Plans Dos o5 zos
February 2, 2005 c4'.-
CITY OF TIGARD
OREGON
Hydro Tech Fire Protection Inc.
Joshua Smith
P.O. Box 40
Brush Prairie, WA 98606
RE: OAK TREE APARTMENTS BUILDINGS A, B, C, D, and E, FIRE SPRINKLER SYSTEM
Project Information
Building Permit: BUP2005 -00018 1 t � 2. ' 7' I Construction Type: NA
Tenant Name: Oak Tree Apartthents Occupancy Type: R -1
Address: 16005 SW 108 Ave. Occupant Load: NA
Area: NA Stories: 3
Hazard: Ordinary Group Commodity: NA
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998
edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The
submitted plans are approved subject to the following.
FLUSHING
The fire service mains shall be completely flushed before connection is made to the sprinkler piping.
The flow rate shall not be less than the hydraulically calculated water demand of the system including
any hose requirements. Standard 9 -1, section 8 -2.1 OSSC
HYDROSTATIC TESTING
All interior piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without
loss for 2 hours. The test pressure shall be read from a gauge located at the low elevation point of the
system or portion being tested. Standard 9 -1, section 8 -2.2.1 OSSC.
GENERAL
1. A key box shall be installed within 20 feet of the riser room entrance. The bottom of the key
box shall be not less than 8 feet nor more than 10 feet above the walking surface unless
approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for key box at 503- 612 -7010.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any
sprinklers that have operated or been damaged in any way can be promptly replaced. These
sprinklers shall correspond to the types and temperature ratings of the sprinklers in the
property. Standard 9 -1, section 2 -2.7.1 OSSC
3. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare
sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2
OSSC
4. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler
deflectors. The distance shall be increased to 36 inches for large drop sprinkler heads. Standard
9 -1, section 4 -4.1.6 and 4 -4.3.2 OSSC
5. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4 inches from
walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC
• 6. Clearances shall be provided around all piping extending through walls, floors, platforms and
foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2 inches shall be not less than
1 inch. Standard 9 -1, section 4- 5.4.3.4
7. Monitoring, Section 904.3.1 OSSC. All valves controlling the water supply for automatic
sprinkler systems and all water flow monitoring devices shall be electrically monitored where
the number of sprinklers are;
• Twenty or more in group I, Divisions 1.1 and 1.2 Occupancies.
• One hundred or more in all other occupancies.
8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an
approved location. An approved audible sprinkler flow alarm to alert the occupants shall be
provided in the interior of the building in a normally occupied location. 904.3.2 OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout
all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the enclosed City
of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectfu ,
Val Henzel,
Senior Plans Examiner
RECE I VrEDev B co
CD
Model F1 JAN 9 2005
W
, Residentia�I : S IN G D '� - ' •N
BULL to
Model Fl Res Sprinlders engineered for the lowest flows •
to meet the minimum design density of .05 gpm/ft
Types: ,<
1. F1 Res 49 Pendent
2. F1 Res 49 Recessed Pendent /F 1 vv.>
3. F1 Res 49 Recessed Pendent /FP .-
4. F1 Res 49 CCP Pendent ,
F1 Res 49 Recessed Fl Res 49 Recessed
5. F1 Res 44 HSW �\ Pendent / F1 Pendent / FP
6. F1 Res 44 Recessed HSW /F2 0
7. F1 Res 40 HSW O t
8. F1 Res 40 Recessed HSW /F2 0
;; : :;:.
Listings & Approvals
1 js k
1. Listed by Underwriters Laboratories Inc. and'`
UL Certified for Canada (cULus) 1
I
2. NYC MEA 258 -93 -E Cs
UL Listing Category F1 Res 49 CCP Fl Res 44 Recessed
Residential Automatic Sprinkler Pendent HSW/F2
- UL Guide Number
; <
VKKW .
Patents
US Patent No 6,516,893 applies to the a:. <
Model F1 Res 49 Pendent Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are Fl Res 40 Recessed
fast response sprinklers combining excellent durability, HSW/F2
high sensitivity glass -bulb and low profile decorative Application
design. The Fl Res Horizontal Sidewall sprinklers (Figs. pp
5 & 6) are equally attractive when above ceiling piping Model Fl Res Sprinklers are used for Residential Are
cannot be used. Protection according to UL 1626 Standard *. Be sure
The 3mm glass -bulb pendent sprinklers, with a that orifice size, temperature rating, deflector style and
K- Factor of 4.9, permit the efficient use of residential sprinkler type are in accordance with the latest
water supplies for sprinkler coverage in residential fire published standards of The National Fire Protection
protection design. Association or the approving authority having
The low flow Fl Res sprinklers are specially Jurisdiction.
engineered for fast thermal response to meet the Installation
sensitive fire protection application needs of the latest Models F1 Res sprinklers are to be installed as shown.
residential market standards (UL 1626 Standard *). Model F1, F2 and FP Escutcheons, illustrated herewith,
Upon fire conditions, rising heat causes a sprinkler's are the only recessed escutcheons to be used with
heat sensitive glass bulb to shatter, releasing the Model F1 Res sprinklers. Use of any other recessed
waterway for water flow onto the deflector, evenly escutcheon will void all approvals and warranties. For
distributing the discharged water to control a fire. installing Model Fl Res Pendent sprinklers use only the
Technical Data: Model D sprinkler Wrench; for installing Models Fl Res
• Thermal Sensor: Nominal 3mm glass -bulb Recessed Pendent & CCP sprinklers use only the
• Sprinkler Frame : Brass Casting Model GFR1 sprinkler wrench; for installing Model Fl
• Sprinklers' Pressure Rating : 175 psi Res Recessed HSW sprinklers use only the Model
Factory Hydrostatically Tested to 500 psi GFR1 Sprinkler Wrench. Use of wrenches other than
,� • •Thread Size: 1/2" NPT (R Y2) those specified may damage these sprinklers. Install F1
Res 44 and 40 HSW with a ceiling to deflector distance
• K- Factor: 4.9 (Actual) - Fl Res 49 Pendent Sprinkler
4.4 (Actual) - Fl Res 44 HSW Sprinkler of 4 , 12". Flow arrow on deflector must point away from
1, 4.0 (Actual) - Fl Res 40 HSW Sprinkler near wall and "Top" marking must face ceiling.
• Density: Minimum 0.05 gpm /ft * Effective date 7/12/02
ThP RPliahit Atrtnmatir_ SnrinkIPr ('n Inr North Marfl ipgten Parkway Mni int Varnnn Naw Ynrk1 n rr, 2
I
• Model F1 Res 49 Recessed r - a
• Model F1 Res 49 Pendent Pendent / F1
1
4 : : : , , , ....):' , .7.t
mar
} x
Fl escutcheon, /" (19mm) Fig. 1
adjustment
Technical Data: F1 Res 49 Pendent and Recessed Pendent
Escutcheon *, Fl or F2, Data:
Sprinkler Max. Face of fitting to
Thread TemP. Pressure Ambient Actual Sprinkler Type ceiling '
Size Rating Temp. (mm) Inch ) Inch (mm)
psi (bar) Factor Inch (mm) r
°F °C F C F1 34 (19.0) MMax. = in.= 3 /1 %,i ((38.1
19.1) /16 -15/6 (4.7 - 24.0)
"
%" NPT 155 68 175 (12) 100 38 4.9 2.25 (57) ) ��
(RX) 175 79 150 66 F2 X (12.7) Max _ = ." 1 38. 8 ) 33 8 - % (4.7 - 17.4) '
* Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49 Recessed Pendent Sprinkler
Deflector - to - ceiling
- Maximum 1" (25rTm) to 4" (100mm)
Max. Sprinkler Sprinkler
Spacing
Fl Press Identification
ft ( gPm ('Pm) Psi (�� Number Lm_
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48) wept. --. l
14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)
16 x 16 (4.9x4.9) 13 (49) 7.0 (0.48) R3516 i - -i
18 x 18 (5.5x5.5) 17 (64.3) 12.0 (0.83)
I 20x20 (6.1x6.1) 20 (75.7) 16.7 (1.14) - t -
.. r i , na o ro
N, m - aa�c u"�isow
*Deflector - to - ceiling -/i - Z
Maximum 4" (100mm) to 8" (203mm) "°""' I lip `- - - I 1 % / / / / /r. '
Max. Sprinkler Sprinkler } Spacing Fl Pressur identificati ft (m) gpm (Lpm) psi (bar) Number (SIN) � ' _ H _ ! %
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65) i
14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73) / , „
16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83) R3516
18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0)
20x20 (6.1x6.1) 21 (79.4) _ 20.2 (1.4)
* Note: The Fl Res 49 pendent and recessed pendent Fig. 2
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1 Maximum beam depth = 7" (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
2.
• Model Pendent F1 Res 4t9 CCP • Model Fl
Pendent Res 49 / Recessed
• J x f 4 F� •
Z
+
FP push -on /thread -off
escutcheon
1
2 M- n. 1e�A•• -1
2 5/8 [66.7mrq DA. MR[ N OE4/M6
2 5/16" OW. HOLE IN CEILING
2 '.{/16 OM
(58.7mmJ laam�!
CUP 2 `✓' / p,P
I ,I /T" REDUCE!? r L =_^__�
— 1 I r_ =_ _._ - =�
I l
CUP I I I • X !/7 ',ova' i-
l 1
l•r l ,
j �. — d � MAX. FACf OF FITTING
\ I
CEILING /
1 - -' I I � _
I TO FAC OF CEILING
,7 ,' DIMENSION
L, ;1,�H
A- J - -- w — I G CROW �.� i
COVER ADJUSTMENT —
HEIGHT i� ��� �1 i I I/a fre. r,,,,,,) ua+
t rKE o Fmnc
�` - -- L W FKE Q� LFYAG
1 LtiIIfNSCW
I
...
J 5/16' OIA. II II i r 1 % / //%
(84. 1 mmJ -�. ;'1 ■ I/ -
F1 RES 49 CCP PEND. �� *41"
Fig. 3 Fig. 4
Technical Data: Fl Res 49 CCP and FP
CCP Options Data:
Sprinlder CCP
Thr Temp. Assembly Max. Ambient Spnnider Cover Adjustment CCP Height
Temp, Pressure p Factor inch (mm) inch (mm)
S e g Rating psi (bar) Tem . i m n) X (12.7) s,� (24)
°F `F ° C ° F ° C 3x, (4.7) % (19) -- I
(R) 155 68 135 57 175 (12) 150 ., 66 4.9 2.25 (57)
FP Data "A ":
Max. Sprinkler I Tow Pressure sprinkler fi FP Position inch mm
Spacing
m) 9Am (4xn) psi (bar)
Number (SN) Max. ReceRecessed ed ( )
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48) Min. ss ';( (24)
14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)
16 x 16 (4.9x4.9) 14 (53) 8.2 (0.56) R3516
18 x 18 (5.5x5.5) 18 (68.1) 13.5 (0.93)
20x20(6.1x6.1) 20( 16.7(1.14)
3.
•
• Model Fl Res 44 Recessed
• Model Fl Res 44 HSW HSW/F2
} t} O r
F2 escutcheon, /" (13mm)
adjustment
Technical Data: Fl Res 44 HSW & HSW/F2
__. Escutcheon, F2, Data:
Sprinkl Frtting
Temp. Max. Face of ail
Th Max. nkler. T ype to wall
si Rating en Factor L ) T ( ) Inch (mm)
°F °C °F °C F2 X (13) X - % (4.7 - 17.4)
1/2" NPT 155 68 175 (12) 100 38 4.4 2.45 (62)
(Rh) 175 79 150 66
Max. Sprinkler Ceiling -to- SPriiMde . Row Pressure Sprinkler ification
Spacing Decor °F (°C 9Pm (4) Psi (Par) N um b er (st)
12 x 12 (3.6x3.6) 155 (68) 175 (79) 12 (45.4) _ 7.5 (0.52)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 14 (53.0) 10.2 (0.71)
16 x 16 (4.9x4.9) 4 -6 155 (68) 175 (79) 16 (60.) 13.3 (0.92)
16 x 18 (4.9)(5.5) (101 -152) 155 (68) _ 175 (79) 18 (68.1) 16.8 (1.16)
18 x 18 (5.5x5.5) 155 (68) 175 (79) 19 (72.0) 18.7 (1.29)
16x20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89) R3531
12 x 12 (3.6x3.6) 155 (68) _ 175 (79) 14 (53.0) 10.2 (0.71)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92)
16 x 16 (4.9x4.9) 6 -12 155 (68) 1 175 (79) 17 (64.4) 15.0 (1.04)
16 x 18 (4.9x5.5) (152-305) 155 (68) 175 (79)_ 20 (75.7) 20.7 (1.43)
•
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89)
4.
• Model Fl Res 40 Recessed
• Model Fl Res 40 HSW HSW/F2
• xt
,„.:4.:::;:i,!::::::::::;:k?:::.. ' .4Prni:
v
s .
k } i
�`
1,
F2 escutcheon, /" (13mm)
adjustment
i
FACEOF "rncm
rM LL meow
w / /e MIN
2 r /< mai I [[31.8m,,,)
/ • [6L 2mT J O (J. CEILING ro
. OEFLECIOR
I' ,- X 1/2' REDUCER \ OEFLECON flits l: t
1111C r � �'= 1 13/16 °A / I
\ t ,1 - 1 -ir -L- 71_1 -1--
I �/ — [49.2".4 a
/i 1 TURN COLLAR LAM
^� Y J I
.1 fl 1T AGUNSY srmo rctER
IVRENCN Bos 6 1.3101;011-8 —I 1/2' (13
ADJUSTMENT
F1 RES 44 HSW/F2
135FG05 AND
F1 RES 40 HSW /F2
Fig. 5 Fig. 6
Technical Data: Fl Res 40 HSW & HSW/F2
Escutcheon, F2, Data:
T iN x. Face of Elting to
Thread Sae Rating Pressure Tamp. Factor Type Inch ( Inch (mm)
°F °C Pai ( OF °C Inch ( ) F2 % (i3) % -, %R (4.7 - 17.4)
(R 175 68 175 (12 150 66 4.0 2.45 (62)
Max Ceii -to• Sprinkler Temp. Flow Pressure Sprinkler Identtflcabon
ft ) Inch nch (m m) Deflector Rating glen (LPm) Psi Oar) (m
(m
12 x 12 (3.6x3.6) 155 (68) , 175 (79) 13 (49.0) 10.6 (0.73)
14 x 14 (4.3x4.3) 155 (68) _ 175 (79) 16 (60.5) 16.0 (1.10)
16 x 16 (4.9x4.9) 155 (68) 17 (64.3) 18.1 (1.24)
16 x 16 (4.9x4.9) (101-152) 175 (79) 18 (68.1) 20.2 (1.39)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72) R3538
18 x 18 (5.5x5.5) 155 (68) 175 (79) 22 (83.3) 302 (2.08)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.0) 33.1 (2.28)
12 x 12 (3.6x3.6) 155 (68) 175 (79) 13 (49.0) 10.6 (0.73)
14 x 14 (4.3x4.3) 6 12 155 (68) 175 (79) 17 (64.3) 18.1 (1.24)
16 x 16 (4.9x4.9) (152 305) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72)
5.
Finished'
Standard Finishes Ordering Information
Specify:
, Sprinkler Fl, F2, FP Escutcheons 1. Sprinkler Model
Bronze Brass
Chrome Plated Bright Chrome Plated 2. Sprinkler Type
White Polyester Coated White Painted 3. Temperature Rating
Special Application Finishes 4. Sprinkler Finish
Sprinkler F1, F2, Escutcheons 5. Escutcheon Finish
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
" Other finishes and colors are available on special order.
Consult factory for details.
Maintenance
Model Fl Res 49, Fl Res 44 and Fl Res 40
Sprinklers should be inspected quarterly, and the
sprinkler system maintained in accordance with NFPA
25, 13, 13D, and 13R. Do not clean sprinkler with soap
and water, Ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle
vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in
any way. A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or
_ operated sprinklers. Prior to installation, sprinklers
should remain in the original cartons and packaging
until used. This will minimize the potential for damage
to sprinklers that could cause improper operation or
non - operation.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable
sprinkler contractors bcated throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
• (800) 431 -1588 Sales Offices
i � (800) 848 -6051 Sales Fax • Recycled
•
(914) 668 3470 Corporate Offices �" Paper
www.reliablesprinkler corn Internet Address Revision lines indicate updated or new data.
FR Printed in l I S A 1x10.1 PM I:M.97023S