From: Mark VanDomelen
Sent: Monday, March 07, 2011 1:37 PM
To: Rick Bolen
Subject: FW: setback challenge
Attachments: image001.gif
From: Mark VanDomelen
Sent: Monday, March 07, 2011 1:36 PM
To: 'Gary Culp'
Subject: RE: setback challenge
Hi Gary,
The proposed alternate is acceptable to The City for as a retrofit solution to protect the corner of the second story
cantilever section that projects approximately four inches into the 3' fire separation distance, protection would not be
required at 3' from the property line. Projections beyond the exterior walls (such as eaves) are still not allowed to
project more than 12" into the area where openings are prohibited per section R301.1. In this case, openings are
prohibited at less than 3' from the property line per table R302.1. The proposed method would be acceptable to protect
the eave that would be allowed to project to within 2' of the property line.
Thank you,
Mark VanDomelen
Building Official
City of Tigard
markvfttigard- or.gov
(503)718 -2448
From: Gary Culp [ mailto:Gary.Culp @PulteGroup.com]
Sent: Monday, March 07, 2011 11:06 AM
To: Mark VanDomelen
Cc: Cheryl Caines; Bill Waggoner
Subject: FW: setback challenge
Mark, I am not able to locate a final approval for this application, 1 know Cheryl Caines responded with her department
approval not long ago, can you send me something we can use as documentation and we'll move forward with the
retrofit and final inspections?
Thank you.
IPuLte
GARY CULP
Division Product Manager :: Pacific Northwest Division
direct (503) 608 - 6036:: Cell (971) 246 -1391
gary.culpApultegroup.com
From: Gary Culp
Sent: Friday, February 11, 2011 8:54 AM
To: 'Mark VanDomelen'
Cc: Bill Waggoner
Subject: RE: setback challenge
Good morning Mark,
Centex Homes (Pulte Group) is submitting the attached sketch as retrofit solution for a wall that extends into a setback
approximately 4 ". This is being submitted under section R104.11 of the ORSC as an alternative to section R302.
This condition exists for a residence located at 10919 S.W. Sage Terrace.
Thank you .
ItPuite
GARY CULP
Division Product Manager :: Pacific Northwest Division
direct (503) 608 - 6036:: Cell (971) 246 -1391
gary.culp(cr�pultegroup.com
CONFIDENTIALITY NOTICE: This email may contain confidential and privileged material for the sole use of the intended recipient(s). Any review. use, distribution
or disclosure by others is strictly prohibited. If you have received this communication in error, please notify the sender immediately by email and delete the
message and any file attachments from your computer. Thank you.
2
-
r. ....w .. ..- . �- a ...:... -.<,. R1"Yfl J^•.. y' s�y�SY. C_"=_..-.,.,..,, w. n .niyyy�••cpyM.::.._...�...,,,__ .. �.. ,.�- o,..m.. .....rte .... ..... ..... .�...::.,.,�.... .�..�:.- ,.. -«-» a,. ,.c ..
$
,.
..., illinIMIIIIMINIF
g
1r
�G tc
�... ,
a
G/
Uh v
y •
1
r
j �
I
.+
_10..._ 44Z let Mill . ' -l i f 4 ' ''' -17)4
'r..._ Y 2. .
li
i
P'
3
v s
24" MIN
5/5" TYPE "X" ATTACHED
E XTERIOR LAYERS IN PLACE (2)
(2) LAYERS 5/5" TYPE "X" GYP
PER BAY
/
`fl R -21 RIGID FIRE CAULK EACH LAYER
INSULATION AT EACH CORNER
NTERIOR
EXTERIOQ W 466EMEILttr
IX2 SPF STOPS TO HOLD
5/5" LAYER IN PLACE
(I) LAYER 5/5" TYPE "X" GYP
PER BAY, ATTACH TO SHEETING W/
CONSTRUCTION ADHESIVE
re 16 I
■ ■ 11
FIRE CAULK EACH CORNER
ill (I) LAYER 5/5" TYPE "X" GYP
PER BAY, ATTACH TO SHEETING W/
CONSTRUCTION ADHESIVE
...<4
4 ,...._-_
I. .........1_
FIRE CAULK EACH CORNER
E XtI R 1 SR R# OF ASSE'51