Correspondence 'E C2.DiC - -cj
7S Sv■ 0ULL / vv i f v Pp
Gary Noble
From: Travis Sheffield [travis @bentonelectric.com]
Sent: Friday, May 13, 2011 10:27 AM
To: Gary Noble
Subject: Re: Electrical correction written on Tigard 10 MG Reservoir
We will lock off the main service as requested. We are working with the engineer to revise the drawings.
Travis Sheffield
541- 936 -0980
On May 13, 2011, at 8:23 AM, Gary Noble <Garyn a tigard- or.gov> wrote:
Travis,
Re: Electrical Permit # ELC2010 -00325
On May 11, 2011 you delivered two sets of 0 and M manuals with Electrical Submittal
information pertaining to the switchgear. I assume you drop these documents off to satisfy
the correction notice I left on the job on May 10, 2011 which states:
This inspection covers work performed outside of approved plans. Plans must be submitted
for plan review by the City of Tigard to include work performed with -in 3 working days of
this notice. Additional inspections will be performed upon receipt of approved plans by the
contractor. This inspection is for utility metering only.
A product submittal does not comply with OAR918- 311 -0040 and as such will not be
accepted by the City of Tigard for the plan review on this project.
The original planes approved by City of Tigard were submitted by Benton Electric and
signed by Gregg H. Scholz, Registered Engineer. The revised set of plans must also be
signed by the engineer of record, Gregg H. Scholz.
Please submit two sets of plans that conform to OAR918- 311 -0040 that have been signed by
the engineer of record.
1
My application of the "Green Label" on the electric meter was performed to foster the
progress of the project, but it does not indicate my approval of the Main Switchboard. I will
not allow the electrical energizing of electrical equipment that does not conform to the
requirements' of OESC and the National Electrical Code. You must lock -off the main
service disconnect until I have performed the aforementioned plan review and approved the
installation for conformity with OESC and the National Electrical Code.
<image001.jpg>
DISCLAIMER: k= -mails sent or received by City of Tigard employees are subject to public record
laws. If requested. e -mail may be disclosed to another party unless exempt from disclosure under
Oregon Public Records Law E -mails are retained by the City of Tigard in compliance with the
Oregon Administrative Rules "City General Records Retention Schedule."
2