Report jciP '2- -DD130
� p,'��N 11, TUALATIN VALLEY FIRE & RESCUE
��P. F13' , ��'4 AND
/'-Qi ?' BEAVERTON FIRE DEPARTMENT
`VC J FIRE MARSHALS OFFICE
A >,, 9 I-2-1 „ G # (503) 526 -2469 POSTED:
F &MS
OCCUPANT p, , Co 15 /15 T.-) 'FE R C.. itJL� c•G'°
CONTRACTOR )4 L (yep -&) BLDG. PERMIT 0 '
PROJECT NAME ' a h tg 6 /6 r 1 72 h d a'(/t-e . PLAN REVIEW 0
LOCATION J 6 655 . a i a •
JURISDICTION: 1= Be. 2= Du. 3= K.C. 4=110 5= Tu. 6= Sh. 7= Wi. 8= CC 9= WC 0= MC
COVER 4801 SPECIAL FOLLOW- UP /REINSPECTION ATTEMPTED FINAL
0 Framing 0 Separation Walls 0 Sprinkler System •
0 Shaft Fire Dampers . (Overhead /Underground)
E -
• V Alarm System 0 Hood' Extng Sy 0 Conference
Ni
ENSpr-ay- Booth U Ceiling Cover 0 Other
- ffie0J-1, 5 4r-P - iLli/p0:7)■/-1 - -
V/ i, J s c4 A - /- A -(1( ------
Li G U W I I / .
•
7
•
Date: 'g 6' (-?. Inspector: 44,,t,f1(1/?-i-
ha/ 5729'792
v N. ...41 q`,,.,
J . .� #1, TUALATIN VALLEY FIRE & RESCUE
' �aljt AND
��
,:.,:,,e zf ' : t f., BEAVERTON FIRE DEPARTMENT
, J
�R u a G 4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, OR 97076 • (503) 526 -2469 • FAX 526 -2538
&REST,;'
April 24, 1992
Mackenzie /Saito & Associates
P.O. Box 69039
Portland, Oregon 97201 -0039
Re: Pactrust Business Center Building 168
-1-6-54-0 S.W. 72nd
/ "'`� `" 6290B- 190 -000 -
Gentlemen:
This is a Fire and Life Safety Plan Review and is based on the
1988 editions of the Uniform Fire Code (UFC) and those sections
of the Uniform Building Code (UBC) and Uniform Mechanical Code
(UMC) specifically referencing the fire department, and other
local ordinances and regulations.
Plans submitted for the above captioned project are
conditionally approved subject to the City of Tigard Building
Department requirements and the following items:
1. Automatic Sprinkler Plans: Plans referred to and examined
by this office contain no provisions for the alteration or
installation of automatic sprinkler system. Not less than
three sets of plans for the installation shall be
submitted to this office for approval prior to
installation. UBC 302(b)
2. Address Required: The tenant space number must be
prominently displayed on the street front where it is
readily visible to drivers and officers of responding fire
apparatus and other emergency vehicles. UFC Sec. 10.208
3. Fire Extinguisher Requirements: Not less than one (1)
approved fire extinguisher(s) with a rating of not less
than ( *) shall be provided for each ( * *) square foot of
floor area or fraction thereof. The travel distance to an
extinguisher from any portion of the building shall not
exceed 75 feet. UFC Sec. 10.303
"Working" Smoke Detectors Save Lives
Mackenzie /Saito & Associates
April 23, 1992
Page 2
( *) 2A10B:C, - Light and Ordinary Hazard
4A10B:C - Extra Hazard
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
Note: Where flammable or combustible liquids are
used, "B" ratings of extinguishers may need to be
higher and travel distances shorter. See
requirements in National Fire Protection Association
Standard 10 -1.
4. Approved Plans on Job Site: One set of approved plans
bearing the stamps of the building department issuing the
construction permit and this office must be maintained on
the project site throughout all phases of construction and
must be made available to building and fire inspectors for
reference during required construction inspections. UBC
Sec. 303
5. Required Occupancy Certificate: Prior to the use and
occupancy of the project (space), a certificate of
occupancy or other written instrument of approval must be
obtained from the building department issuing the
construction permit. UBC Sec. 307
Approval of submitted plans is not an approval of omissions or
oversights by this office or of non - compliance with any
applicable regulations of local government.
If I can be of any further assistance to you, please feel free
to contact me at 526 -2502.
Sincerely,
RIO 0
Gene Birchill
Deputy Fire Marshal
GB:kw
cc: Tigard Building Department ✓_
H.L. Green