Correspondence Project: Elite Care - Grant Facility
Address: 12353 SW Grant St.
Permit #: ELC2007 -00181
Electrical Contractor: R & R Energy
2401 NW MLK, Jr Blvd
Portland, OR 97212
April 20, 2007
Re: Plan Review Letter
Mr. Marvin Schmutzler
The re- submittal of plans for electrical review are still incomplete. Please submit the
following for review by this office:
1) Two complete sets of plans including buildings one and two.
2) Two complete sets of floor plans and specifications for equipment in the
kitchen(s).
3) Verification of the horsepower for the elevator motors.
4) Verification of the horsepower for the Hydraulic and rain recovery systems.
5) Method for compliance with Art. 701.6 which states that a standby generator
system shall have adequate capacity and rating for the supply of all equipment
intended to be operated at one time.
Gary Noble
Senior Electrical Inspector
City of Tigard