Report BUP2° -00070 I I 9'45 Svc/ 70 -rr +4 ✓ NEUDORFER ENGINEERS INC. TEST ADJUST & BALANCE BALANCE REPORT TVF&R Corn. And Ops Center 11945 SW 70th Ave. Tigard, OR 97223 2010 -430 Project Completion Date: 10/01/10 Revision Date: Revision Number: de r En fine_ l sn.ineers **44 ap N X38 110 g p WILLIAM C. NEUDORFER MIKE VAWTER, P.E. CERTIFICATION CERTIFICATION 2465 3414 Exp. 3131111 Exp. 3(31(11 `t°r d/or,ic no, drortic 9y 4`e 5516 1" Ave S 1500 NE Sandy Boulevard, Suite #1 Seattle, WA 98108 Portland, OR 97232 Phone (206) 621 -1810 Phone (503) 235 -8924 Fax (206) 343 -9820 Fax (503) 235 -8925 10/6 1 of 53 leudorter Engineers, Inc. 14,04- ta Consuk ng Engine rs Seattle Porlian.i J *two Neer arter r gin corn TVF &R Corn. And Ops Center 11945 SW 70th Ave. Table of Contents Cover 1 Table of Contents 2 Title 3 Certification 4 terms 5 Calibrations 6 Summary 7 RTU -01 9 RTU -02 31 CRU -01 46 CRU -02 48 EF -02 49 EF -03 50 Prints 51 10/6 2 of 53 ill �� Neudorter Engineers. Inc. , Consulting Envneors Saattlo Ponl8rld wwrr.MeudprtarErtgiti ..ixar#t Report Title CERTIFIED TEST: BALANCE REPORT Project: TVF &R Corn. And Ops Center 11945 SW 70th Ave. Tigard, OR 97223 NEI Job #: 2010 -430 Mechanical Engineer: R & W Architect: Peck Smiley Ettlin Title HVAC Contractor: American Heating TAB Firm: Neudorfer Engineers Inc Test Engineer: KYLE DRAEGER 031 En•ine@,^ y en /We �e i ' Ri. e � ��'� N E 311,13-.° 8 o Z „ , WILLIAM C. NEUDCRFEFi MIKE VAWTER, P.E. CERTIFICATION CERTIFICATION 2465 3414 exp. 141111 Exp. 3/31/11 SA Y drornc S `� o' drorlic S`1 5516 1' Ave S 1500 NE Sandy Boulevard, Suite #1 Seattle, WA 98108 Portland, OR 97232 Phone (206) 621 -1810 Phone (503) 235 -8924 Fax (206) 343 -9820 Fax (503) 235 -8925 10/6 3 of 53 Neudorfer Engineers. Inc. h C*nsulttng Engan ers Seattle Portland d www. NcauoarterEngIRi., =...corn CERTIFICATION TVF &R Com. And Ops Center The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test - Adjust - Balance Report Project Summary. Significant / Noteworthy Remarks are noted on the General Remarks and General Field Notes pages. Other remarks are noted on individual test sheets. Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent. Warranty is limited to one year from date of this report. Within that time, any discrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required. Submitted and Certified by: NEBB TAB Firm: Neudorfer Engineers Inc Certification No: 2465 / 3414 Expiration Date: March 31, 2011 Certification Date: March 31, 2009 (Date completed) Signed and Sealed by: NEBB Supervisor: William C. Neudorfer NEBB Supervisor: Mike Vawter P.E. de r En frpe% 0speinee, N.P rtn - ■ o r ""ti N . o 2 9 WI.LIA A C.NEUDORFER MIKE VAWTER, P.E. CERTIFICATION CERTIFICATION 2465 3414 exp. 3/310 I Exp. 3/31 /1 1 10/6 �� °' drontc S s� � ' a drorilc S` 4 of 53 Neudorfer Engineers. Inc. ftif Consutr ng E,ngulf:Ws Seattle Portland Terms and Abbreviations Project: TVF &R Corn. And Ops Center AC or ACU Air Conditioner or Air Conditioning Unit TDH Pressure Difference across the entering AH or AHU Air Handler or Air Handling Unit and leaving side of a pump. AVG Average HEPA High Efficiency Particulate Arrestance BHP Brake Horsepower HP Horsepower CAV Constant Air Volume HVAC Heating Ventilation and Air Conditioning CBV Calbirated Balancing Valve HWS Heating Water Supply (Circuit Setter) HWR Heating Water Return CC Cooling Coil HX Heat Exchanger CD Ceiling Diffuser HZ Hertz, cycle per second in. inches CFM Cubic Feet per Minute in.w.g. inches of water gauge CH Chiller Kfactor Correction factor to the free area need to CHWS Chilled Water Supply calculate CFM. CHWR Chilled Water Return KW Kilowatts LAT Leaving Air Temperature CP Circulating Pump LWG Low Wall Grille CR Ceiling Register LWR Low Wall Register CRAC Computer Room Air Conditioner LWT Leaving Water Temperature CRU Computer Room Unit MAU Make -up Air Hangling Unit CT Cooling Tower MBH 1,000 BTUH CU Condenser Unit N/A Not Applicable CUH Cabinet Unit Heater OSA Outside Air CWS Condenser Water Supply OBD Opposed Blade Damper CWR Condenser Water Return AP Pressure Drop. DAT Discharge Air Temperature PH Phase DB Dyr Bulb PSI Pounds per Square Inch DD Direct Drive RA Return Air DDC Direct Digital Controls: EMS Control RAT Return Air Temperature System for the HVAC RF Return Fan Des. Design RH Relative Humidity Dia. Diameter RHC Reheat Coil Disc h. Discharge RPM Revolutions per Minute EA Exhaust Air RTU Roof Top Unit EAT Entering Air Temperature SA Supply Air Economizer Controls and components that allow an SAT Supply Air Temerature air handler to logically utilize outdoor air S.F. Service Factor for cooling as opposed to the use of SF Supply Fan mechanical cooling. SFD Smoke /Fire Damper EF Exhaust Fan SP Static Pressure EG Exhaust Grille sq.ft. square feet EMCS Energy Management Control System Suct. Suction ERU Energy Recovery Unit SWG Sidewall Grille E.S.P. External Static Pressure SWR Sidewall Register HRC Heat Recovery Coil TAB Test; Adjust; and Balance EWT Entering Water Temperature TSP Total Static Pressure: Difference FCU Fan Coil Unit between the entering and leaving FD Fire Damper static pressure of a fan. FLA Full Load Amperage: Maximum UH Unit Heater amperage a motor can draw. VAV Variable Air Volume; box that Flow Hood Instrument that captures air and contains a motorized damper that converts the reading to CFM. modulates airflow. FPB Fan Powered Box VD Volume Damper FPM Feet per Minute VFD Variable Frequency Drive FR Field Report Velgrid Instrument that reads used to read FT Foot, Feet velocity in feet per minute. FTU Fan Terminal Unit VVT Variable Volume Terminal GPM Gallons per Minute WC Water Column HC Heating Coil W.G. Water Gauge 10/6 WB Wet Bulb 5 of 53 Neudorfer Engineers. Inc, i r „...v.,,,t, Consulting Engineers Seattle Portland wrrrr.NeuttorterEngin ..cum TVF &R Corn. And Ops Center 11945 SW 70th Ave. Instrument Calibrations Instrument Type Air Data Meter with Flowhood Instrument Serial # M08839 Instrument Manufacturer Shortridge Calibration Date 1/19/2011 Instrument Model Number ADM 860C Instrument Type Differential Pressure Water Meter Instrument Serial # W08088 Instrument Manufacturer Shortridge Calibration Date 11/18/2009 Instrument Model Number HDM -250 Instrument Type Psychrometer Instrument Serial # H078215 Instrument Manufacturer Extech Calibration Date 1/28/2010 Instrument Model Number RH390 Instrument Type Tachometer Instrument Serial # 166489 Instrument Manufacturer Hasler Bern Calibration Date 2/10/2010 Instrument Model Number Type B Instrument Type Amp Probe Instrument Serial # 78212531 Instrument Manufacturer Fluke Calibration Date 2/2/2010 Instrument Model Number 36 Clamp Meter Instrument Type Digital Thermometer Instrument Serial # 7190028 Instrument Manufacturer Fluke Calibration Date 1/27/2010 Instrument Model Number 52 Instrument Type Manometer Instrument Serial # 8085434 Instrument Manufacturer Extech Calibration Date 2/2/2010 Instrument Model Number HD755 10/6 6 of 53 leu ar er Engineers. Inc. Consulting Engneers Stratus Portland www. NeuckxferEnpin PROJECT TVF &R Command and Operation Center LOCATION Tigard, OR EXECUTIVE SUMMARY This project has been balanced per plans and specifications using the National Environmental Balancing Bureau (NEBB) standards and procedures. The fans have been checked for fan data, operating amperage, voltage, rotation, RPM, belt tension, alignment, and operating static pressure. All outlets have been proportioned to ± 10% of the percentage of total airflow of the system unless otherwise noted. Balancing diagrams are attached to this report with outlets numbered for locations. RTU - 01 This fan serves 3rd 2nd floor east and all of the 1st floor. Design total flow is 35,000 CFM, our recorded total flow is 27065 CFM. VAV summation at this time is 26770 CFM. Fan is performing at 101% of VAV summation. RTU - 02 This fan serves 3 2 floor west. Design total flow is 12.000 CFM, our recorded total flow is 12065 CFM. VAV summation at this time is 18660 CFM. Fan is performing at 100% of design total. Fan total was achieved by opening VAV's to total 12,000 CFM, and the rest were closed. Static pressure was then dialed in to make sure all boxes were satisfied with one VAV at 100% open. EF - 02 This fan serves all floors central exhaust . Design total flow is 1200 CFM, our recorded total flow is 1180 CFM. Fan is performing at 98% of design flow. EF - 03 This fan serves 2 floor Break room and west toilets. Design total flow is 1225 CFM, our recorded total flow is 990 CFM. Fan is performing at 81% of design flow. Speeding the fan up any further exceeds rated amperage. Outlets were proportioned to draw a negative pressure in the toilets. 10/6 7 of 53 Summary cont' CRU -01 This fan serves the server room. Design total flow is 5500 CFM, our recorded total flow is 5277 CFM. Fan is performing at 96% of design flow. CRU -02 This fan serves the server room. Design total flow is 5500 CFM, our recorded total flow is 5355 CFM. Fan is performing at 97% of design flow. NATIONAL ENVIRONMENTAL BALANCING BUREAU 10/6 8 of 53 N eudo rf er Engineers. Inc, Gonsulbng Engineers Seattle Portland w NaudorierEngin.. •corn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 Tested By: Kyle Draeger AREA: East 2nd& 3rd all of 1st fl. Test Date: October 01, 2010 Unit Data Motor Data Unit Manufacturer Trane RTU -01 / Supply Fan Unit Model Number SFHGC904H3H7CFED9001 Motor Manufacturer A.O. Smith Unit Serial Number C07F07035 Drive Type Belt Drive Unit Discharge Top Horizontal Motor Frame 286T Fan Rotation Clockwise Motor HP 30 HP RTU -01 / Filter Bank Motor RPM 1760 RPM Filter Manufacturer Aerostar Motor Rated Volts 460 Volts Filter Type Pleated Motor Phase 3 Filter Quantity - Size 1 20 Motor Hertz 60 Hz Filter Dimensions - Size 1 24x24x2 Motor FL Amps 36.2 Amps Motor Service Factor 1.15 Starter Data Motor Efficiency 93.6 % Motor Power Factor 82.0 PF RTU -01 I Supply Fan Installed Thermal VFD Sheave Data Test Data RTU -01 I Supply Fan Motor Sheave MFG Browning Total Design Flow 35000 CFM Motor Sheave Model 1B5V124 Total Actual Flow 27065 CFM Motor Sheave Bore B x 1 7/8 in. OA Design Flow 2400 CFM Motor Sheave Type Fixed OA Actual Flow 2545 CFM Fan Sheave MFG Browning RTU -01 / Supply Fan Fan Sheave Model 1B5V154 Fan RPM Design 1445 RPM Fan Sheave Bore B 2 7/16 in. Fan RPM Actual 1419 RPM Number of Belts 1 VFD Setting 49.6 Hz Belt Size 5VX1150 AHU SP Setpoint 2.4 in. Motor to Extend 4 in. Motor Volts T1 -T2 393 Volts Motor to Retract 1 in. Motor Volts T2 -T3 390 Volts Motor Volts T1 -T3 392 Volts Motor Amps TI 22.5 Amps Test pressures Motor Amps T2 22.4 Amps SF Suction SP -1.61 in. wc Motor Amps T3 22.5 Amps SF Discharge SP 2.40 in. wc Actual Total SP 4.01 in. wc Filter DP 0.13 in. wc Coil DP 0.50 in. wc OA Damper Pos 4.0 % RA Damper Pos 96.0 % * Notes IRTU -01 1- Oct -10 Kyle Draeger VAV summation at this time =26770 CFM. 10/6 9 of 53 Neudorfer Engineers, Inc. li i Neudorfer Engineers Inc ,, - - ER Cansultbng Englneers Seattle Portiand www.NeuoerfarEngi T= . ,.o cart Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 /FPB -101 Tested By Kyle Draeger AREA: Media 123 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 1400 CFM VAV Address 65 VAV Fan Actual Flow 1390 CFM Cooling Inlet Size 14" inches Clg Max Des. Primary Flow 2000 CFM Cooling K Factor 1.20 Clg Min Des. Primary Flow 600 CFM Fan: Variable /Constant 40% Clg Max Act. Primary Flow 2025 CFM Clg Min Act. Primary Flow 635 CFM RTU - 01 / FPB - 101 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Control 120 Flowhood A 8" 1.00 - 200 265 215 108 Outlet -02 * Control 120 Flowhood A 8" 1.00 - 200 250 185 93 Outlet -03 Control 120 Flowhood A 8" 1.00 - 200 260 205 103 Outlet -04 Control 120 Flowhood A 8" 1.00 - 200 255 185 93 Outlet -05 Media 123 Flowhood K 5x48 1.00 - 400 480 420 105 Outlet -06 Media 123 Flowhood K 5x48 1.00 - 400 465 405 101 Outlet -07 Media 123 Flowhood K 5x48 1.00 - 400 450 410 103 Totals - - - - - 2,000 2,425 2,025 1101 % - * Notes RTU -01 / FPB -101 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 SYSTEM /UNIT: RTU -01 / FPB -102 Tested By: Kyle Draeger AREA. Media 126 Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 365 CFM VAV Address 66 VAV Fan Actual Flow 340 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 510 CFM Cooling K Factor 0.96 Clg Min Des. Primary Flow 155 CFM Fan: Variable /Constant 1% Clg Max Act. Primary Flow 490 CFM Clg Min Act. Primary Flow 175 CFM RTU - 01 / FPB - 102 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet-01 * Media 126 Flowhood A 8" 1.00 - 170 160 160 94 Outlet -02 Media 126 Flowhood A 8" 1.00 - 170 160 160 94 Outlet -03 Media 126 Flowhood A 8" 1.00 - 170 170 170 100 - Totals : - - - - - 510 490 490 96 % - 1 OMbtes RTU -01 / FPB -102 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. 10 of 53 outlet -o1 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. 1r Consulting Encpneers Seank.; www.N .com Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -103 Tested By: Kyle Draeger AREA: Receiving Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 410 CFM VAV Address 67 VAV Fan Actual Flow 405 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 580 CFM Cooling K Factor 0.89 Clg Min Des. Primary Flow 170 CFM Fan: Variable /Constant 90% Clg Max Act. Primary Flow 575 CFM Clg Min Act. Primary Flow 165 CFM RTU -01 / FPB -103 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Receiving Flowhood B 12x12 1.00 - 460 425 465 101 Outlet -02 * Stair 160 Flowhood C 6x6 1.00 - 120 95 110 92 Totals : - - - - - 580 520 I 575 99 % - * Notes RTU -01 / FPB -103 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 SYSTEM /UNIT: RTU -01 /FPB -104 Tested By: Kyle Draeger AREA: Logistics IT Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 410 CFM VAV Address 68 VAV Fan Actual Flow 440 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 585 CFM Cooling K Factor 1.02 Gig Min Des. Primary Flow 170 CFM Fan: Variable /Constant 60% Clg Max Act. Primary Flow 600 CFM Clg Min Act. Primary Flow 160 CFM RTU - 01 / FPB - 104 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 Logistics IT Flowhood A 8" 1.00 - 195 260 205 105 Outlet -02 Logistics IT Flowhood A 8" 1.00 - 195 200 195 100 Outlet-03 * Logistics IT Flowhood A 8" 1.00 195 175 200 103 Totals : - - - - - 585 635 I 600 103 % - * Notes RTU -01 / FPB -104 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -03 10/6 11 of 53 Neudorfer Engineers, Inc. i , . I Ieudorler Engineers. Inc Consulting Engineers Saattie Portland www A ttootterEttg a:.::two Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -105 Tested By: Kyle Draeger AREA: Logistics IT Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 815 CFM VAV Address 69 VAV Fan Actual Flow 790 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1170 CFM Cooling K Factor 1.22 Clg Min Des. Primary Flow 345 CFM Fan: Variable /Constant 75% Clg Max Act. Primary Flow 1160 CFM Clg Min Act. Primary Flow 400 CFM RTU -01 / FPB -105 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Logistics IT Flowhood A 8" 1.00 - 195 210 190 97 Outlet -02 * Logistics IT Flowhood A 8" 1.00 - 195 205 185 95 Outlet -03 Logistics IT Flowhood A 8" 1.00 - 195 210 195 100 Outlet -04 Logistics IT Flowhood A 8" 1.00 - 195 260 190 97 Outlet -05 Logistics IT Flowhood A 8" 1.00 - 195 275 200 103 Outlet -06 Logistics IT Flowhood A 8" 1.00 - 195 260 200 103 Totals : - - - - - 1,170 1,420 1,160 199 % * Notes RTU -01 / FPB -105 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 10/6 12 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. .. Consuftmg Engineers Seattle Portfat d www.NeunorterEr al ..own Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -106 Tested By: Kyle Draeger AREA: Logistics IT Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 715 CFM VAV Address 70 VAV Fan Actual Flow 730 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1025 CFM Cooling K Factor 0.95 Clg Min Des. Primary Flow 310 CFM Fan: Variable /Constant 25% Clg Max Act. Primary Flow 1065 CFM Clg Min Act. Primary Flow 335 CFM RTU -01 / FPB -106 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type I D Velocity Value Reading Reading % Outlet -01 * Logistics IT Flowhood A 8" 1.00 - 205 170 210 102 Outlet -02 Logistics IT Flowhood A 8" 1.00 - 205 190 220 107 Outlet -03 Logistics IT Flowhood A 8" 1.00 - 205 200 210 102 Outlet -04 Logistics IT Flowhood A 8" 1.00 - 205 230 210 102 Outlet -05 Logistics IT Flowhood A 8" 1.00 - 205 205 215 105 Totals : - - - - - 1,025 995 1,065 104% - * Notes RTU -01 / FPB -106 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 SYSTEM /UNIT: RTU -01 / FPB -107 Tested By: Kyle Draeger AREA: Logistics IT Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 715 CFM VAV Address 71 VAV Fan Actual Flow 730 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1025 CFM Cooling K Factor 1.11 Clg Min Des. Primary Flow 310 CFM Fan: Variable /Constant 30% Clg Max Act. Primary Flow 1040 CFM Clg Min Act. Primary Flow 335 CFM RTU -01 / FPB -107 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Logistics IT Flowhood A 8" 1.00 - 205 225 205 100 Outlet -02 * Logistics IT Flowhood A 8" 1.00 - 205 205 205 100 Outlet -03 Logistics IT Flowhood A 8" 1.00 - 205 255 200 98 Outlet -04 Logistics IT Flowhood A 8" 1.00 - 205 230 210 102 Outlet -05 Logistics IT Flowhood A 8" 1.00 - 205 230 220 107 Totals : - - - 1,025 1,145 ( 1,040 101 % - 101'6otes RTU -01 / FPB -107 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. 13 of 53 Outlet -02 Neudorfer Engineers, Inc. } Neudorfer Engineers. Inc. [ 1 Got suit nq Engineers Seattle 1'101.1100 www. Neudc?rttut = own +. ..com Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -108 Tested By: Brad Haugen AREA: Exercise 103 Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 1000 CFM VAV Address 72 VAV Fan Actual Flow 980 CFM Cooling Inlet Size 12" inches Clg Max Des. Primary Flow 1430 CFM Cooling K Factor 0.94 CIg Min Des. Primary Flow 425 CFM CIg Max Act. Primary Flow 1435 CFM Clg Min Act. Primary Flow 450 CFM RTU -01 / FPB -108 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 * Exercise 103 Flowhood A 8" 1.00 - 210 155 200 95 Outlet -02 Exercise 103 Flowhood A 8" 1.00 - 210 160 200 95 Outlet -03 Exercise 103 Flowhood A 8" 1.00 - 210 220 215 102 Outlet -04 Exercise 103 Flowhood A 8" 1.00 - 210 260 210 100 Outlet -05 Exercise 103 Flowhood B 9x9 1.00 - 295 305 305 103 Outlet -06 Exercise 103 Flowhood B 9x9 1.00 - 295 270 305 103 Totals : - - - - 1,430 1,370 1,435 1100 Y - * Notes RTU -01 / FPB -108 / 29- Sep -10 Brad Haugen Volume damper is full open. Outlet -01 10/6 14 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc F Consulting Engineers Seattle Porllarid www.Meudtu 'Ei In : ,,cam Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 /FPB -209 Tested By: Kyle Draeger AREA: Board rm. 217 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 600 CFM VAV Address 81 VAV Fan Actual Flow 630 CFM Cooling Inlet Size 8x14 inches CIg Max Des. Primary Flow 865 CFM Cooling K Factor 1.14 CIg Min Des. Primary Flow 255 CFM Fan: Variable /Constant 60% CIg Max Act. Primary Flow 840 CFM CIg Min Act. Primary Flow 250 CFM RTU -01 / FPB -209 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet - Board rm. Flowhood A 8" 1.00 - 175 200 175 100 217 Outlet -02 Board rm. Flowhood A 8" 1.00 - 175 210 165 94 217 Outlet -03 * Board rm. Flowhood A 8" 1.00 - 175 160 160 91 217 Outlet -04 Rm. 218 Flowhood A 8" 1.00 - 170 245 165 97 Outlet -05 Rm.218 Flowhood A 8" 1.00 - 170 175 175 103 Totals : - - - - - 865 990 I 840 , 97 % - * Notes RTU - 01 / FPB - 209 / 28 Sep - 10 Kyle Draeger (1) Volume damper is full open Outlet -03 10/6 15 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. s Cc�rrsul1rng kn inners S? • .f - rtfarxf mit* NeuctorferEogin= - .win Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -210 Tested By: Kyle Draeger AREA: Integrated Operations 221 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 1005 CFM VAV Address 82 VAV Fan Actual Flow 990 CFM Cooling Inlet Size 12" inches Clg Max Des. Primary Flow 1435 CFM Cooling K Factor 1.00 Clg Min Des. Primary Flow 430 CFM Fan: Variable /Constant 20% Clg Max Act. Primary Flow 1415 CFM Clg Min Act. Primary Flow 455 CFM RTU -01 / FPB -210 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Integrated Flowhood A 8" 1.00 - 205 205 195 95 Operations 221 Outlet -02 * Integrated Flowhood A 8" 1.00 - 205 155 200 98 Operations 221 Outlet -03 Integrated Flowhood A 8" 1.00 - 205 235 205 100 Operations 221 Outlet -04 Integrated Flowhood A 8" 1.00 - 205 235 190 93 Operations 221 Outlet -05 Integrated Flowhood A 8" 1.00 - 205 210 215 105 Operations 221 Outlet -06 Integrated Flowhood A 8" 1.00 - 205 185 210 102 Operations 221 Outlet -07 Integrated Flowhood A 8" 1.00 - 205 220 200 98 Operations 221 Totals : - , - - - - 1,435 1,445 I 1,415 (99 % Notes RTU -01 / FPB -210 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 10/6 16 of 53 Neudorfer Engineers, Inc. J Neudorfer Eng Inc. .f Consulting Engineers Seattle Portland wwer.NsaudorterEng ..tx Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 /FPB -211 Tested By: Kyle Draeger AREA: Integrated Operations 221 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 540 CFM VAV Address 83 VAV Fan Actual Flow 560 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 760 CFM Cooling K Factor 1.03 Clg Min Des. Primary Flow 225 CFM Fan: Variable /Constant 10% Clg Max Act. Primary Flow 780 CFM Clg Min Act. Primary Flow 220 CFM RTU -01 / FPB -211 Supply Outlet Summary System I Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 * Integrated Flowhood A 8" 1.00 - 190 190 190 100 Operations 221 Outlet -02 Integrated Flowhood A 8" 1.00 - 190 195 195 103 Operations 221 Outlet -03 Integrated Flowhood A 8" 1.00 - 190 195 195 103 Operations 221 Outlet -04 Integrated Flowhood A 8" 1.00 - 190 200 200 105 Operations 221 Totals : - - - - - 760 780 780 1103 % - * Notes RTU - 01 / FPB - 211 / 1 Oct - 10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 17 of 53 Neudorfer Engineers, Inc. Neudorfer i . nc Conti ult ng €set turn c3 +vww . Neuctorriarkrkgln 4 •.coral Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -212 Tested By: Kyle Draeger AREA: Logistics 223 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 510 CFM VAV Address 84 VAV Fan Actual Flow 500 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 730 CFM Cooling K Factor 0.94 Clg Min Des. Primary Flow 220 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 730 CFM Clg Min Act. Primary Flow 230 CFM RTU -01 / FPB -212 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Stair 240 Flowhood D 6x6 1.00 - 100 95 100 100 Outlet -02 Logistics 223 Flowhood A 8" 1.00 - 210 265 215 102 Outlet -03 Logistics 223 Flowhood A 8" 1.00 - 210 235 205 98 Outlet -04 Logistics 223 Flowhood A 8" 1.00 - 210 115 210 100 Totals : - - - - - 730 710 730 100% * Notes RTU -01 / FPB -212 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 18 of 53 Neudorfer Engineers, Inc. Neudor Engineers. Inc. Consulting Eng ineets Seattle Pc tland wwNuterg .: .:. Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -213 Tested By: Brad Haugen AREA: Logistics 223 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 370 CFM VAV Address 85 VAV Fan Actual Flow 460 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 870 CFM Cooling K Factor 1.13 Clg Min Des. Primary Flow 500 CFM Clg Max Act. Primary Flow 860 CFM Clg Min Act. Primary Flow 485 CFM RTU -01 / FPB -213 Supply Outlet Summary System i Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Logistics 223 Flowhood A 8" 1.00 - 120 135 125 104 Outlet -02 Logistics 223 Flowhood A 8" 1.00 - 120 125 120 100 Outlet -03 Logistics 223 Flowhood A 8" 1.00 - 120 170 115 96 Outlet -04 Logistics 223 Flowhood A 8" 1.00 - 120 175 115 96 Outlet -05 Logistics 223 Flowhood A 8" 1.00 - 120 175 120 100 Outlet -06 Logistics 223 Flowhood A 8" 1.00 - 120 125 115 96 Outlet -07 * ' Plotter 222 Flowhood A 8" 1.00 - 150 130 150 100 Totals : - - - 870 1,035 860 99 % * Notes RTU -01 / FPB -213 29- Sep -10 Brad Haugen Terminal unit fan speed control at minimum speed. RTU -01 / FPB -213 / 29- Sep -10 Brad Haugen Volume damper is full open. Outlet -07 10/6 19 of 53 Neudorfer Engineers, Inc. isie Neudorfer Engineers. Inc. t Consultin Engineers Seattle Portland wwee.t+4eueorterEogin oom Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -308 Tested By: Kyle Draeger AREA: 2nd -3rd fl.east Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 750 CFM VAV Address 94 VAV Fan Actual Flow 760 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1070 CFM Cooling K Factor 1.08 Clg Min Des. Primary Flow 320 CFM Fan: Variable /Constant 100% Clg Max Act. Primary Flow 1245 CFM Clg Min Act. Primary Flow 325 CFM RTU -01 / FPB -308 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type I D Velocity ' Value Reading Reading % Outlet -01 * Finance 329 Flowhood A 8" 1.00 - 205 40 195 95 Outlet -02 Finance 329 Flowhood A 8" 1.00 - 205 155 205 100 Outlet -03 Finance 329 Flowhood A 8" 1.00 - 205 220 205 100 Outlet -04 Finance 329 Flowhood A 8" 1.00 - 205 190 200 98 Outlet -05 Finance 329 Flowhood A 8" 1.00 - 205 255 200 98 Outlet -06 Office 327 Flowhood A 8" 1.00 - 125 250 120 96 Outlet -07 Office 327 Flowhood A 8" 1.00 - 125 245 120 96 Totals : - - - 1,275 1,355 1,245 198 % - * Notes RTU -01 / FPB -308 22- Sep -10 Kyle Draeger Outlet total =1275. Flow balanced to 1275 CFM. RTU -01 / FPB -308 23- Sep -10 Kyle Draeger Terminal unit fan speed control at maximum speed. RTU -01 / FPB -308 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 20 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers, Inc. i t. Consulting Engineers Suattlo Portland www.Neuro erErrg ,-cam Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 /FPB -309 Tested By: Kyle Draeger AREA: Finance 329 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 865 CFM VAV Address 95 VAV Fan Actual Flow 875 CFM Cooling Inlet Size 10 inches Clg Max Des. Primary Flow 1230 CFM Cooling K Factor 0.97 Clg Min Des. Primary Flow 365 CFM Fan: Variable /Constant 80% Clg Max Act. Primary Flow 1220 CFM Clg Min Act. Primary Flow 450 CFM RTU -01 / FPB -309 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Finance 329 Flowhood A 8" 1.00 - 205 160 205 100 Outlet -02 Finance 329 Flowhood A 8" 1.00 - 205 195 205 100 Outlet -03 Finance 329 Flowhood A 8" 1.00 - 205 205 205 100 Outlet -04 Finance 329 Flowhood A 8" 1.00 - 205 215 205 100 Outlet -05 Finance 329 Flowhood A 8" 1.00 - 205 220 200 98 Outlet -06 Finance 329 Flowhood A 8" 1.00 - 205 210 200 98 Totals : - - - - - 1,230 1,205 1,220 99 % - * Notes RTU -01 / FPB -309 / 22- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 SYSTEM /UNIT: RTU -01 / FPB -310 Tested By: Kyle Draeger AREA: Finance 329 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 560 CFM VAV Address 96 VAV Fan Actual Flow 590 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 800 CFM Cooling K Factor 1.09 Clg Min Des. Primary Flow 235 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 800 CFM Clg Min Act. Primary Flow 240 CFM RTU -01 / FPB -310 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Finance 329 Flowhood A 8" 1.00 - 200 215 205 103 Outlet -02 Finance 329 Flowhood A 8" 1.00 - 200 165 200 100 Outlet -03 Finance 329 Flowhood A 8" 1.00 - 200 240 195 98 Outlet -04 Finance 329 Flowhood A 8" 1.00 - 200 230 200 100 Totals : - - - - - 800 850 1 800 1100 % - 101 tes RTU -01 / FPB -310 / 22- Sep -10 Kyle Draeger (1) Volume damper is full open. 21 of 53 outlet -o1 Neudorfer Engineers, Inc. , Neudorfer Engineers. Inc, Consulting Engineers Soatnss Poniard wwwN rEn -corn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -311 Tested By: Kyle Draeger AREA: Human Res. 335 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 560 CFM VAV Address 97 VAV Fan Actual Flow 555 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 840 CFM Cooling K Factor 1.18 Clg Min Des. Primary Flow 250 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 835 CFM Clg Min Act. Primary Flow 300 CFM RTU -01 / FPB -311 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 Human Res. Flowhood A 8" 1.00 - 200 255 200 100 335 Outlet -02 Human Res. Flowhood A 8" 1.00 - 200 240 195 98 335 Outlet -03 Office 333 Flowhood A 8" 1.00 - 220 235 215 98 Outlet -04 * Quiet rm 331 Flowhood A 8" 1.00 - 220 250 225 102 Totals : - - - - - 840 980 835 99 % - * Notes RTU -01 / FPB -311 / 22- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -04 10/6 22 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc, ut Consulting Engineers Gale Porttatd ww NeueorterEng t :_ orn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / FPB -312 Tested By: Kyle Draeger AREA: Human Res. 335 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 620 CFM VAV Address 98 VAV Fan Actual Flow 635 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 930 CFM Cooling K Factor 1.12 Clg Min Des. Primary Flow 305 CFM Fan: Variable /Constant 30% Clg Max Act. Primary Flow 950 CFM Clg Min Act. Primary Flow 355 CFM RTU -01 / FPB -312 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % _ Outlet -01 ' Human Res. Flowhood A 8" 1.00 - 140 0 140 100 335 Outlet -02 Human Res. Flowhood A 8" 1.00 - 140 180 140 100 335 Outlet -03 Human Res. Flowhood A 8" 1.00 - 140 190 140 100 335 Outlet -04 Human Res. Flowhood A 8" 1.00 - 140 185 145 104 335 Outlet -05 Human Res. Flowhood A 8" 1.00 - 140 210 140 100 335 Outlet -06 Human Res. Flowhood A 8" 1.00 - 150 175 160 107 335 Outlet -07 Comm. rm Flowhood C 6x6 1.00 - 80 100 85 106 338 Totals : - - - - - 930 I 1,040 950 102 % - * Notes RTU -01 / FPB -312 / 22- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 23 of 53 Neudorfer Engineers, Inc. t^ Neudorfer Engineers. Inc. F s di= Consulting Gngineers Seattle Portland taws Noudorfarl=rtgirr= .octrn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -101 Tested By: Brad Haugen AREA: Storage 117 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 900 CFM VAV Address 100 Clg Max Act. Primary Flow 905 CFM Cooling Inlet Size 10 inches Htg Min Des. Primary Flow 300 CFM Cooling K Factor 0.93 Htg Min Act. Primary Flow 315 CFM RTU -01 / VAV -101 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type I D Velocity Value Reading Reading % Outlet -01 Server 102 Flowhood B 6x6 1.00 - 150 120 155 103 Outlet -02 * Storage 121 Flowhood B 6x6 1.00 - 140 110 140 100 Outlet -03 Corridor 129 Flowhood B 6x6 1.00 - 150 145 145 97 Outlet -04 Services 122 Flowhood B 6x6 1.00 - 125 120 130 104 Outlet -05 Work 119 Flowhood B 6x6 1.00 - 110 135 110 100 Outlet -06 Storage 118 Flowhood B 6x6 1.00 - 150 125 150 100 Outlet -07 Storage 117 Flowhood B 6x6 1.00 - 75 130 75 100 Totals : - - - - - 900 885 I 905 1101 % - * Notes RTU -01 / VAV -101 / 29- Sep -10 Brad Haugen Volume damper is full open Outlet -02 SYSTEM /UNIT: RTU -01 / VAV -102 Tested By: Brad Haugen AREA: Conference 116 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 280 CFM VAV Address 101 Clg Max Act. Primary Flow 290 CFM Cooling Inlet Size 6 inches Htg Min Des. Primary Flow 90 CFM Cooling K Factor 1.03 Htg Min Act. Primary Flow 85 CFM RTU -01 / VAV -102 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet 01 Conference Flowhood B 9x9 1.00 - 280 290 290 104 116 Totals : - - - - - 280 290 290 104 % - * Notes 10/6 24 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. Consultin Engtneets Seattle Portland y y WW vit. Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -103 Tested By: Brad Haugen AREA: Exercise 103 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 420 CFM VAV Address 102 Clg Max Act. Primary Flow 435 CFM Cooling Inlet Size 10 inches Htg Min Des. Primary Flow 130 CFM Cooling K Factor 0.93 Htg Min Act. Primary Flow 230 CFM RTU -01 / VAV-103 Supply Outlet Summary System f Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Shower 106 Flowhood C 6x6 1.00 - 60 85 65 108 Outlet - 02 Toilet 107 Flowhood C 6x6 1.00 - 60 80 65 108 Outlet -03 Toilet 108 Flowhood C 6x6 1.00 - 60 70 60 100 Outlet -04 Shower 109 Flowhood C 6x6 1.00 - 60 70 60 100 Outlet -05 Locker 105 Flowhood C 6x6 1.00 - 90 65 90 100 Outlet -06 * Locker 104 Flowhood C 6x6 1.00 - 90 60 95 106 Totals - - 420 430 435 1104 % - * Notes RTU -01 / VAV -103 / 29- Sep -10 Brad Haugen Volume damper is full open. Outlet -06 SYSTEM /UNIT: RTU -01 / VAV -104 Tested By: Brad Haugen AREA: Exercise 103 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 550 CFM VAV Address 103 Clg Max Act. Primary Flow 545 CFM Cooling Inlet Size 8 inches Htg Min Des. Primary Flow 200 CFM Cooling K Factor 0.98 Htg Min Act. Primary Flow 190 CFM RTU -01 / VAV -104 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Corridor 134 Flowhood B 6x6 1.00 - 150 140 145 97 Outlet -02 Women 112 Flowhood C 6x6 1.00 - 200 175 205 103 Outlet -03 Men 113 Flowhood C 6x6 1.00 - 200 220 195 98 Totals : - - - - - 550 535 545 I 99 * Notes RTU -01 / VAV -104 / 29- Sep -10 Brad Haugen Volume damper is full open. Outlet -01 10/6 25 of 53 Neudorfer Engineers, Inc. i Nieudorfor Engineers. Inc. t it Consulting Engineers Scuttle Portland www. rEntri'c- c ,., Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -202 Tested By Brad Haugen AREA: Hallway Test Date, September 29, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 730 CFM VAV Address 105 Clg Max Act. Primary Flow 770 CFM Cooling Inlet Size 10" inches Htg Min Des. Primary Flow 220 CFM Cooling K Factor 1 08 Htg Min Act. Primary Flow 230 CFM RTU -01 / VAV -202 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Hallway Flowhood B 9x9 1.00 - 225 205 250 111 Outlet -02 Rm 224 Flowhood B 6x6 1.00 - 100 120 105 105 Outlet -03 Coffee 225 Flowhood B 6x6 1.00 - 115 160 110 96 Outlet -04 " Storage rm Flowhood B 6x6 1.00 - 150 105 160 107 210 Outlet -05 Storage rm Flowhood B 6x6 1.00 - 50 120 55 110 222 Outlet -06 Office 219 Flowhood B 6x6 1.00 - 90 95 90 100 Totals : - - - - - 730 805 770 1105 % - * Notes RTU -01 / VAV -202 / 29- Sep -10 Brad Haugen (1) Volume damper is full open. Outlet -04 10/6 26 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers.. Inc. 7 rS Consulting Engineers Seattle Pottle�nd wwa.NeucrcxterEngl,1 -- :,cam Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -203 Tested By: Brad Haugen AREA: Integrated Operations 221 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 835 CFM VAV Address 106 Clg Max Act. Primary Flow 815 CFM Cooling Inlet Size 10" inches Htg Min Des. Primary Flow 240 CFM Cooling K Factor 1.03 Htg Min Act. Primary Flow 240 CFM RTU -01 / VAV -203 Supply Outlet Summary System I Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet - Integrated Flowhood B 9x9 1.00 - 200 200 210 105 Operations 221 _ Outlet -02 * Integrated Flowhood B 9x9 1.00 - 200 180 205 103 Operations 221 Outlet -03 Integrated Flowhood B 9x9 1.00 - 200 215 195 98 Operations 221 Outlet -04 Integrated Flowhood B 9x9 1.00 - 200 215 205 103 Operations 221 Totals: - - - 800 810 815 1102 % - * Notes RTU -01 / VAV -203 / 29- Sep -10 Brad Haugen Volume damper is full open Outlet -02 10/6 27 of 53 Neudorfer Engineers, Inc. Ill Neudorfer ngineers.Inc. :� Consulting Er }t rs Seaale Portland Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 - 430 SYSTEM /UNIT: RTU -01 / VAV -204 Tested By: Brad Haugen AREA: Logistics 223 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 1230 CFM VAV Address 107 Clg Max Act. Primary Flow 1250 CFM Cooling Inlet Size 12" inches Htg Min Des. Primary Flow 375 CFM Cooling K Factor 1.09 Htg Min Act. Primary Flow 370 CFM RTU -01 / VAV -204 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design ' Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Office 227 Flowhood B 6x6 1.00 - 90 135 90 100 Outlet -02 Logistics 223 Flowhood B 9x9 1.00 - 230 45 240 104 Outlet -03 Office 235 Flowhood B 6x6 1.00 - 90 130 95 106 Outlet -04 Logistics 223 Flowhood B 9x9 1.00 - 230 265 230 100 Outlet -05 * Work 226 Flowhood B 6x6 1,00 - 130 150 125 96 Outlet -06 Logistics 223 Flowhood B 9x9 1.00 - 230 330 240 104 Outlet -07 Logistics 223 Flowhood B 9x9 1.00 - 230 295 230 100 Totals : - - - 1,230 1,350 1,250 1102 % - * Notes RTU -01 / VAV -204 / 29- Sep -10 Brad Haugen Volume damper is full open Outlet -05 SYSTEM /UNIT: RTU -01 / VAV -205 Tested By: Brad Haugen AREA: Toilets 229,231 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 500 CFM VAV Address 108 Clg Max Act. Primary Flow 510 CFM Cooling Inlet Size 8" inches Htg Min Des. Primary Flow 450 CFM Cooling K Factor 0.96 Htg Min Act. Primary Flow 435 CFM RTU -01 / VAV -205 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Men 231 Flowhood B 6x6 1.00 - 250 265 260 104 Outlet -02 * Women 229 Flowhood B 6x6 1.00 - 250 215 250 100 Totals : - - -_ 500 480 510 102 % - * Notes RTU -01 / VAV -205 / 1- Oct -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 10/6 28 of 53 Neudorfer Engineers, Inc. iii J. .. Neudorfer En n rs.n. Consulting Engineers Seattle Portland wwiv.$euc rferEnglf4. -- .2or Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -303 Tested By: Kyle Draeger AREA: Office 301 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 700 CFM VAV Address 111 Clg Max Act. Primary Flow 725 CFM Cooling Inlet Size 8" inches Htg Min Des. Primary Flow 210 CFM Cooling K Factor 0.98 Htg Min Act. Primary Flow 205 CFM RTU -01 / VAV -303 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Copy Flowhood B 6x6 1.00 - 130 145 130 100 Outlet -02 Recycle Flowhood B ' 6x6 1.00 - 120 160 120 100 Outlet -03 Office 301 Flowhood B 6x6 1.00 - 200 185 185 93 Outlet -04 Meeting 323 Flowhood B 6x6 1.00 - 150 155 150 100 Outlet -05 * Hallway Flowhood B 6x6 1.00 - 150 125 140 93 Totals : - - - - - 750 770 725 97 % - * Notes RTU -01 / VAV -303 22- Sep -10 Kyle Draeger Outlet total =750. Fiow balanced to 750 CFM. RTU -01 / VAV -303 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -05 SYSTEM /UNIT: RTU -01 / VAV -304 Tested By: Kyle Draeger AREA: Finance 329 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 1100 CFM VAV Address 112 Clg Max Act. Primary Flow 1110 CFM Cooling Inlet Size 10" inches Htg Min Des. Primary Flow 330 CFM Cooling K Factor 1.00 Htg Min Act. Primary Flow 345 CFM RTU -01 / VAV -304 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 " Finance 329 Flowhood D 9x9 1.00 - 220 220 220 100 Outlet -02 Finance 329 Flowhood D 9x9 1.00 - 220 210 210 95 Outlet -03 Finance 329 Flowhood D 9x9 1.00 - 220 240 240 109 Outlet -04 Finance 329 Flowhood D 9x9 1.00 - 220 225 225 102 Outlet -05 Finance 329 Flowhood D 9x9 1.00 - 220 215 215 98 Totals : - - - - - 1,100 1,110 1,110 1101 % - * Notes RTU -01 / VAV -304 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 29 of 53 Neudorfer Engineers, Inc. i. is. l eudorfer Engineers. Inc, Consult +ng Engoneers Seattle Poituard ww,r.MeuotxferEng . - -ca Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -01 / VAV -305 Tested By: Kyle Draeger AREA: Human Res. 335 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 1170 CFM VAV Address 114 Clg Max Act. Primary Flow 1145 CFM Cooling Inlet Size 10" inches Htg Min Des. Primary Flow 350 CFM Cooling K Factor 1.04 Htg Min Act. Primary Flow 335 CFM RTU -01 / VAV -305 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Work 336 Flowhood B 1.00 - 150 120 155 103 Outlet -02 Human Res. Flowhood B 1.00 - 200 235 195 98 335 Outlet -03 Human Res. Flowhood B 1.00 - 200 210 195 98 335 Outlet -04 Human Res. Flowhood B 1.00 - 200 215 195 98 335 Outlet -05 Office 334 Flowhood B 1.00 - 90 135 85 94 Outlet -06 Human Res. Flowhood B 1.00 - 200 200 195 98 335 Outlet -07 * Stair 340 Flowhood C 1.00 - 130 90 125 96 Totals : - - - - - 1,170 1,205 I 1,145 198 % - * Notes RTU -01 / VAV -305 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -07 SYSTEM /UNIT: RTU -01 / VAV -306 Tested By: Kyle Draeger AREA: Toilets 341,342 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 500 CFM VAV Address 113 Clg Max Act. Primary Flow 500 CFM Cooling Inlet Size 8" inches Htg Min Des. Primary Flow 150 CFM Cooling K Factor 1.01 Htg Min Act. Primary Flow 145 CFM RTU -01 / VAV -306 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type I D Velocity Value Reading Reading Outlet -01 * men 341 Flowhood C 6x6 1.00 - 250 215 245 98 Outlet -02 Women 342 Flowhood C 6x6 ' 1.00 - 250 285 255 102 Totals : - - - - - 500 500 I 500 100 % - * Notes RTU -01 / VAV -306 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 30 of 53 Neudorfer Engineers, Inc. Neudorfer Engtneers. 1 nc wi t i f Consulting Engineers Seattle Portland www,i+le u .com Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 Tested By: Kyle Draeger AREA: West 2nd & 3rd fl. Test Date: October 01, 2010 Unit Data Motor Data Unit Manufacturer Trane RTU -02 / Supply Fan Unit Model Number SFHLF304L Motor Manufacturer A.O. Smith Unit Serial Number Not listed Drive Type Belt Drive Unit Discharge Top Horizontal Motor Frame 256T Fan Rotation Clockwise Motor HP 20 HP RTU -02 / Filter Bank Motor RPM 1765 RPM Filter Manufacturer Airguard Motor Rated Volts 460 Volts Filter Type Pleated Motor Phase 3 Filter Quantity - Size 1 16 Motor Hertz 60 Hz Filter Dimensions - Size 1 20x20x2 Motor FL Amps 24.7 Amps Motor Service Factor 1.15 Starter Data Motor Efficiency 93.0 Motor Power Factor 81.5 PF RTU -02 / Supply Fan Installed Thermal VFD Sheave Data Test Data RTU -02 / Supply Fan Motor Sheave MFG Browning Total Design Flow 12000 CFM Motor Sheave Model 1B5V124 Total Actual Flow 12065 CFM Motor Sheave Bore B x 1 5/8 in OA Design Flow 2400 CFM Motor Sheave Type Fixed OA Actual Flow 2505 CFM Fan Sheave MFG Browning RTU -02 / Supply Fan Fan Sheave Model BK190 Fan RPM Design 1340 RPM Fan Sheave Bore 1 7/16 in. Fan RPM Actual 1189 RPM Number of Belts 1 VFD Setting 59 Hz Belt Size BX95 AHU SP Setpoint 2.2 in. Motor to Extend 2 in. Motor Volts T1 -T2 468 Volts Motor to Retract 0 in. Motor Volts T2 -T3 469 Volts Motor Volts T1 -T3 468 Volts Motor Amps T1 22.5 Amps Test Pressures Motor Amps T2 22.4 Amps SF Suction SP -1.94 in. wc Motor Amps T3 22.7 Amps SF Discharge SP 2.20 in. wc Actual Total SP 4.14 in. wc Filter DP 0.17 in. wc Coil DP 0.70 in. wc OA Damper Pos 6.0 % RA Damper Pos 94.0 °A) * Notes IRTU -02 1- Oct -10 Kyle Draeger VAV summation at this time =18660 CFM 10/6 31 of 53 Neudorfer Engineers, Inc. i . Neudorfer Engineers. Inc. . i Consulting Engineers Seattle Portland wwrw.NouttortarEn9kr'.:. ,.core Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -201 Tested By: Kyle Draeger AREA: Integrated Operations Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 815 CFM VAV Address 73 VAV Fan Actual Flow 775 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1165 CFM Cooling K Factor 1.09 Clg Min Des. Primary Flow 350 CFM Fan: Variable /Constant 100% Clg Max Act. Primary Flow 1140 CFM Clg Min Act. Primary Flow 355 CFM RTU -02 / FPB -201 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Reception Flowhood B 6x6 1.00 - 115 85 120 104 Outlet -02 Integrated Flowhood A 8" 1.00 - 150 190 140 93 Operations Outlet - Integrated Flowhood A 8" 1.00 - 150 200 145 97 Operations Outlet -04 Integrated Flowhood A 8" 1.00 - 150 190 145 97 Operations Outlet -05 Integrated Flowhood A 8" 1.00 - 150 175 150 100 Operations Outlet -06 Integrated Flowhood A 8" 1.00 - 150 170 150 100 Operations Outlet -07 Integrated Flowhood A 8" 1.00 - 150 160 140 93 Operations Outlet -08 Integrated Flowhood A 8" 1.00 - 150 165 150 100 Operations Totals : - - - - 1,165 1,335 1,140 98 % * Notes RTU -02 / FPB -201 28- Sep -10 Kyle Draeger Terminal unit fan speed control at maximum speed. RTU -02 / FPB -201 / 28- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 32 of 53 Neudorfer Engineers, Inc. Neudorfer Engineer Inc _ , 1 Consulting Engineers Seattle Pei nd www.MeuctarterErrgin =. ;_t:om Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -202 Tested By: Kyle Draeger AREA: Integrated Operations Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 490 CFM VAV Address 74 VAV Fan Actual Flow 475 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 700 CFM Cooling K Factor 0.99 Clg Min Des. Primary Flow 210 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 695 CFM Clg Min Act. Primary Flow 220 CFM RTU -02 / FPB -202 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % - Outlet-01` Integrated Flowhood A 8" 1.00 - 175 175 175 100 Operations _ Outlet -02 Integrated Flowhood A 8" 1.00 - 175 170 170 97 Operations Outlet -03 Integrated Flowhood A 8" 1.00 - 175 175 175 100 Operations Outlet -04 Integrated Flowhood A 8" 1.00 - 175 175 175 100 Operations Totals : - - - - - 700 695 695 199 % - Notes RTU -02 / FPB -202 / 24- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -01 10/6 33 of 53 Neudorfer Engineers, Inc. Ne arfo Engineers. Inc fa' Conautting Englncws Seatti9 Porttand www.NeudorlarEagln Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -203 Tested By: Kyle Draeger AREA: Breakroom 210 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 665 CFM VAV Address 75 VAV Fan Actual Flow 670 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 950 CFM Cooling K Factor 1.20 Clg Min Des. Primary Flow 285 CFM Fan: Variable /Constant 80% Clg Max Act. Primary Flow 970 CFM Clg Min Act. Primary Flow 300 CFM RTU -02 / FPB -203 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 Breakroom Flowhood A 8" 1.00 - 190 250 190 100 210 Outlet -02 * Breakroom Flowhood A 8" 1.00 - 190 100 180 95 210 Outlet -03 Breakroom Flowhood A 8" 1.00 - 190 245 190 100 210 Outlet -04 Breakroom Flowhood A 8" 1.00 - 190 265 205 108 210 Outlet -05 Breakroom Flowhood A 8" 1.00 - 190 310 205 108 210 Totals : - - - - - 950 1,170 970 102 % * Notes RTU -02 / FPB -203 / 28- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -02 10/6 34 of 53 Neudorfer Engineers, Inc. Jeud orfor n veers. Inc} _x Consuttang Engar errs mottle Portland ware NeuctorrerEfg n .. corm Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -204 Tested By: Kyle Draeger AREA: Breakroom 210 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 980 CFM VAV Address 76 VAV Fan Actual Flow 1010 CFM Cooling Inlet Size 12" inches Clg Max Des. Primary Flow 1400 CFM Cooling K Factor 1.06 Clg Min Des. Primary Flow 420 CFM Fan: Variable /Constant 40% Clg Max Act. Primary Flow 1450 CFM Clg Min Act. Primary Flow 440 CFM RTU -02 / FPB -204 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Breakroom Flowhood A 8" 1.00 - 200 240 220 110 210 Outlet -02 Breakroom Flowhood A 8" 1.00 - 200 225 215 108 210 Outlet -03 * Breakroom Flowhood A 8" 1.00 - 200 215 215 108 210 Outlet -04 Breakroom Flowhood A 8" 1.00 - 200 200 205 103 210 Outlet -05 Breakroom Flowhood A 8" 1.00 - 200 185 200 100 210 Outlet -06 Breakroom Flowhood A 8" 1.00 - 200 210 200 100 210 Outlet -07 Breakroom Flowhood A 8" 1.00 - 200 180 195 98 210 Totals : - - - - - 1,400 1,455 1,450 1104 % - * Notes RTU -02 / FPB -204 / 24- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -03 10/6 35 of 53 Neudorfer Engineers, Inc. l' N eudorfer Engineers. Inc. Consulting ErugEneers Seattle Portland www .NeuctorffrErfgln - t. own Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 /FPB -205 Tested By: Kyle Draeger AREA: Conf. 221 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 685 CFM VAV Address 77 VAV Fan Actual Flow 675 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 980 CFM Cooling K Factor 1.06 Clg Min Des. Primary Flow 295 CFM Fan: Variable /Constant 80% Clg Max Act. Primary Flow 975 CFM Clg Min Act. Primary Flow 300 CFM RTU -02 / FPB -205 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 Conf. 221 Flowhood A 8" 1.00 - 190 205 185 97 Outlet -02 Conf. 221 Flowhood A 8" 1.00 - 190 215 185 97 Outlet -03 * Conf. 221 Flowhood A 8" 1.00 - 190 180 195 ' 103 Outlet -04 Conf. 221 Flowhood A 8" 1.00 - 190 195 205 108 Outlet -05 Conf. 221 Flowhood A 8" 1.00 - 190 195 205 108 Totals : - - - - - 950 990 975 103 % - * Notes RTU -02 / FPB -205 / 28- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -03 10/6 36 of 53 Neudorfer Engineers, Inc. r Neudorfer E ngineers. inc. Consulting Ln jtneors Sttlo f'rsrtiend www.NeunlcrrlerEng _ - . ccsn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -206 Tested By: Kyle Draeger AREA: Multi -purp. 215 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 810 CFM VAV Address 78 VAV Fan Actual Flow 785 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 1130 CFM Cooling K Factor 1.27 Clg Min Des. Primary Flow 320 CFM Fan: Variable /Constant 60% Clg Max Act. Primary Flow 1150 CFM Clg Min Act. Primary Flow 520 CFM RTU -02 / FPB -206 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 * Multi -purp. Flowhood A 8" 1.00 - 200 245 210 105 215 Outlet -02 Multi -purp. Flowhood A 8" 1.00 - 200 235 210 105 215 Outlet -03 Multi -purp. Flowhood A 8" 1.00 - 200 260 200 100 215 Outlet -04 Multi -purp. Flowhood A 8" 1.00 - 200 300 200 100 215 Outlet -05 Multi -purp. Flowhood B 12x12 1.00 - 330 355 330 100 215 Totals - - - - 1,130 1,395 i 1,150 V102 % - 1 * Notes RTU -02 / FPB -206 / 28- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 37 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. Cansultbn EngarE, • ar td www.NeuoorterEngt ....corn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -207 Tested By: Kyle Draeger AREA: Multi -purp. 215 Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 915 CFM VAV Address 79 VAV Fan Actual Flow 965 CFM Cooling Inlet Size 10" inches Clg Max Des. Primary Flow 1300 CFM Cooling K Factor 1.00 Clg Min Des. Primary Flow 385 CFM Fan: Variable /Constant 30% Clg Max Act. Primary Flow 1240 CFM Clg Min Act. Primary Flow 400 CFM RTU -02 / FPB -207 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Multi -purp. Flowhood A 8" 1.00 - 200 220 195 98 215 Outlet -02 Multi -purp. Flowhood A 8" 1.00 - 200 235 190 95 215 Outlet -03 Multi -purp. Flowhood A 8" 1.00 - 200 255 185 93 215 Outlet -04 Multi -purp. Flowhood A 8" 1.00 - 200 180 190 95 215 Outlet -05 * Multi -purp. Flowhood B 9x9 1.00 - 250 215 230 92 215 Outlet -06 Multi -purp. Flowhood B 9x9 1.00 - 250 255 250 100 215 Totals : - - - 1,300 1,360 1,240 I 95 % - * Notes RTU -02 / FPB -207 / 28- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -05 10/6 38 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers Inc. , � „ a Consulting Engineers S.: € r rttand ww+x.f4auaorfrEngin: e -.cm Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -208 Tested By: Kyle Draeger AREA: Multi -purp. 215 Test Date: September 29, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 915 CFM VAV Address 80 VAV Fan Actual Flow 900 CFM Cooling Inlet Size 10" inches Clg Max Des. Primary Flow 1300 CFM Cooling K Factor 0.93 Clg Min Des. Primary Flow 385 CFM Fan: Variable /Constant 60% Clg Max Act. Primary Flow 1310 CFM Clg Min Act. Primary Flow 420 CFM RTU -02 / FPB -208 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 Multi -purp. Flowhood A 8" 1. 00 - 200 205 195 98 215 Outlet -02 Multi -purp. Flowhood A 8" 1.00 - 200 180 195 98 215 Outlet -03 Multi -purp. Flowhood A 8" 1.00 - 200 225 200 100 215 Outlet -04 Multi -purp. Flowhood A 8" 1.00 - 200 205 190 95 215 Outlet -05 Multi -purp. Flowhood B 9x9 1.00 - 250 250 265 106 215 Outlet -06 * Multi -purp. Flowhood B 9x9 1.00 - 250 175 265 106 215 Totals : - - - - - I 1,300 1,240 1,310 1101 % - * Notes RTU -02 / FPB -208 / 29- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -06 10/6 39 of 53 Neudorfer Engineers, Inc. Nouidorior n ineers Inc. � 1 Consulting En r nets Seattle f ruand www. t+IkouaortarEngin - corp Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -301 Tested By: Kyle Draeger AREA: Office 311 Test Date: October 01, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 550 CFM VAV Address 87 VAV Fan Actual Flow 525 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 780 CFM Cooling K Factor 1.03 Clg Min Des. Primary Flow 230 CFM Fan: Variable /Constant 60% Clg Max Act. Primary Flow 760 CFM Clg Min Act. Primary Flow 280 CFM RTU -02 / FPB -301 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 * Library 308 Flowhood B 6" 1.00 - 100 65 95 95 Outlet -02 Library 308 Flowhood A 8" 1.00 - 140 175 135 96 Outlet -03 Office 309 Flowhood A 8" 1.00 - 180 170 180 100 Outlet -04 Office 311 Flowhood A 8" 1.00 - 180 185 175 97 Outlet -05 Office 312 Flowhood A 8" 1.00 - 180 220 175 97 Totals : - - - - - 780 815 760 97 % - * Notes RTU -02 / FPB -301 / 24- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 SYSTEM /UNIT: RTU -02 / FPB -302 Tested By: Kyle Draeger AREA: Office 313 Test Date: September 23, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 415 CFM VAV Address 88 VAV Fan Actual Flow 405 CFM Cooling Inlet Size 8" inches Clg Max Des. Primary Flow 585 CFM Cooling K Factor 1.00 Clg Min Des. Primary Flow 170 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 580 CFM Clg Min Act. Primary Flow 160 CFM RTU -02 / FPB -302 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 * Office 313 Flowhood A 8" 1.00 - 195 185 185 95 Outlet -02 Office 313 Flowhood A 8" 1.00 - 195 190 190 97 Outlet -03 Office 313 Flowhood A 8" 1.00 - 195 205 205 105 Totals : - - - - - 585 580 I 580 99 % - * Notes RTU -02 / FPB -302 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 10/6 40 of 53 Neudorfer Engineers, Inc. iti i , . Neudorfer Engineers... Inc. ° Consuttang Engineers Seattle Portland www.NauoorferEogkt ..Gera Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -303 Tested By: Kyle Draeger AREA: Office 314 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 680 CFM VAV Address 89 VAV Fan Actual Flow 665 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 960 CFM Cooling K Factor 1.24 Clg Min Des. Primary Flow 280 CFM Fan: Variable /Constant 80% Clg Max Act. Primary Flow 985 CFM Clg Min Act. Primary Flow 350 CFM RTU -02 / FPB -303 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading Outlet -01 ' Office 316 Flowhood A 8" 1.00 - 160 195 170 106 Outlet -02 Office 316 Flowhood A 8" 1.00 - 160 220 165 103 Outlet -03 Office 315 Flowhood A 8" 1.00 - 160 80 170 106 Outlet -04 Office 315 Flowhood A 8" 1.00 - 160 220 170 106 Outlet -05 Office 314 Flowhood A 8" 1.00 - 160 250 155 97 Outlet -06 Office 314 Flowhood A 8" 1.00 - 160 225 155 97 Totals : - - - 960 1,190 985 103 % - * Notes RTU -02 / FPB -303 I 24- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -01 SYSTEM /UNIT: RTU -02 / FPB -304 Tested By: Kyle Draeger AREA: Office 317 Test Date: September 23, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 560 CFM VAV Address 90 VAV Fan Actual Flow 585 CFM Cooling Inlet Size 8x14 inches Clg Max Des. Primary Flow 800 CFM Cooling K Factor 1.20 Clg Min Des. Primary Flow 240 CFM Fan: Variable /Constant 30% Clg Max Act. Primary Flow 810 CFM Clg Min Act. Primary Flow 235 CFM RTU -02 / FPB -304 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Office 317 Flowhood A 8" 1.00 - 200 255 200 100 Outlet -02 * Office 317 Flowhood A 8" 1.00 - 200 230 205 103 Outlet -03 Office 317 Flowhood A 8" 1.00 - 200 230 205 103 Outlet -04 Office 317 Flowhood A 8" 1.00 - 200 225 200 100 Totals : - - - - - 800 940 I 810 101 % - 10rfotes RTU -02 / FPB -304 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. 41 of 53 Outlet -02 Neudorfer Engineers, Inc. Neudorfer Eng Inc. Consulting Engineers Seattle Portland woe* , NeoctoderEng ..:. «,n, Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -305 Tested By: Kyle Draeger AREA: Office 321 Test Date: September 23, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 1400 CFM VAV Address 91 VAV Fan Actual Flow 1425 CFM Cooling Inlet Size 14" inches Clg Max Des. Primary Flow 1980 CFM Cooling K Factor 1.21 Clg Min Des. Primary Flow 580 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 1905 CFM Clg Min Act. Primary Flow 555 CFM RTU -02 / FPB -305 Supply Outlet Summary System f Unit Area Served Type of Outlet Size LxW - AK Design Design Prelim Final Final Remarks Reading Type I D Velocity Value Reading Reading % Outlet -01 Office 318 Flowhood A 8" 1.00 - 165 205 160 97 Outlet -02 Office 318 Flowhood A 8" 1.00 - 165 170 155 94 Outlet -03 Office 318 Flowhood A 8" 1.00 - 165 190 155 94 Outlet -04 Office 319 Flowhood A 8" 1.00 - 165 205 165 100 Outlet -05 Office 319 Flowhood A 8" 1.00 - 165 190 165 100 Outlet -06 Office 319 Flowhood A 8" 1.00 - 165 175 155 94 Outlet -07 Office 321 Flowhood A 8" 1.00 - 165 255 160 97 Outlet -08 Office 321 Flowhood A 8" 1.00 - 165 240 160 97 Outlet -09 Office 321 Flowhood A 8" 1.00 - 165 185 160 97 Outlet -10 Office 322 Flowhood A 8" 1.00 - 165 210 160 97 Outlet -11 * Office 322 Flowhood A 8" 1.00 - 165 165 155 94 Outlet -12 Office 322 Flowhood A 8" 1.00 - 165 215 155 94 Totals : - - - - 1,980 2,405 1,905 96 % * Notes RTU -02 / FPB -305 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -11 10/6 42 of 53 Neudorfer Engineers, Inc. Neudorfer Engineers. I nc. Consulting Engineers Seattle Portland wiry/. NeudcatterErt91. .coils Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / FPB -306 Tested By: Kyle Draeger AREA: Conf. 302 Test Date: September 23, 2010 Unit Data Air Test Data Manufacturer TRANE VAV Fan Design Flow 850 CFM VAV Address 92 VAV Fan Actual Flow 840 CFM Cooling Inlet Size 10" inches Clg Max Des. Primary Flow 1200 CFM Cooling K Factor 1.04 Clg Min Des. Primary Flow 350 CFM Fan: Variable /Constant 50% Clg Max Act. Primary Flow 1155 CFM Clg Min Act. Primary Flow 330 CFM RTU -02 / FPB -306 Supply Outlet Summary System / Unit , Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type t D Velocity Value Reading Reading % Outlet -01 * Conf. 302 Flowhood A 8" 1.00 - 200 180 190 95 Outlet -02 Conf. 302 Flowhood A 8" 1.00 - 200 195 195 98 Outlet -03 Conf. 302 Flowhood A 8" 1.00 - 200 210 190 95 Outlet -04 Conf. 302 Flowhood A 8" 1.00 - 200 220 190 95 Outlet -05 Conf. 302 Flowhood A 8" 1.00 - 200 225 190 95 Outlet -06 Conf. 302 Flowhood A 8" 1.00 - 200 220 200 100 Totals : - - - 1,200 1,250 1,155 ( 96 % - * Notes RTU -02 / FPB -306 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -01 SYSTEM /UNIT: RTU -02 / FPB -307 Tested By: Kyle Draeger AREA: Office 324 Test Date: September 23, 2010 Unit Data . Test Data Manufacturer TRANE VAV Fan Design Flow 415 CFM VAV Address 93 VAV Fan Actual Flow 255 CFM Cooling Inlet Size 8" inches CIg Max Des. Primary Flow 615 CFM Cooling K Factor 1.16 CIg Min Des. Primary Flow 200 CFM Fan: Variable /Constant 100% CIg Max Act. Primary Flow 615 CFM Clg Min Act. Primary Flow 185 CFM RTU -02 / FPB -307 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type I D Velocity Value Reading Reading % Outlet -01 * Office 324 Flowhood A 8" 1.00 - 205 240 200 98 Outlet -02 Office 324 Flowhood A 8" 1.00 - 205 240 205 100 Outlet -03 Office 324 Flowhood A 8" 1.00 - 205 240 210 102 - Totals - - - • 615 720 I 615 100 % - * Notes RTU -02 / FPB -307 23- Sep -10 Kyle Draeger Terminal unit fan speed control at maximum speed. 10/6 RTU -02 / FPB -307 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open. 43 of 53 Outlet -01 Neudorfer Engineers, Inc. Neudorfer Engineers. Inc. ii t Cnsuttong Erx,}sneers Seattle Portland v►`v+rrr.Maudorfi r ragirs o ..:.txxn Roof Top Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / VAV -201 Tested By: Brad Haugen AREA: Hallway Test Date: September 28, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 900 CFM VAV Address 104 Clg Min Des. Primary Flow 925 CFM Cooling Inlet Size 10" inches Htg Min Des. Primary Flow 300 CFM Cooling K Factor 0.99 Htg Min Act. Primary Flow 310 CFM RTU -02 / VAV -201 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet - * Integrated Flowhood B 6x6 1.00 - 150 120 160 107 Operations Outlet -02 Storage 217 Flowhood B 6x6 1.00 - 50 100 50 100 Outlet -03 Mail 204 Flowhood B 6x6 1.00 - 110 95 110 100 Outlet -04 Rm 205 Flowhood B 6x6 1.00 - 120 85 120 100 Outlet -05 Hallway Flowhood B 6x6 1.00 - 125 100 135 108 Outlet -06 Hallway Flowhood B 6x6 1.00 - 125 135 130 104 Outlet -07 Storage rm Flowhood B 6x6 1.00 - 70 125 70 100 Outlet -08 Toilets 213 Flowhood C 6x6 1.00 - 50 70 50 100 Outlet -09 Toilets 212 Flowhood C 6x6 1.00 - 50 80 50 100 Outlet -10 Janitor 204 Flowhood B 6x6 1.00 - 50 85 50 100 Totals : - - 900 995 925 103 Vi - * Notes RTU -02 / VAV -201 / 28- Sep -10 Brad Haugen Volume damper is full open. Outlet -01 10/6 44 of 53 Neudorfer Engineers, Inc. ii Neudor Engineers. Inc, C onsulting Engineers Seattle Portland www,N. _ .- Roof Top Unit PROJECT: TVF&R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: RTU -02 / VAV -301 Tested By: Kyle Draeger AREA: Executve staff 305 Test Date: September 24, 2010 Unit Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 1075 CFM VAV Address 109 Clg Max Act. Primary Flow 1105 CFM Cooling Inlet Size 10 inches Htg Min Des. Primary Flow 325 CFM Cooling K Factor 0. Htg Min Act. Primary Flow 310 CFM RTU -02 / VAV -301 Supply Outlet Summary System I Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Executve Flowhood D 9x9 1.00 315 350 320 102 staff 305 Outlet -02 Executve Flowhood D 9x9 1.00 - 315 335 330 105 staff 305 Outlet -03 * Executve Flowhood D 9x9 1.00 - 315 285 330 105 staff 305 _ Outlet -04 Stair 360 Flowhood D 6x6 1.00 - 130 0 125 96 Totals : 1,075 970 1,105 1103 % - * Notes RTU - / VAV -301 I 24- Sep -10 Kyle Draeger (1) Volume damper is full open. Outlet -03 SYSTEM /UNIT: RTU -02 / VAV -302 Tested By Kyle Draeger AREA: Executve staff 305 Test Date: September 23, 2010 Un Data Air Test Data Manufacturer TRANE Clg Max Des. Primary Flow 840 CFM VAV Address 110 Clg Max Act. Primary Flow 850 CFM Cooling Inlet Size 10 inches Htg Min Des. Primary Flow 255 CFM Cooling K Factor 0.97 Htg Min Act. Primary Flow 255 CFM RTU -02 / VAV -302 Supply Outlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Outlet -01 Executve Flowhood D 9x9 1.00 - 280 265 285 102 staff 305 Outlet -02 * Executve Flowhood D 9x9 1.00 - 280 260 285 102 staff 305 Outlet -03 Executve Flowhood D 9x9 1.00 - 280 290 280 100 staff 305 Totals: - - - - - ` 840 815 850 101 % - * Notes RTU -02 / VAV -302 / 23- Sep -10 Kyle Draeger (1) Volume damper is full open Outlet -02 10/6 45 of 53 Neudorfer Engineers, Inc. II i . Neudor er Engineers. Inc. Consulting Engineers Seattle Portland www .NeudorferEng r Fan Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: CRU -01 Tested By: Kyle Draeger AREA: Server rm. Test Date: October 01, 2010 Unit Data Motor Data Fan Manufacturer Liebert Motor Manufacturer Emerson Fan Model Number DS035AUA001871A Motor Frame 182T Fan Serial Number C10G8E0001 Motor HP 3 HP Fan Rotation Clockwise Motor RPM 1770 RPM Drive Type Belt Drive Motor Rated Volts 460 Volts Motor Phase 3 Starter Data Motor Hertz 60 Hz Motor Full Load Amps 3.90 Amps Installed Thermal H2108B Motor Service Factor 1.15 Rating (Amps) 3.38 - 5.54 Amps Nominal Efficiency 89.5 % Required Thermals H2108B Power Factor 80.0 Required Amps 3.90 Amps Test Data Sheave Data Motor Sheave MFG Browning Total Design Flow 5500 CFM Motor Sheave Model 2BK40 Total Actual Flow 5277 CFM Motor Sheave Bore H x 1 1/8 in. Fan RPM Actual 754 RPM Motor Sheave Type Fixed Motor Volts T1 -T2 475 Volts Fan Sheave MFG Browning Motor Volts T2 -T3 476 Volts Fan Sheave Model BK90 Motor Volts T1 -T3 480 Volts Fan Sheave Bore H x 1 3/16 in. Motor Amps T1 3.00 Amps Number of Belts 2 Motor Amps T2 3.30 Amps Belt Size 181030P1 Motor Amps T3 3.20 Amps Sheave Center Line 14.25 in. Motor to Extend 2 in. Motor to Retract 2 in. Test Pressures Fan Suction SP -0.67 in. we * Notes CRU -01 30- Sep -10 Kyle Draeger DP of filters and coil together = 0.62 CRU -01 30- Sep -10 Kyle Draeger No access to discharge in the floor. 10/6 46 of 53 Neudorfer Engineers, Inc. 10 f Neudorfer Engineers. Inc. , i Ctxnauttng Engineers Seattle F gtianet wwww. NeeeufiarEeg r,. ._met Duct Traverse PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: CRU -01 Tested By: Kyle Draeger Test Date: September 30, 2010 Unit Data Final Data Type of Traverse Rectangular Sum of Readings 22698 Outer Height 26 in. Average Reading 504 FPM Outer Width 58 in. Design Total Flow 5500 CFM Air Flow Area 10.47 sq. ft. Actual Total Flow 5277 CFM Number Of Rows 5 Static Pressure -0.05 in. Readings Per Row 9 Total Readings 45 NOTES: Duct Traverse Data Points r N C7 Q N !O A co Q, ) O 9 4 C O O 1 1 Row 1 1 512 I 1 266 I 1 376 I 1 466 I 1 549 I 1531 I 1 533 1 636 I 613 I Row 2 1 617 I 1 358 11 514 5901 1 6231 1523 I 1 539 1 537 I 1 574 I Row 3 1 602 I 1 497 I 1 567 i 1 875 I 641 I 491 1 1 554 I 1 362 1 253 I r te , Row 4 1 585 I 1 568 I I 564 I 1 539 I 1 516 I 1 391 I 1 446 I I I 1 405 Row 5 I ass 1 463 I 1 637 I 1 419 11 I 1 473 I 1 409 1 1 542 I 1 563 58 >1 10/6 47 of 53 Neudorfer Engineers, Inc. si ji Neudo er Engineers. Inc Conraeltang Engineers Seattle Portland wwvr.N®udtrferErrg _.: .corm Fan Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: CRU -02 Tested By: Kyle Draeger AREA: Server rm. Test Date: October 01, 2010 Unit Data Motor Data Fan Manufacturer Liebert Motor Manufacturer Emerson Fan Model Number DS035AUA001871A Motor Frame 182T Fan Serial Number C10G8E0002 Motor HP 3 HP Fan Rotation Clockwise Motor RPM 1770 RPM Drive Type Belt Drive Motor Rated Volts 460 Volts Motor Phase 3 Starter Data Motor Hertz 60 Hz Motor Full Load Amps 3.90 Amps Installed Thermal H2108B Motor Service Factor 1.15 Rating (Amps) 3.38 - 5.54 Amps Nominal Efficiency 89.5 % Required Thermals H2108B Power Factor 80.0 Required Amps 3.90 Amps , Test Data Sheave Data Motor Sheave MFG Browning Total Design Flow 5500 CFM Motor Sheave Model 2BK40 Total Actual Flow 5355 CFM Motor Sheave Bore H x 1 1/8 in. Fan RPM Actual 766 RPM Motor Sheave Type Fixed Motor Volts T1 -T2 476 Volts Fan Sheave MFG Browning Motor Volts T2 -T3 477 Volts Fan Sheave Model BK90 Motor Volts T1 -T3 481 Volts Fan Sheave Bore H x 1 3/16 in. Motor Amps T1 3.00 Amps Belt Size 181030P1 Motor Amps T2 3.40 Amps Sheave Center Line 14.25 in. Motor Amps T3 3.30 Amps Motor to Extend 2 in. Motor to Retract 2 in. Test Pressures Fan Discharge SP -0.69 in. we * Notes CRU -02 30- Sep -10 Kyle Draeger DP of filters and coil together = 0.62 CRU -02 30- Sep -10 Kyle Draeger No access to discharge in the floor. 10/6 48 of 53 Neudorfer Engineers, Inc. Consulting Engineers Seattle Portland www.NeudorterEragth ,corm Fan Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: EF -02 Tested By: Kyle Draeger AREA: Central exhaust all floors Test Date: October 01, 2010 Unit Data Motor Data Fan Manufacturer Greenheck Motor Manufacturer Marathon Fan Model Number 135 ACE Motor Frame 48Z Fan Serial Number 034SD23254- 00/0000701 Motor HP 1/2 HP Fan Rotation Counterclockwise Motor RPM 1725 RPM Drive Type Belt Drive Motor Rated Volts 115 Volts Motor Phase 1 Starter Data Motor Hertz 60 Hz Motor Full Load Amps 7.5 Amps Installed Thermal Thermally protected Motor Service Factor 1.25 Test Data Sheave Data Total Design Flow 1500 CFM Motor Sheave MFG Maska Total Actual Flow 1180 CFM Motor Sheave Model 1VL34 Fan RPM Actual 1486 RPM Motor Sheave Bore 1/2 in. Motor Volts T1 -T2 119 Volts Motor Sheave Type Adjustable Motor Amps T1 6.7 Amps Adj Mtr Sheave Pos Middle Fan Sheave MFG Maska Fan Sheave Model MA38 Fan Sheave Bore 3/4 in. Number of Belts 1 Belt Size 4L210 Sheave Center Line 5.25 in. Motor to Extend 2 in. Motor to Retract 2 in. EF -02 Exhaust Inlet Summary System / Unit - Area Served Type of Outlet Size LxW AK Design ` Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Inlet -01 Locker105 Flowhood E 6x6 1.00 - 115 105 120 104 Inlet -02 * Locker104 Flowhood E 6x6 1.00 - 115 100 110 96 Inlet -03 Shower 106 Flowhood E 6x6 1.00 - 75 50 70 93 Inlet -04 Toilets 107 Flowhood E 6x6 1.00 - 75 50 75 100 Inlet -05 Toilets 108 Flowhood E 6x6 1.00 - 75 55 70 93 Inlet -06 Shower 109 Flowhood E 6x6 1.00 - 75 60 75 100 Inlet -07 Elec. 232 Airfoil E 9" 0.44 681 300 295 295 98 Inlet -08 Elec. 339 Airfoil E 9" 0.44 681 300 450 295 98 Inlet -09 Jan. 325 Flowhood E 6x6 1.00 - 70 185 70 100 Totals : - - - - - 1,200 I 1,350 1,180 [98 % * Notes EF -02 30- Sep -10 Kyle Draeger Outlet total CFM= 1200. EF -02 / Inlet -02 1- Oct -10 Kyle Draeger (1) Volume damper is full open. 10/6 49 of 53 Neudor er Engineers, Inc. Neudorfer Engineers. Inc. Consulting Engineers Seattle Portland wentNoudorterEr /.. „cern Fan Unit PROJECT: TVF &R Command and business ops center DATE: 10/1/2010 LOCATION: , OR CONTACT: Kyle Draeger PROJECT #: 2010 -430 SYSTEM /UNIT: EF -03 Tested By: Kyle Draeger AREA: Breakroom 210 Test Date: October 01, 2010 Unit Data Motor Data Fan Manufacturer Greenheck Motor Manufacturer Marathon Fan Model Number 135 ACE Motor Frame 48Y Fan Serial Number 034SD23254- 00/0002001 Motor HP 1/3 HP Fan Rotation Counterclockwise Motor RPM 1725 RPM Drive Type Belt Drive Motor Rated Volts 115 Volts Motor Phase 1 Starter Data Motor Hertz 60 Hz Motor Full Load Amps 5.5 Amps Installed Thermal Thermally protected Motor Service Factor 1.35 Test Data ' Sheave Data Total Design Flow 1225 CFM Motor Sheave MFG Maska Total Actual Flow 990 CFM Motor Sheave Model 1VL34 Fan RPM Actual 1102 RPM Motor Sheave Bore 1/2 in. Motor Volts T1 -T2 119 Volts Motor Sheave Type Adjustable Motor Amps T1 5.3 Amps Adj Mtr Sheave Pos Maximum Fan Sheave MFG Maska Fan Sheave Model AL54 Fan Sheave Bore 3/4 in. Number of Belts 1 Belt Size 4L240 Sheave Center Line 5.25 in. Motor to Extend 2 in. Motor to Retract 2 in. EF -03 Exhaust Inlet Summary System / Unit Area Served Type of Outlet Size LxW AK Design Design Prelim Final Final Remarks Reading Type / D Velocity Value Reading Reading % Inlet -01 Breakroom Flowhood H 10x10 1.00 - 250 305 185 74 210 Inlet -02 Breakroom Flowhood H 10x10 1.00 - 250 250 185 74 210 Inlet -03 Breakroom Flowhood H 10x10 1.00 - 250 215 190 76 210 Inlet -04 Breakroom Flowhood H 10x10 1.00 - 250 205 190 76 210 Inlet -05 Toilets 212 Flowhood E 6x6 1.00 - 75 30 80 107 Inlet -06 Toilets 213 Flowhood E 6x6 1.00 - 75 30 80 107 Inlet -07 * Jan. 200 Flowhood E 6x6 1.00 - 75 25 80 107 Totals : - - - - 1,225 1,060 990 1 81 % - * Notes EF -03 1- Oct -10 Kyle Draeger Proportioned system so toilets would draw negative pressure. EF -03 30- Sep -10 Kyle Draeger Speeding fan up anymore exceeds rated amperage. EF -03 / Inlet -07 30- Sep -10 Kyle Draeger (1) Volume damper is full open. 10/6 50 of 53 Neudorfer Engineers, Inc. • 'O 0 O O 5 O O O , , I I ®, LT' A �' , - 4401 �T k i ll. M �� �� t • -. (fA 1. 120 $ —f? � 1111.1,7 T D , '� .� wy A �'� �� •, �_ ' t <�. ,�: Try ► ® - . 1 B. _ � ! +- p _ ; ® _B , ®4 , W - i�j MIm1il�� . J` •y /. — —� - - --- • © ` �E - ( , - �,..�,, - - ►�(�y �� xl', � ►�E ,�ri.����■, r. i !t � � ° �j � C , X37 � � � e il 7i •. ( r - I 411 � I O .. 0 1 l _ . , 0, I - gemli mi e, G ' fe i ■ ry 0 I . N e , �. ' NIA , . . Om . : I gm : ma r.:.4 A _ 1 � •' L I l y �3` 1 4i 1 ® _ —_ —_ -,- - i b IF ■ .. _.' I LA. 1�4.�., - _- � r-: _ `' 1 01 Ln [� �r P � y IY i —� — ElEIIIIL A �' � J 4 '! ' ,. � d , ► =R �� �,'�� 1 f ! s1r ' O � ���u � a 4 . ©° A -I 10►° ° L! • ` ,a IIif OI� 2103 )< 11Vom � Zrk:1 Q _". _ o f ♦ - ,r ' a ' . ,9, ,� �. /.yrrv4 D i I I r =1 D p+�1,S1 )• 41)� '/ ® n. �_ � � ' t % �' _ — r-� -- — — — ii-pie ,-� �.,� E ; I �'� 1 1 _ I � +5EISPz �■�05eIQ =� ti � t 12 G7 `-T, — ;( 111 .9 : �' et �� . , a , B _ ma y _ �' n '�� : � s � �._I�� -2-0-1 4 ►� ' <Ie �� �i ,, • 14 KS 0 X 1 , 1 lom I z IT] , , EL I1 , 1 L 1170 0 1/1 I `� `'�L^II I 1.1 ' ,,, „ 1 . i • • , aNt_ _ �� L LT . L•7 . . _:,..,, , -.7iik , 7I --. a ��\\ T 5 o D 5 �MI WI., 5 I3['Y. • •. 4 . 0 0 2 3 q O (i O O 1 FIRST FLOOR - MECHANICAL a M2.1 SCALE: 1/6" - 1' -0' GENERAL NOTES NOTES THIS SHEET A MAINTAIN BOTTOM OF DUCT AND EQUIPMENT ELEVATIONS AS HIGH AS 0 PROVIDE 100 DUCT AND TERMINATE OPEN END ABOVE TRANSFORMER W 0 PROVIDE SERVICE AND MAINTENANCE CLEAR POSSIBLE BUT NO LOWER ABOVE FINISHED FLOOR THAN EXISTING 5' AFF. SET AIRFLOW FOR 300 CFM. BOTTOM OF TERMINAL UNIT AS REQUIRED E \P MAIN DUCT ELEVATION. ; RECOMMENDED BY MANUFACTURER. LOCATE O2 REMOVE DUCT BACK TO VAV BOX AND CAP. BOTTOM OF BAR JOISTS AND RUN SUPPLY 0- B. FOR CLARITY A SINGLE LINE HAS BEEN USED 10 REPRESENT WEBS' TYPICAL 3 MULTIPLE REFRIGERANT PIPES ON THIS DRAWING. ACTUAL PIP O PROVIDE RA BOOT FOR ALL RETURN GRILLES, SEE 7/143.1. ■ Q PROVIDE SERVICE AND MAWTENANCE CLEAR QUANTITY AND STZE SHALL BE DETERMINED DURING PIPE SIZING TO TERMINAL UNIT AS REQUIRED BY CODE AM ,n MANUFACIURFR'S RECOMMENDATIONS. ® SEE DETAIL 5/143.1. TYPICAL FOR ALL FAN POWERED BOXES: MANUFACTURER. L0O4TE ALL TERMINAL UHT N A .. ,.,.a aaa. ra.... .raw a rco ,ur. RETURN PLENUM. ALL AREAS /1 SPT f1FT 5 /M3 . 1. TYPICAL FOR ALL VAV BOXES. JOISTS AND RUN SUPPLY DUCTS THROUGH . • ., • ,1 0 • 0. . Cy£Y D - Ara _ _ ten► A 0 A NOE lYP.3 11E7 '. 7 Tit•:1 Mg7 TYF II I I I a - 1- --- - - f � � e I 0 I� : �— Iii — vs ----_` { !' 11, - R - 0 � , �M .1 lU � 111.1114..... O . , , � -. � 1 i� Q G� rr Yr7 ��I , � �� ' , 10 oY �/W NP. 4 1 B I i ` , 00 #f 1 0 - B.. "� �. , � , ' 0 �� © + - �r "YI!' I I.� �p �'t00I j - 'Iii \� .�,;FPB -w7 i" I�I� ® h r`s'"""" FPB - 2 13 6 I 80 r _ .._ D �Y �J _ I � P � � 14x8 O �_ _ ,: ° _ - Al: Ma �` ��E f lle lru '� i � � -" /1, ee I � 9 y I t {1 WI' es . 48 cit c a� „e `® I� M6, 0TJ ! L . I i : 1 . vnv-2o1 r► 14 z _. �� PIr , FP=- 202 ® .� - to u �', , ■ to . Y p I 1 ' � i till 1 T .. I).7 = �+ di_ - , - -. - E � .r !TS” IL : ee {{may ,- fe -1- I L�'.� r t x: '.. II 14e 1��1 r.r. ` ' I� � ,. _, I ■ � QI7 TYP. 1 1 160 s ` ' p ►• ( E )46x12 •,7 aII i l�� �� 17 ,.._ x1 �!'': l� tly „ may D O r l . ■ I • ��, ►) G Al i ' , - i t w _ e. , . w . _ a , _ 1,. -: � � - = _ .12' .:,, ams Lima '"'°__ ► (r/I ► 120 �(- low � �i' II 1 I : g0 C ► . ' ► rte, D I y� r >, D� as 60 i III p ,, � � 3 -, f ` Q► + I aq a -- _ r Yr .Ya t�`- ^ (ENsI© .. .+� O L04, i o (� . � : � [: 3 ts' I �� S : y r , ,° � I ',, a {, ,i + ii � _ �. /ACM I ' � .. P8- , 6 207 I ryiy ' ■ F.,3 , 7 r.n; , . ' -- - _ I -1: fii fYOC:dfl _ it - - 72 - - ga -- - - - ■ p O toe �( .v.. AVIII ' ► d - C „ �� . ►1 ^� "" � .. �zJ�l �� 0 ► .4 eo.,mw,.4 @.1 +� of v M iiik I O ,, FFP8 ` \ l � ® FPB -205 0 vi IIF� TIN. 12 wwl..n .. - / — B0 + I i, ' -L°11111, De _ 1 20 1D,L ©��. 6 161°° 0 I ems..: woos, ,. 16x12 'i , ru AMnx,e I , ' F 100 i 11,_� 12 ` "pow 1 18x1 . ` - 0 8 � SI ► * � L u- - - . Q _ f ; T" . el t� 46 6. - � 2 8e Wl - 1 ■. ll� -- rte— — — = —�i �i _ _ - -�t� _ Om_ A t ! - I A a i B .. O WAIT - A. -. TYP. 3 Mak / 0 • r - I 4 A A '. 5 0 7YP. 4 0 SECOND FLOOR - MECHANICAL ...... ,„ .. 1._o- GENERAL:NOTES NOTES THIS SHEET A. MAINTAIN BOTTOM I OF DUCT AND EQUIPMENT ELEVATIONS AS HIGH AS Ot PROVIDE RA BOOT FOR All RETURN GRILLES. SEE DETAIL 7/M3.1. POSSIBLE BUT NO LOWER ABOVE FINISHED FLOOR THAN EXISTING MAIN DUCT ELEVATION. 0 6'0 DOWN TO REGISTER, PROVIDE MD. B. FOR CLARITY A SINGLE LINE HAS BEEN USED TO REPRESENT 3 PROVIDE 100 DUCT AND TERMINATE OPEN END ABOVE TRANSFORMER 0 5FT AFF. MULTIPLE REFRIGERANT PIPES ON THIS DRAWING. ACTUAL. PIP AIRFLOW FOR 300 CFM. QUANTITY AND SIZE SHALL BE DETERMINED DURING PIPE SIZING TO MANUFACTURER'S RECOMMENDATIONS. LO. SEE DETAIL 5/M3.1. TYPICAL FOR ALL FAN POWERED BOXES. (,,:_ T „, T Cer) '[> CAI . r TS�� i Q S7I 7 �g.4. . •.a ea 1 1 I - •s. ' Eg1,1 . f u s • �C3 TYP iL7 - w r— _ �. Ds . .� �� — 89 F ` liC J - I - ■ a ter • — VIM i, j t - �Y S i ICI � . . / <a liCiiiiii:t r !■� " .t. 0 ,• ri�� ..1. J� FPO- i r •� . {�! - r t a ���I w yv $ /�14 ° 1 4 tail. t i7+8 b s , 30J _ ` t P � Al ►� WI ' J ► ' l `' , . gil ~ [ ti i �C ` 8 � ' 4 © r1 MtI1IfT1�> tip t 1, n� ltxl i TIT.. ! ♦?S'� ms li IIIC e a ! � � d / I � �tE? �t ' i€3 S ' + � j1Y pT `D . : i wbir - . 3 gg,0 Fo --. 'il ) — - : ‘ , , ra—,,k - - '. 77 .116 [ If re , • . > A — �.� Mil G x.lihi 7 {D 2 a+ t+ D \ A t r >rt y � c ? f ........ o � �. _ Iii. �■ :1 8 �' � a _ �� � ,.. ;. ...'.� �Gf <0 ��•, _ ... 'e.� A Vile G V k�i) 3 Q JILL A . _, 4 / � il 4 a !% ►„�` ti:Pl. ►jy : ! • ►,•E , � '.' IOW 4 1 ° 1 ! 4 / 2" / 12p �� �, wa - it +1 Tii , � !i# 4 n k R i i . � I 1 * 5 a71�i Q►ib < nl Y �f as l � �tF'i t ,_,_ r v 't ill 0rs� s.. {0)547,, c t` - °, Y _ f - „ 4 i °l 3i , 12 _ 1 -4 /ter G — c,4 14 - - -T SBx� y � � � :�� ►�i r � w a r ' �n - `i 1 �� i 1 &i a ., F 04 A ; [Fir X111 ®7 , t, � � .`- � i� �,.,. r : ' I Vet - - � t �i� E ttI 115! I �ie ` -, ® Z '. ( Itttttf w1 / iz. El ! _ ( - �t l ,..u. FPO [ 1 • 1 �� � T7+ 1� 1 • e+ ze Ma ; 'I . P f ,..,,,e7,12 ^, 1 a , tJ °-\ ft Kg Tiors• E17"1. s;- 12 , lir gii . , ,: ..5, aet .._•.. 'C'� , .„ 4 "— - . a a I ' ' j`r� A A t i �.0 8 9 - LCZ A 074'. • ;,. 89 A Zit. P. 3 g R 118 TH O ' FL9t-4 RR - MECHANICAL GENERAL NOTES NOTES THIS SHEET �- -- - -- _ - - -- _- _ _-, - -_ -_- /� _ . A. MAINTAIN BOTTOM OF DUCT AND EQUPMDIT ELEVATIONS AS HIGH AS l;! PROVIDE RA BOOT FOR ALL RETURN GRILLES. SEE 7/M3.1. PROVIDE SERVICE AND M.SMDEMANCE CLEARANCE (2)__ �• POSSIBLE BUT NO LOWDR ABOVE FINISHED FLOOR THAN DUSTING REQUIRED BY CAE AND AS RECOMMENDED BY MiMt#"i ci, MAIN DUCT ELEVATION. Q PROVIDE 109 DUCT AND TERMINATE OPEN END ABOVE TRANSFORMER O 5' AFF. DO TON Of era JO15TS AND RUN SUPPLY DUCTS TROUGH BA O. FON CINDTY A SINGLE LINE HAS BEEN USED TO REPRESENT O SEE OCTAL 5/M3.1. TYPICAL FOR ALL FAN POWERED BOXES. 0 PROVIDE SERVICE AND MAINTETWICE CLEARAIJLE ON (3) THREE MULTIPLE REFRiGERA. PIPES ON THIS DRAWING. ACRIAL PIP REQUIRED BY CODE AS RECOMMENDED BY MANUFACTURER. _.... __. ..... ._...... .,.- .....�.,....,rn n•.mu,e c.oe cnu.es: m ..._ _.. ___r.. _- _.__..�. ...