specifications 3 -4
Dimensions 5
Performance Data 6 -11
Typical Installation 12
Accessories 13 -16
Controls 17
Guide Specs 18
MODEL NUMBER IDENTIFICATION GUIDE
MODEL NUMBER P G E 090 H 224 A
PRODUCT FAMILY
Package Units Sales Code
TYPE
GAS HEATING OPTIONS (BTUH)
224 = 224,000 250 = 250,000
H= Heat Pump G = Gas/Electric
A = Air Conditioner
VOLTAGE I PHASE / HERTZ
H = 208/230 -3 -60
DESIGN SERIES L = 460 -3 -60 S = 575 -3 -60
' COOLING CAPACITY (NOMINAL BTUH)
090 = 7 -1/2 120 = 10 Ton
150 = 12 -1/2 Ton
•
C ®L
.
2
.
UNIT SPECIFICATIONS (Legend on Next Page) MODELS
COOLING PGE090H PGE090L L PGE090S PGE120H PGE120 " PGE120S PGE150H PGE150L PGE150S
ARI Rated Capacity Btuh (Net) 87,000 0t0 136,000
Nominal Tons
t
Standard CFM 2800 •ttt tt
EER t
IPLV t
10.4 10.' 10.2
Sound Rating (Bels)
Unit Weight (lbs. / kg) 870 t t
ELECTRICAL - • I PGE090H I PGEO9OL I PGE090S I PGE120H I PGE120L I PGE120S I PGE150H I PGE150L I PGE15OS •
60Hertz 208/230 460 575 208/230 460 575 208/230 460
Voltage Range Min/Max 187 /254 414 /508 518 /632 187 /254 414
t: t: 518 /632
01 t t
COMPRESSOR I RECIPROCATING ` I _ SCROLL I SCROLL -"
.t ea
RLA t t t •t 15.81130 .•t t .t •t tt t
REFRIGERANT TYPE , R -22
Expansion Device
Fixed Orifice Device
CONDENSER FAN Propeller Type
Nominal CFM 6400
ttt 7000
t• tt
Watts Input (Total) 600 .tt 650
FLA 1.4 0.7 0.7 1.4 t t t t
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced fins
.,
t
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins •
Rows...Fins/Inch 3...15 3...15
• - Total Face (sq: ft.) •--- - - - - -- - -- ---- -8:9 -- — — 10.0 11.1
EVAPORATOR FAN Centrifugal Type
Quantity...Size(in.) 1...15x15 1...15x15 1...15x15
Type Drive Belt Belt
Belt
Nominal CFM 3000 4000 5000
Max. Continuous Bhp 2.4 2.4 5.25
FLA- 208- 230/460/575V 5.8/2.6/2.6 5.8/2.6/2.6 15.0/7.4/7.4
Motor Frame Size 56 56 56
Fan RPM Range 590 -840 685 -935 900 -1260
Motor Bearing Ball Ball Ball
Maximum Allowable RPM 2100 2100 2100
Motor Pulley Pitch / Diameter Min /Max. (in.) 2.4 / 3.4 2.8 / 3.8 _ 2.8 / 3.8
Motor Shaft Diameter (in.) 5/8 5/8 7/8
Fan Pulley Pitch Diam (in) 7.0 7.0 • 8.0
Belt, Quantitiy...Type... Length (in.) 1...A...49 1...A...49 1...A...52
Pulley Center Line Distance (in) 16.75 -19.25 15.85 -17.50 15.85 -17.50
Speed Change per Full Turn of Movable Pulley 50 50 60
Flange (RPM)
Pulley Max. full Turns From Closed Postion 5 5 6
Factory Setting 5 5 5
Factory Speed Setting RPM 590 685 960
Fan Shaft Diam. at Pulley 1 1 1
3
•
UNIT SPECIFICATIONS (CONT) MODELS
FURNACE SECTION i PGE090 - I PGE120 PGE150
Rollout Switch Cutout Temp (F) 195 195 195
Burner Orifice Diameter (in. .drill size)
Natural Gas 120...31 129...30 129...30
Liquid Propane 096...41 102...38 102...38
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575v Stage 1 14 14 14
208/230 v and 575v Stage 2 20 20 20
460 v Stage 1 14 14 14
460 v Stage 2 20 20 20
Gas Input (Btuh)
Stage 2 / Stage 1 224,000 / 180,000 250,000 / 200,000 250,000 / 200,000
-- Output.Capacity.(Btuh).- ____- -__ -__ __.__ - - -._— — 1-79,200 - - -- - - -. - 200,-000 -- -• -- — 200;000 - - - - -- -
Efficiency (Steady State) ( %) AFUE 80 80 80
Temperature Rise Range 45 -75 40 -70 40 -70
Manifold Pressure (in. wg)
Natural Gas 3.5 3.5 3.5
Liquid Propane 3.5 3.5 3.5
Gas Valve Quantity 1 1 1
Gas Valve Pressure Range Psig . 0.180 -0.487 0.180 -0.487 0.180 -0.487
in. wg 5.0 -13.5 5.0 -13.5 5.0 -13.5
Field Gas Connection Size (in.) 3/4 3/4 3/4
HIGH PRESSURE SWITCH (psig • .
Standard Compressor 450 +/- 50 450 +/- 50 450 +/- 50
Internal Relief (Differential) Cutout 428 428 428
Reset (Auto.) 320 320 320
LOSS - OF - CHARGE SWITCH (psig) (LOW - PRESS.) •
Cutout 7 +l- 3 7 +/- 3
7 +/- 3
Reset (Auto.) 22 +/- 7 22 +l- 7 22 +/- 7
FREEZE PROTECTION THERM OSTAT (F) .
Opens 30 +/- 5 30 +l- 5
30 +/- 5
Closes 45 +/- 5 45 +1- 5 45 +/- 5 •
- RETURN - AIR FILTERS (THROWAWAY) , _
Quantity...Size(in.) 4...16x20x2 • 4...20x20x2 4...20x20x2
LEGENDS AND NOTES
Bhp = Brake Horsepower NOTES: 1. Rated in accordance with ARI Standards 210/240, latest
revision (for sizes 090 & 120) or 360, latest revision (for size
Legend 150).
Bets - Sound Levels 2. ARI ratings are net values, reflecting the effects of circulating
EER - Energy Efficiency Ratio fan heat.
IPLV - Integrated Part Load Values 3. Ratings are based on:
MCA - Minimum Circuit Amps Cooling Standard: 80F db, 67F wb indoor entering air
MOCP - Maximum Over- current Protection temperture and 95F db air entering outdoor unit.
FLA - Full Load Amps IPLV Standard: 80F db, 67F wb indoor entering air temperture
LRA - Locked Rotor Amps and 80F db entering air temperature.
Fuse or HACR circuit breaker EXAMPLE: Supply voltage is 460 -3 -60.
RLA - Rated Load Amps A B C
AB = 452 v Average Voltage = 452 + 464 + 455
Fl BC = 464 v = 3
AC = 455 v 1371
3
NOTES: MOTOR = 457
1. In compliance with NEC requirements for multimotor and combina- Determine maximum deviation from average voltage.
tion load equipment (refer to NEC Articles 430 and 440), the over- (AB) 457 - 452 = 5 V
current protective device for the unit shall be fuse or HACR breaker . (BC) 464 - 457 = 7 V ■
Canadian units may be fuse or circuit breaker . (AB) 457 - 455 = 2 V
2. Unbalanced 3 -Phase Supply Voltage Maximum deviation is 7 v.
Never operate a motor where a phase imbalance in supply voltage is
greater than 2 %. Use the following formula to determine the percent Determine percent voltage imbalance.
voltage imbalance.
% Voltage Imbalance 100 x 7 = 1.53%
Voltage Imbalance 457
= 100 x max voltage deviation from average voltage This amount of phase imbalance is satisfactory as it is below the
average voltage
maximum allowable 2 %.
IMPORTANT: If the supply voltage phase imbalance is more than
2 %, contact your local electric utility company immediately .