TEST, ADJUST, BALANCE REPORT
FOR
Project: H &M US220 @ Washington Square
Location: Tigard, Oregon
Engineer: HBK Consultants
HVAC Contractor: Pace Heating & AC
— E 11
NEBB Cert #3177
NI mil 7?) LoP
PO . Box 653 • Beaverton, OR 97075. • ARA@ABA[nc.OS • 15031297 =6594 • 15031292 -4825 fax
A B A Table of Contents
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Page #
Table of Contents 1
Certification 2
Terms and Abbreviations 3
Instrument Calibration 4
General Remarks and Summaries 5
Fan Test Reports 6
Air Outlet Test Reports 16
Indexed Floor Plans
A
Accurate Balancing Agency, Inc. Page 1 of 23 Supervisor: Edward M. May Jr.
4
A B A Certification
Project Location: H &M US220 @ Washington Square - Tigard, Oregon
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the NEBB
Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems.
Any variances from design quantities, which exceed NEBB tolerances, are noted in the
Test - Adjust - Balance Report Project Summary.
Significant or noteworthy remarks are noted on the General Remarks or on individual
test reports.
Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this
report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any
descrepancies, ambiguities, or omissions found in this report will be retested, adjusted,
or balanced as needed. A written notification will be required.
Submitted and Certified by
NEBB TAB Firm: Accurate Balancing Agency, lnc.
Certification: 3177
Expiration Date: March 31, 2011
Certification Date: February 4, 2011
Signed and Sealed by
NEBB Supervisor: Edward M. May Jr.
Ce) z afCin . �•
E o B
Q .
eL MAP, 7( AY,.J 4
n
/ C "1 ICATION
3177
f Exp. 3/31/11
co
rOMC
Accurate Balancing Agency, Inc. Page 2 of 23 Supervisor: Edward M. May Jr.
A B A Terms and Abbreviations
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
AC Air Conditioning Unit
AH Air Handler
AHU Air Handling Unit
BHP Brake Horsepower
BMS Building Management System
BTUH British Thermal Units per Hour
CEF Ceiling Exhaust Fan
CFM Cubic Feet per Minute
CRU Computer Room Unit
DB Dry Bulb
DDC Direct Digital Control
EAT Entering Air Temperature
EWT Entering Water Temperature
EF Exhaust Fan
EG Exhaust Grille (Shown as Triangled number on indexed plans)
ERU Energy Recovery Unit
FPB Fan Powered Box (Terminal Unit which incorporates a fan)
FSD Fire / Smoke Damper
GPM Gallons per Minute
Head Pressure Difference across the entering and leaving side of a pump
HRU Heat Recovery Unit
HVAC Heating Ventilation and Air Conditioning
HZ Hertz
Inches( ") Inches of water gauge
K Correction factor to the free area needed to calculate CFM
LAT Leaving Air Temperature
LWT Leaving Water Temperature
N/A Not Applicable
N/L Note Listed
OBD Opposed Blade Damper
OAD Outside Air Damper
OD Outside Diameter
OSA Outside Air Damper
PSI Pounds per Square Inch
RA Return Air
RG Return Grille (Shown as a Circled number on indexed plans)
RPM Revolutions Per Minute
RTU Roof Top Unit
SA Supply Air
SG Supply Grille (Shown as a Standard number on indexed plans)
SFA Service Factor Amperage
TAB Test; Adjust; and Balance
VAV Variable Air Volume (Terminal Unit which regulates airflow)
VEL Velocity
WB Web Bulb
Accurate Balancing Agency, Inc. Page 3 of 23 Supervisor: Edward M. May Jr.
A B A Instrument Calibration Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Instrument Manufacturer I Model # I Serial # j Calibrated J Cal. Due I
Type
Tachometer UEI I DPM5 I L420478 I 10/14/2010 I 10/14/2011
Rotation
Thermometer UEI 550B I 021109675 I 10/14/2010 I 10/14/2011
Immersion
Thermometer UEI I 550B I 090502268 I 10/14/2010 I 10/14/2011
Air Temp
Electrical UEI I DL389 I 90501731 I 10/14/2010 I 10/14/2011 I
Multimeter
Manometer Shortridge I ADM -860 I M03371 I 10/13/2010 I 10/13/2011
Air Pressure
Hygro- Thermometer Extech I RH490 1 10052806 I 9/30/2010 I 9/30/2011
Humidity
Anemometer UEI I DAFM2 I 900501731 I 10/14/2010 I 10/14/2011
Air Velocity
Flowhood Shortridge I ADM -860 1 M03371 I 10/13/2010 I 10/13/2011 I
Air Volume
Thermometer UEI I ATT47 probe I 90501731 I 10/14/2010 I 10/14/2011 I
Contact
Hydrometer Alnor / TSI I HM680 I 70552165 I 11/9/2010 I 11/9/2011
Differential Pressure
I I I I I
Accurate Balancing Agency, Inc. Page 4 of 23 Supervisor: Edward M. May Jr.
A ;B A General Remarks and Summary
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
1) Rooftop units were tested for cooling supply temperatures as follows:
RTU -1 49.5 degrees
RTU -2 47.6 degrees
RTU -3 49.7 degrees
RTU-4 45.6 degrees
RTU -5 53.0 degrees
RTU -6 53.3 degrees
RTU -7 50.8 degrees
2) Rooftop units were tested for heating supply temperatures as follows:
RTU -1 82.5 degrees
RTU -2 82.3 degrees
RTU -3 97.2 degrees
RTU-4 95.5 degrees
RTU -5 87.3 degrees
RTU -6 85.4 degrees
RTU -7 80.8 degrees
3) Rooftop unit powered exhaust fans were tested for total airflow at 100% OSA as follows:
RTU -1 2030 CFM
RTU -2 2220 CFM
RTU -3 2160 CFM
RTU-4 2110 CFM
RTU -5 2250 CFM
RTU-6 2210 CFM
RTU -7 2375 CFM
4) Outside air temperature was tested as follows:
Dry Bulb 45.3 degrees
Wet Bulb 44.0 degrees
5) Economizer settings of rooftop units were obtained as follows:
RTU -1 D
RTU -2 C
RTU -3 D
RTU-4 D
RTU -5 C
RTU -6 C
RTU -7 D
6) EF -1 through EF -3 are direct drive fans set by speed controller.
Accurate Balancing Agency, Inc. Page 5 of 23 Supervisor: Edward M. May Jr.
A B A Air Handling Unit Test Report
(Packaged / Belted)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data I
Unit Designation RTU -1
Service First Level
Manufacturer Trane
Model Number WSC072L4RGA
Serial Number 103211183L
Test Data
Item Design Actual
Total Supply Airflow (CFM Design / Outlet) 2400 /2800 2920
External Static Pressure (Inches water gauge) Not Listed 0.67"
Total Return Airflow (CFM) 2220 2337
Minimum Outside Air (CFM) 580 583
Motor Horsepower 2.0
Motor Manufacturer Marathon
Motor Frame 145T
Motor Service Factor 1.15
Full Load Amperage (Ti / T2 / T3) 3.1 3.0/3.1/3.0
Voltage (T1 -T2 / Ti -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Motor (RPM) I 1725 I 1732
Fan (RPM) Not Listed 899
Motor Sheave 1 VL40x7/8"
Fan Pulley AK59Hx 1 "
Belt (Number) Size (1) AX29
Sheave Centerline Distance 8.5"
Static Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan -0.47" +0.43" 0.90"
Coil / Filter - 0.24" - 0.47" 0.23"
Remarks: I
I
Accurate Balancing Agency, Inc. Page 6 of 23 Supervisor: Edward M. May Jr.
A B; A Air Handling Unit Test Report
(Packaged / Belted)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data I
Unit Designation RTU -2
Service First Level
Manufacturer Trane
Model Number WSC072E4RGA
Serial Number 103211173L
Test Data I
Item . Design Actual
Total Supply Airflow (CFM Design / Outlet) 2400 /2800 2930
External Static Pressure (Inches water gauge) Not Listed 0.67"
Total Return Airflow (CFM) 2220 2343
Minimum Outside Air (CFM) 580 587
Motor Horsepower 2.0
Motor Manufacturer Marathon
Motor Frame 145T
Motor Service Factor 1.15
Full Load Amperage (T1 / T2 / T3) 3.1 3.0/3.0/3.1
Voltage (T1 -T2 / Ti -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Motor (RPM) 1725 I 1772
Fan (RPM) Not Listed 901
Motor Sheave 1 VL40x7/8"
Fan Pulley AK56Hx1"
Belt (Number) Size (1) AX28
Sheave Centerline Distance 8.5"
Static Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan -0.47" +0.43" 0.90"
Coil / Filter - 0.24" - 0.47" 0.23"
Remarks: I
u
Accurate Balancing Agency, Inc. Page 7 of 23 Supervisor: Edward M. May Jr.
A B A Air Handling Unit Test Report
(Packaged / Belted)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data I
Unit Designation RTU -3
Service First Level
Manufacturer Trane
Model Number WSC090E4RGA
Serial Number 103211083L
Test Data
Item Design Actual
Total Supply Airflow (CFM Design / Outlet) 3000 / 3280 3415
External Static Pressure (Inches water gauge) Not Listed 0.90"
Total Return Airflow (CFM) 2590 2722
Minimum Outside Air (CFM) 690 693
Motor Horsepower 3.0
Motor Manufacturer GE
Motor Frame 56Hz
Motor Service Factor 1.15
Full Load Amperage (T1 / T2 / T3) 4.6 2.8/2.9/3.1
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Motor (RPM) I 1725 I 1765
Fan (RPM) Not Listed 788
Motor Sheave 1 VL34x7/8"
Fan Pulley AK74Hx1"
Belt (Number) Size (1) AX37
Sheave Centerline Distance 10.5"
Static Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan - 0.49" +0.58" 1.07"
Coil / Filter - 0.32" - 0.42" 0.10"
Remarks: I
Accurate Balancing Agency, Inc. Page 8 of 23 Supervisor: Edward M. May Jr.
A 'B A Air Handling Unit Test Report
(Packaged / Belted)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/201 I
Submittal Data I
Unit Designation RTU-4
Service Second Level
Manufacturer Trane
Model Number WSC090E4RGA
Serial Number 10321 1073L
Test Data I
Item Design Actual
Total Supply Airflow (CFM Design / Outlet) 3000 / 3280 3145
External Static Pressure (Inches water gauge) Not Listed 0.42"
Total Return Airflow (CFM) 2920 2783
Minimum Outside Air (CFM) 360 362
Motor Horsepower 3.0
Motor Manufacturer GE
Motor Frame 56Hz
Motor Service Factor 1.15
Full Load Amperage (T1 / T2 / T3) 4.6 2.5/2.6/2.6
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Motor (RPM) 1725 1774
Fan (RPM) Not Listed 629
Motor Sheave 1 VL44x7/8"
Fan Pulley AK94Hx 1 "
Belt (Number) Size (1) AX40
Sheave Centerline Distance 11.0"
Static Pressure. Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan - 0.32" +0.26" 0.58"
Coil / Filter - 0.16" - 0.32" 0.16"
Remarks: _ I
Accurate Balancing Agency, Inc. Page 9 of 23 Supervisor: Edward M. May Jr.
A B A Air Handling Unit Test Report
(Packaged / Direct Drive)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data I
Unit Designation RTU -5
Service Mezzanine Level
Manufacturer Trane
Model Number WSC120E4RKA
Serial Number 103211231L
Test Data ' I
Item Design . Actual
Total Supply Airflow (CFM Design / Outlet) 4000 / 4500 4615
External Static Pressure (Inches water gauge) Not Listed 0.84"
Total Return Airflow (CFM) 3820 3929
Minimum Outside Air (CFM) 680 686
Motor Horsepower 3.6
Motor Manufacturer Not Listed
' Motor Frame Not Listed
Motor Service Factor 1.0
Full Load Amperage (Ti / T2 / T3) 4.3 2.0/2.1/2.1
Voltage (T1 -T2 / Ti -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Speed Setting Potentiometer
Fan (RPM) N/A N/A
Static. Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan - 0.61" +0.35" 0.96"
Coil / Filter - 0.49" - 0.61" 0.12"
Remarks: I
Accurate Balancing Agency, Inc. Page 10 of 23 Supervisor: Edward M. May Jr.
A B A Air Handling Unit Test Report
(Packaged / Direct Drive)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data I
Unit Designation RTU -6
Service Mezzanine Level
Manufacturer Trane
Model Number WSCl20R4RKA
Serial Number 103211217L
Test Data I
. Item` Design Actual
Total Supply Airflow (CFM Design / Outlet) 4000 / 4500 4710
External Static Pressure (Inches water gauge) Not Listed 0.77"
Total Return Airflow (CFM) 3820 4020
Minimum Outside Air (CFM) 680 690
Motor Horsepower 3.6
Motor Manufacturer Not Listed
Motor Frame Not Listed
Motor Service Factor 1.0
Full Load Amperage (T1 / T2 / T3) 4.3 2.0/2.1/1.9
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Speed Setting
Fan (RPM) N/A N/A
Static Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan - 0.58" +0.32" 0.90"
Coil / Filter - 0.45" -0.58" 0.13"
Remarks: I
1
Accurate Balancing Agency, Inc. Page 11 of 23 Supervisor: Edward M. May Jr.
A B, A Air Handling Unit Test Report
(Packaged / Belted)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/27/2011
Submittal Data 1
Unit Designation RTU -7
Service Mezzanine Level
Manufacturer Trane
Model Number WSC072E4RGA
Serial Number 103211193L
Test Data I
Item Design Actual
Total Supply Airflow (CFM Design / Outlet) 2400 / 2800 2895
External Static Pressure (Inches water gauge) Not Listed 0.34"
Total Return Airflow (CFM) 2370 2461
Minimum Outside Air (CFM) 430 434
Motor Horsepower 2.0
Motor Manufacturer Marathon
Motor Frame 145T
Motor Service Factor 1.15
Full Load Amperage (T1 / T2 / T3) 3.1 3.1/3.0/3.0
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 460 -3 -60 479/482/482
Operating Hz. 60 60
Motor (RPM) 1725 1776
Fan (RPM) Not Listed 791
Motor Sheave 1 VL40x7/8"
Fan Pulley AK64Hx1"
Belt (Number) Size (1) AX32
Sheave Centerline Distance 10.0"
Static Pressure Profile I
Component In (Suction SP) Out (Discharge SP) Differential Pressure
Fan - 0.40" +0.19" 0.59"
Coil / Filter - 0.15" - 0.40" 0.25"
Remarks: ' I
Accurate Balancing Agency, Inc. Page 12 of 23 Supervisor: Edward M. May Jr.
•
A B A Fan Test Report
(Direct Drive)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/25/2011
Submittal Data
Unit Designation EF -1
Service Janitor / Restrooms
Manufacturer Greenheck
Model Number G- 076 -D -X
Serial Number 12290160-1011
Test -Data -I
Item Design' Actual
Total Airflow (CFM Design / Outlet) 200 / 200 200
Total Static Pressure (Inches water gauge) 0.375" N/A
Motor Horsepower 1/25
Motor Manufacturer Fasco
Motor Frame Not Listed
Motor Service Factor 1.0
Full Load Amperage (T1 / T2 / T3) 1.3 1.1
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 115 -1 -60 121 -1 -60
Operating Hz. 60 60
Speed Setting - Speed Controller
Fan (RPM) N/A N/A
Static Pressure Profile I
Component In (Suction SP) Out (Discharge, SP) Differential Pressure
Fan N/A N/A N/A
, Remarks: I
Fan was set with speed controller.
Accurate Balancing Agency, Inc. Page 13 of 23 Supervisor: Edward M. May Jr.
A B A Fan Test Report
(Direct Drive)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/25/201 I
Submittal Data I
Unit Designation EF -2
Service Electrical Room
Manufacturer Greenheck
Model Number CSP- A1410 -QD
Serial Number 12255634 -1011
Test Data
Item Design Actual
Total Airflow (CFM Design / Outlet) 1245 / 1245 1250
Total Static Pressure (Inches water gauge) 0.50" N/A
Motor Horsepower Not Listed
Motor Manufacturer Not Listed
Motor Frame Not Listed
Motor Service Factor 1.0
Full Load Amperage (T1 / T2 / T3) Not Listed 7.4
Voltage (T1 -T2 / T1 -T3 / T2 -T3) 115 -1 -60 121 -1 -60
Operating Hz. 60 60
Speed Setting Speed Controller
Fan (RPM) N/A N/A
- Static Pressure Profile I
Component _"In (Suction SP) - Out. (Discharge. SP) Differential Pressure
Fan N/A N/A N/A
Remarks: I
Fan was set with speed controller.
Accurate Balancing Agency, Inc. Page 14 of 23 Supervisor: Edward M. May Jr.
A B A Fan Test Report
(Direct Drive)
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/25/2011
Submittal Data I
Unit Designation EF -3
Service LAN Room
Manufacturer Greenheck
Model Number CSP- A700 -QD
Serial Number 12281377 -1011
Test; Data = I
Item Design Actual
Total Airflow (CFM Design / Outlet) 600 / 600 625
Total Static Pressure (Inches water gauge) 0.50" N/A
Motor Horsepower Not Listed
Motor Manufacturer Not Listed
Motor Frame Not Listed
Motor Service Factor 1.0
Full Load Amperage (Ti / T2 / T3) Not Listed 3.6
Voltage (T1 -T2 / Tl -T3 / T2 -T3) 115 -1 -60 121 -1 -60
Operating Hz. 60 60
Speed Setting Speed Controller
Fan (RPM) N/A N/A
Static. Pressure Profile I
•
Component In (Suction SP) Out (DischargeSP) Differential Pressure
Fan N/A N/A N/A
Remarks: I
Fan was set with speed controller.
Accurate Balancing Agency, Inc. Page 15 of 23 Supervisor: Edward M. May Jr.
A 8 A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
System • / link' Design Preliminary Final Test
Area Served #, Size Type _ AK VEL CFM VEL CFM VEL CFM
RTU - Supply
Womens Sales 1 l0 "R SG 1.00 330 330 440 440 345 345 105%
Womens Sales 2 10'R SG 1.00 340 340 470 470 355 355 104%
Womens Sales 3 12"R SG 1.00 430 430 590 590 450 450 105%
Womens Sales 4 12 "R SG 1.00 430 430 560 560 450 450 105%
Womens Sales 5 10 "R SG 1.00 330 330 450 450 345 345 105%
Womens Sales 6 10 "R SG 1.00 340 340 460 460 355 355 104%
Fitting Rooms 7 8"R SG 1.00 200 200 350 350 210 210 105%
Fitting Rooms 8 8 "R SG 1.00 200 200 300 300 200 200 100%
Fitting Rooms 9 8 "R SG 1.00 200 200 320 320 210 210 105%
Total 2800 3940 2920 104%
RTU -1 Return 1 Total SA -OA 1.00 2220 2220 2337 2337 2337 2337 105%
Plenum Total 2220 2337 2337 105%
RTU - 1 36x15 Inlet 3.81 152 580 153 583 153 583 101%
Outside Air Total - 580 583 583 101'%
Remarks:
Accurate Balancing Agency, Inc. Page 16 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
Design Preliminary
System';% °Unit �� 9 �'Y Final Test
Area Served, # Size Type AK VEL CFM VEL CFM VEL CFM
RTU -2 Supply
Womens Sales 1 12 "R SG 1.00 470 470 720 720 495 495 105%
Womens Sales 2 12 "R SG 1.00 465 465 535 535 485 485 104%
Womens Sales 3 12 "R SG 1.00 465 465 520 520 485 485 104%
Womens Sales 4 12 "R SG 1.00 470 470 605 605 495 495 105%
Womens Sales 5 12 "R SG 1.00 465 465 600 600 485 485 104%
Womens Sales 6 12 "R SG 1.00 465 465 665 665 485 485 104%
Total 2800 3645 2930 105%
RTU -2 Return 1 Total SA -OA 1.00 2220 2220 2343 2343 2343 2343 106%
Plenum Total 2220 2343 2343 106%
RTU -2 1 36x15 Inlet 3.81 152 580 154 587 154 587 101%
Outside Air Total - 580 587 587 101%
Remarks: • I
Accurate Balancing Agency, Inc. Page 17 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
System] . 'Unlit • ,Design- Preliminary Final Test_
Area-Served - # S ize Type AK VEL CFM VEL CFM VEL CFM ?/o
RTU -3 Supply
Womens Sales 1 12 "R SG 1.00 480 480 600 600 500 500 104%
Womens Sales 2 12 "R SG 1.00 460 460 580 580 480 480 104%
Womens Sales 3 12 "R SG 1.00 480 480 575 575 495 495 103%
Womens Sales 4 12 "R SG 1.00 470 470 595 595 490 490 104%
Womens Sales 5 12 "R SG 1.00 460 460 560 560 485 485 105%
Womens Sales 6 12 "R SG 1.00 460 460 555 555 475 475 103%
Womens Sales 7 12 "R SG 1.00 470 470 550 550 490 490 104%
Total 3280 4015 3415 104%
RTU -3 Return 1 Total SA -OA 1.00 2590 2590 2722 2722 2722 2722 105%
Plenum Total - 2590 2722 2722 105%
RTU -3 1 36x15 Inlet 3.81 181 690 182 693 182 693 100%
Outside Air Total 690 `693 693 100%
Remarks: ,
Accurate Balancing Agency, Inc. Page 18 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
System %'Unit" Design Preliminary Final Test
,Area Served. "# Size Type AK VEL CFM VEL CFM VEL CFM
RTU-4 Supply
Lounge 1 12 "R SG 1.00 470 470 880 880 450 450 96%
Meeting 2 10 "R SG 1.00 330 330 405 405 315 315 95%
Hall 3 8 "R SG 1.00 100 100 270 270 95 95 95%
Administration 4 10 "R SG 1.00 260 260 385 385 250 250 96%
LAN Room 5 8 "R SG 1.00 150 150 330 330 145 145 97%
Hardware 6 6 "R SG 1.00 50 50 120 120 50 50 100%
Processing 7 12 "R SG 1.00 450 450 640 640 430 430 96%
Electrical 8 12 "R SG 1.00 370 370 605 605 355 355 96%
Electrical 9 10'R SG 1.00 300 300 390 390 290 290 97%
Electrical 10 12 "R SG 1.00 450 450 645 645 430 430 96%
Electrical 11 10 "R SG 1.00 350 350 400 400 335 335 96%
Total 3280. 5070 3145 =96%
RTU-4 Return 1 Total SA -OA 1.00 2920 2920 2783 2783 2783 2783 95%
Plenum Toial 2920 2783 2783 95%
RTU-4 1 36x15 Inlet 3.81 94 360 95 362 95 362 101%
Outside Air Total 360 362 362 101%
Remarks: I
Accurate Balancing Agency, Inc. Page 19 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
system % Unit Design Preliminary, Final Test
Area Served # Size Type AK VEL CFM VEL CFM VEL CFM
RTU - Supply
Mens Sales 1 12 "R SG 1.00 480 480 460 460 495 495 103%
Mens Sales 2 12 "R SG 1.00 425 425 380 380 420 420 99%
Mens Sales 3 12 "R SG 1.00 480 480 435 435 490 490 102%
Mens Sales 4 12 "R SG 1.00 480 480 510 510 495 495 103%
Mens Sales 5 12 "R SG 1.00 480 480 490 490 505 505 105%
Mens Sales 6 12 "R SG 1.00 390 390 505 505 400 400 103%
Mens Sales 7 12 "R SG 1.00 390 390 545 545 395 395 101%
Kids & Baby 8 10 "R SG 1.00 325 325 295 295 330 330 102%
Kids & Baby 9 10 "R SG 1.00 325 325 280 280 335 335 103%
Kids & Baby 10 10 "R SG 1.00 325 325 340 340 340 340 105%
Kids & Baby 11 8 "R SG 1.00 150 150 185 185 160 160 107%
Kids & Baby 12 10 "R SG 1.00 250 250 345 345 250 250 100%
Total 4500 - 4770 - 4615 103%
RTU -5 Return 1 Total SA -OA 1.00 3820 3820 3929 3929 3929 3929 103%
Plenum Total . 3820 - 3929 :. - 3929 103- %
RTU -5 1 36x15 Inlet 3.81 178 680 180 686 180 686 101%
Outside Air Total 680 686 - 686 -101%
Remarks; I
Accurate Balancing Agency, Inc. Page 20 of 23 Supervisor: Edward M. May Jr.
A ,B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
System/ Unit '
Area Served # Size Type AK
RTU -6 Supply
Mens Sales 1 8 "R SG 1.00 110 110 270 270 115 115 105%
Mens Sales 2 12 "R SG 1.00 470 470 550 550 490 490 104%
Mens Sales 3 12 "R SG 1.00 470 470 495 495 490 490 104%
Mens Sales 4 12 "R SG 1.00 380 380 485 485 11 400 105%
Mens Sales 5 12 "R SG 1.00 3N 380 545 545 395 • 104%
Mens Sales 6 12 "R SG 1.00 400 1 4 11 500 500 415 415 104%
Mens Sales 7 12 "R SG 1.00 470 470 330 330 495 495 105%
Mens Sales 8 12 "R SG 1.00 470 470 300 300 490 490 104%
Mens Sales 9 12 "R SG 1.00 3N 3N 430 430 400 400 105%
Mens Sales 10 12 "R SG 1.00 380 3N 445 445 400 400 105%
Mens Sales 11 12 "R SG 1.00 400 400 360 360 420 420 105%
Display Window 12 8 "R SG 1.00 110 110 140 140 115 115 105%
Display Window 13 I 6 "R SG 1.00 I 80 I 80 I 80 I 80 I 85 I 85 1 106%
Total 4500 4930 4710 105%
RTU -6 Return 1 Total SA -OA 1.00 3810 3810 4020 4020 4020 4020 106%
Plenum Total 3810 4020 4020 106%
RTU -6 1 36x15 Inlet 3.81 181 690 181 690 181 690 100%
Outside Air Total 690 690 690 100%
Remarks:
Accurate Balancing Agency, Inc. Page 21 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
° System / Unit Design Preliminary Final Test
-Area Served # Size Type AK. VEL CFM VEL CFM VEL CFM
RTU -7 Supply
Kids & Baby 1 10 "R SG 1.00 325 325 450 450 340 340 105%
Kids & Baby 2 10 "R SG 1.00 325 325 525 525 340 340 105%
Kids & Baby 3 10'R SG 1.00 325 325 560 560 335 335 103%
Mens Sales 4 10 "R SG 1.00 425 425 610 610 445 445 105%
Kids & Baby 5 10 "R SG 1.00 350 350 560 560 365 365 104%
Kids & Baby 6 10 "R SG 1.00 350 350 460 460 355 355 101%
Kids & Baby 7 10 "R SG 1.00 350 350 565 565 360 360 103%
Kids & Baby 8 10 "R SG 1.00 350 350 520 520 355 355 101%
Total 2800 4250 .2895 103%
RTU -7 Return 1 Total SA -OA 1.00 2370 2370 2461 2461 2461 2461 104%
Plenum Total 2370, 2461 2461 104%
RTU -7 1 36x15 Inlet 3.81 113 430 114 434 114 434 101%
Outside Air Total 430 434 434 101%
Remarks:
•
Accurate Balancing Agency, Inc. Page 22 of 23 Supervisor: Edward M. May Jr.
A B A Air Outlet Test Report
Project - Location: H &M US220 @ Washington Square - Tigard, Oregon
Technician: AP Test Date: 1/26/2011
',,- System: /y Unit° Design Preliminary Final Test
Area Seared #. -_ Size ' Type AK VEL CFM VEL I CFM VEL CFM
EF -1
Janitor 1 6 "R SG 1.00 50 50 30 30 50 50 100%
Restroom 2 6 "R SG 1.00 75 75 80 80 75 75 100%
Restroom 3 6 "R SG 1.00 75 75 100 100 75 75 100%
Total - 200 210 200 100%
EF -2 1 CEF EG 1.00 1245 1245 1250 1250 1250 1250 100%
Electrical Room Total 1245 . 1250 1250 100%
EF -3 1 CEF EG 1.00 600 600 625 625 625 625 104%
LAN Room Total 600 625: _ 625 104%
Remarks
EF -1 through EF -3 are direct drive fans set by speed controller.
Accurate Balancing Agency, Inc. Page 23 of 23 Supervisor: Edward M. May Jr.,