Permit CITY OF TIGARD FIRE PROTECTION SYSTEM PERMIT
3 COMMUNITY DEVELOPMENT Permit #: FPS2010 -00154
T I G AR D 13125 SW Hall Blvd., Tigard OR 97223 503.718.2439 Date Issued: 01/06/2011
Parcel: 2S113AB01201
Jurisdiction: TIGARD
Site address: 16290 SW UPPER BOONES FERRY RD
Project: Dow Agrosciences Subdivision: PACTRUST BUSINESS CENTER Lot: 0
Project Description: Modification of fire alarm system.
Contractor: ADVANCED SECURITY & FIRE Owner: PACIFIC REALTY ASSOCIATES
2218 NE SUNRISE LN 15350 SW SEQUOIA PKWY #300
HILLSBORO, OR 97124 PORTLAND, OR 97224
PHONE: 503 - 519 -4550 PHONE: 503 - 624 -6300
FAX: 503 - 640 -8311
FEES 1
Description Date Amount
Specifics: Permit Fee - COM 12/09/2010 $91.44
12% State Surcharge - Building 12/09/2010 $10.97
Type of Use: COM Plan Review - Fire Life Safety - COM 12/09/2010 $36.58
Class of Work: ALT Type of Const: IIIB
Occupancy Grp: B Height: ft
Stories: 1
Commercial Sprinkler System:
Sprinkler Required: Sprinkler Type:
Standpipe Required: Hazard:
Density: 0 Design Area: 0
K Factor: 0
Commercial Fire Alarm System:
Fire Alarm Required: Yes Alarm Type: Manual
Pull Station Required: Yes Smoke Detectors Req: No
Battery Calcs Provided: Yes Cut Sheets Required: Yes
Total $138.99
Valuations: Required Items and Reports (Conditions)
Sprinkler Valuation: $0.00
Residential Square Footage: 0
Fire Alarm Valuation: $2,000.00
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of
issuance, or if work is suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon
Utility Notification Center. Those rules are set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0090. You may obtain a copy of the rules
or direct questions to OU C by calling 503.232.1987 or 1.800.332.2344.
Issued By: / Permittee Signature: 2 z4.4,2,2 < 406..„..„..<
Call 503.6 MIN 7:00 a.m. for the next available inspection date.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
Building Permit Application RECENED
Fire Protection System FOR OFFICE USI•: ONLY
9 ?M.
` . Received 9 City of Tigard � �� fa . Revie
teBe: ill 7 /O Permit No.:�"200_DO /S Y
�G' I•
13125 SW Hall Blvd., Tigard, OR 97223 '�I
�.�/ O�+ 1 A► Other Permit:
Phone: 503.639.4171 Fax: 503.598.1960 Cl ► + IN IV 1 i: • :: , �t 1 1
1 . 1 . A I . I) !/y / Inspection Line: 503.639.4175 Bu�IN Date Ready/By: Page 2 for
Internet: www.tigard or.gov Notified/Method: , �� � ► � Supplemental Information
6.. -� = -, ald
TYPE OF WORK Sck.) ' QUIRED DATA: 1- AND 2- FAMILY DWELLING
❑ New construction ❑ Demolition Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
Addition /alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
❑ 1- and 2- family dwelling ®.Commercial/industrial Valuation: $
❑ Accessory building ❑ Multi - family Number of bedrooms:
❑ Master builder El Other: Number of bathrooms:
JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site address: /6096 Up,Pe r &ones F erry Rd . New dwelling area: square feet
City /State /ZIP: 775 /9 P a Q / 9 7 a) , L) Garage /carport area: square feet
Suite/bldg. /apt. no.: Project name:bozo /9-g r p S i P n Q`e Covered porch area: square feet
Cross street/directions to job site: Deck area: square feet
Other structure area: square feet
REQUIRED DATA: COMMERCIAL -USE CHECKLIST
Subdivision: I Lot no.: Permit fees* are based on the value of the work performed.
Tax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
p DESCRIPTION OF WORK work indicated on this application.
f ■
,,9Q(t�(i L e rl Q � hto p n/ `si - ern h es 71'Q Valuation: $ c J D ,OQ, BO
e_X / sta n �/ T re /9 /� r r sy.sT e/ Existing building area: square feet
J New building area: square feet
❑ PROPERTY OWNER I ❑ TENANT Number of stories:
Name: Pi90 Tra ST Type of construction:
Address: Occupancy groups:
City /State /ZIP: Existing:
Phone: ( ) Fax: ( ) New:
❑ APPLICANT ❑ CONTACT PERSON NOTICE
Business name: All contractors and subcontractors are required to be
Contact name: licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: jurisdiction in which work is being performed. If the
City/State /ZIP: applicant is exempt from licensing, the following reasons
apply:
Phone: ( ) Fax:: ( )
E -mail:
CONTRACTOR BUILDING PERMIT FEES*
Business name: i q y, n c ed se c , ' f `, S (Please refer to _fee schedule)
J T r , �O
Permit fee:
Address: ,z) 7 9 ) / J) Ay e n a e
R q surcharge (12% of permit fee):
City /State /ZIP: j\
�o re s G /NO ye p ) / i' FLS plan review (40% of permit fee):
Phone: (5 03 5)q- If 5-50 Fax: (5Q3) 357- 0 s - 2 (Due upon application.)
CCB lic.: / 64 J'6 Total permit fees:
Authorized signature: D Amount received: �� $ • 9�
This permit application expires if a permit is not obtained
Print name: O/5 y / /11 Q r Y J k Date: /tg ' j6
within 180 days after it has been accepted as complete.
* Fee methodology set by Tri-County Building Industry
Service Board.
L\ Building \Permits\FPS- PermitApp.doc 10 /01/09 440- 4613T(1I /02/COM/WEB)
City of Tigard: Fire Protection Permit Checklist
Page 2 - Supplemental Information
Describe work to be done:
1.) ❑ New 2.) Modification to sprinkler heads only:
❑ Addition ❑ 1 -10 heads: No plan review required.
❑ Alteration El 11+ heads: Plan review required.
El Repair
Number of sprinkler heads:
•
Additional description of work:
Type of System (Complete A, B, C or D as applicable):
A.) Commercial Sprinkler
❑ Wet ❑ Dry
Additional Standpipes
Information: Hazard Group
Density
Design Area
K. Factor
Sprinkler Project Valuation: $
B.) Type I - Hood Fire Suppression System
Hood Project Valuation: $
C.) Fire Alarm
Submittal shall Battery Calculations El Yes
include: Individual Component ❑ Yes
Cut Sheets
Fire Alarm Project Valuation: $
D.) Residential Sprinkler (Stand Alone System)
Square Footage: Permit Fee:
0 to 2,000 $198.75
2,001 to 3,600 $246.45
3,601 to 7,200 $310.05
7,201 and greater $404.39
Sprinkler Project Square Footage: sq. ft.
Fire Protection Permit Fees
Project valuation subtotal (see A, B & C above): $
Permit fee based on project valuation (see fee schedule): $
Permit fee based on square footage (see D above): $
State Surcharge (12% of permit fee): $
FLS Plan Review (40% of permit fee): $
TOTAL: $
Plan review requires a completed application and 2 sets of plans at submittal. Plan review fees are required at submittal.
•
I:\ Building \Pemrits \FPS- PermitApp.doc 10/01/09 2
1 -7 Documentation 43
lation wiring has been checked. Part 3 shall be completed The Record of Completion was previously referred to
after the operational acceptance tests have been completed. as the Certificate of Completion. This document is very
A preliminary copy of the record of completion shall be given important to the owner, maintainer and the authority
to the system owner and, where requested, to other authori- having jurisdiction because it provides information nec-
ties having jurisdiction after completion of the installation wir- essary to maintain, repair and modify the system. A
ing tests, and a final copy shall be provided after completion record of completion is required for all installed fire
of the operational acceptance tests. Alarm Systems.
Record of Completion S2 to 00 icy
Name of Protected Property: O /9 ro S C/ f`n ees
Address: 40 90 SW Upper Beef) e5ferry Fd. 7 4ie 47 4
Rep. of Protected Prop. (name /phone):
Authority Having Jurisdiction:
Address /Phone Number:
1. Type(s) of System or Service
NFPA 72, Chapter 3 — Local
It alarm is transmitted to location(s) off premises, list where received:
�1 C eh f rn J Sf /9 fie.) ll /')Carl rl' Orr
5 4.30- EN
NFPA 72, Chapter 3 — Emergency Voice /Alarm Service
Quantity of voice /alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in system:
NFPA 72, Chapter 4 — Auxiliary
Indicate type of connection:
Local energy: Shunt: Parallel telephone:
Location and telephone number for receipt of signals:
sffi cnda, 5o3- d3G - 16
NFPA 72. Chapter 4 — Remote Station �(
Alarm: 0 e/1 / Lr'io Sf /o moo; �Or; /-1�j 3
5 - .4�G` 9
Supervisory: ! / \}
NFPA 72, Chapter 4 — Proprietary
If alarms are retransmitted to public fire service communications center or others, indicate location and telephone number of the organization
receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72. Chapter 4 — Central Station
C. -f - // 71 /
The Prime Contractor: /1 JJ
Central Station Location: E
Figure 1 - 7.2.1 Record of Completion.
NATIONAL FIRE ALARM CODE HANDBOOK
44 Chapter 1: Fundamentals of Fire Alarm Systems
Means of transmission of signals from the protected premises to the central station:
McCulloh Multiplex One -Way Radio
Digital Alarm Communicator Two -Way Radio Others
Means of transmission of alarms to the public fire service communications center:
(a) C en1!', / 57,97 Cr) CpN
(b)
System Location: S d ' G
p Organization Name/Phone / Q Representative Name/Phone 57-13-5-15- c�
�G{ / �JNCLti`,1y �S F''e Dnv rc( �t3!'/>IV,I� 5
"T .5 .)
Installer v 9 tl C EC /
Supplier
Service Organization Ad V/) nc f j _ S EC Ur i J F i re
Location of Record (As- Built) Drawings:
, dv'ncecC - Sec.ur; , w ;' ( Cf7
Location of Owners Manuals:
Location of Test Reports:
e n S ;tom
Acontrnr' clgted .2 /' /I , fortestandinspectioninaccordancewithNFPAstandard (s)No(s).
dated a _ / _ / ( ' n effect.
Record of System Installation
(Fill out after installation is complete and wiring checked for opens, shorts, ground faults, and improper branching, but prior to conducting op-
erational acceptance tests.) /n� // n�1 l_
This system has G {J
keen installed in accordance with the NFPA standards as shown below, was inspected by '9 V I !d�'�ti�r 1�
on ' a - / / / _, includes the devices shown below, and has been in service
since • - 1 ° / l
f NFPA 72, Chapters 1 3 4 5 6 7 (circle all that apply)
NFPA 70, National Electrical Code, Article 760
-7 Manufacturer's Instructions
Ot er (specify : �i
Signed: G yr r � ` .c /Y1 -014.0 �? 1 Date: c)
Organization: /9d vf9Jlcer4 .5(ciA •
3. Record of System Operation ! /� J
All operational features and functions of this system were tested by { Y /[- inor/9 %,'". on ` /`// , and
found to be operating properly in accordance with the requirements of:
NFPA 72, Chapters 1 3 4 5 6 7 (circle all that apply)
NFPA 70, National Electrical Code, Article 760
V /// Manufacturer's Instructions
Ot r (specify):
Signed: 6,',.g / -41 Date:
Organization: ./7 v7(/ n Ceti SL-P/ / '✓ / r
✓ i
Figure 1 -7.2.1 Continued
NATIONAL FIRE ALARM CODE HANDBOOK
•
1 -7 Documentation 45
4. Alarm- Initi Devices and Circuits (use blanks to indicate quantity of devices)
MANUAL _ _ AC •
(a) / Manual Stations Noncoded, Activating Transmitters _ Coded
(b) Combination Manual Fire Alarm and Guard's Tour Coded Stations
AUTOMATIC
Coverage: Complete: Partial:
(a) Smoke Detectors Ion Photo
(b) Duct Detectors Ion Photo
(c) Heat Detectors FT RR FT /RR RC
(d) Sprinkler Watertlow Switches: Transmitters Noncoded, Activating Coded
(e) Other (list):
5. Supervisory Signal- Initiating Devices and Circuits (use blanks to indicate quantity of devices)
GUARD'S TOUR
•
(a) Coded Stations
(b) Noncoded Stations, Activating Transmitters
(c) Compulsory Guard Tour System Comprised of Transmitter Stations and Intermediate Stations
NOTE: Combination devices recorded under 4(b) and 5(a).
SPRINKLER SYSTEM
(a) -_ Coded Valve Supervisory Signaling Attachments
Valve Supervisory Switches, Activating Transmitters
(b) Building Temperature Points
(c) _ Site Water Temperature Points
(d) Site Water Supply Level Points
Electric Fire Pump:
(e) Fire Pump Power
(f) Fire Pump Running
(g) Phase Reversal
Engine- Driven Fire Pump:
(h) Selector in Auto Position
(i) Engine or Control Panel Trouble
(i) Fire Pump Running
Engine- Driven Generator:
(k) Selector in Auto Position
(I) Control Panel Trouble
(m) Transfer Switches
(n) Engine Running
Other Supervisory Function(s) (specify):
Figure 1 - 7.2.1 Continued
NATIONAL FIRE ALARM CODE HANDBOOK
46 Chapter 1: Fundamentals of Fire Alarm Systems •
6. Alarm Notification Appliances and Circuits
Quantity of indicating appliance circuits connected to the system:
Types and quantities of alarm indicating appliances installed:
(a) Bells Inch
(b) Speakers
(c) / g Horns/
(d) Chimes
(e) Other: c /
(I) Visual Signals Type: �fi'db e4
with audible w/o audible
(9) / Local Annunciator
7. Signaling Line Circuits
Quantity and Style (see NFPA 72, Table 3 -6) of signaling line circuits connected to system:
Quantity: 'y Style:
' 8. System Power Supplies D
(a) Primary (Main):Nominal Voltage: /- Current Rating: .20.9-/r),
Overcurrent Protection: Type: Sr r Current Rating: °2 G# T
Location:
(b) Secondary (Standby):
Storage Battery: Amp -Hour Rating 7.5 X / 5
Calculated capacity to drive system, in hours: 24 60
Engine- driven generator dedicated to fire alarm system:
Location of fuel storage:
(c) Emergency or Standby System used as backup to Primary Power Supply, instead of using a Secondary Power Supply:
Emergency System described in NFPA 70, Anicle 700
Legally Required Standby System described in NFPA 70, Article 701
Optional Standby System described in NFPA 70, Article 702, which also meets the performance requirements of Article 700
or 701
9. System Software
(a) Operating System Software Revision Level(s):
(b) Application Software Revision Level(s):
(c) Revision Completed by:
(name) (firm)
10. Comments:
l /CLtiz�t�� LO A^ e S i d em * 2-1-/1
(signed) for Central Station or Alarm Service Company (title) (date)
Figure 1 - 7.2.1 Continued -
NATIONAL FIRE ALARM CODE HANDBOOK
1 -7 Documentation <17
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standards(s): / ! ., - � n ! - --
) 1 e Gi h> �i - 1 - C C�n n� �_5f/)f,Cn o /; G u__ _ / --
System deviations from the referenced NFPA standard(s) are: /v - -- -- --- - - - - --
( \ 104-124 1 7-77.4r1Z21-4 l n c:2- 1 - l I — :
(signed) for Central Station or Alarm Service Company (title) (date)
Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction):
bitca 7rZotaj POE 5 i n -- - -- 1-
- - - --
(signed) for Central Station or Alarm Service Company (tale) (date)
Figure 1 -7.2.1
A-1-7.2.1 The requirements of Chapter 7 should be used 2. Step -by -step instructions detailing the requisite test
to perform the installation wiring and operational acceptance ing and maintenance procedures. and the intervals at which
tests required when completing the record of completion. these procedures shall be performed. for each type of device
installed;
1-7.2.2 Every system shall include the following documen-
3. A schedule that correlates the testing and mainte-
nance procedures recommended by A- 1- 7.2.2(c)2 with the
tation, which shall be delivered to the owner or the owner's listing recommended by A-1 7.2.2(c)1.
representative upon final acceptance of the system.
(d) Detailed troubleshooting instructions for each trouble
(a)' An owner's manual and installation instructions cover- condition generated from the monitored field wiring, including
ing all system equipment; and opens, grounds, and loop failures. These instructions should
include a list of all trouble signals annunciated by the system,
(b) Record drawings. a description of the condition(s) that causes such trouble sig-
. nals, and step -by -step instructions describing how to isolate
A-1- 7.2.2(a) The owner's manual should include: such problems and correct them (or how to call for service, as
appropriate).
(a) A detailed narrative description of the system inputs, (e) A service directory, including a list of names and tele-
evacuation signaling, ancillary functions. annunciation, in- phone numbers of those who provide service for the system.
tended sequence of operations, expansion capability, applica-
tion considerations, and limitations. 1-7.2.3 Central Station Fire Alarm Systems. It shall be
(b) Operator instructions for basic system operations, conspicuously indicated by the prime contractor (see Chapter
including alarm acknowledgment, system reset. interprets- 4) that the fire alarm system providing service at a protected
tion of system output (LEDs, CRT display, and printout), oper-
ation of manual evacuation signaling and ancillary function
controls, and change of printer paper. code by providing a means of verification as specified in
(c) A detailed description of routine maintenance and test- either 1- 7.2.3.1 or 1- 7.2.3.2.
ing as required and recommended and as would be provided
under a maintenance contract, including testing and mainte- 1-7.2.3.1 The installation shall be certificated.
nance instructions for each type of device installed. This infor-
mation should include the following: 1-7.2.3.1.1 Central station fire alarm systems providing
1. A listing of the individual system components that re- service that complies with all requirements of this code shall 1
quire periodic testing and maintenance: be certificated by the organization that has listed the prime
NATIONAL FIRE ALARM CODE HANDBOOK
•} Z or 0- o0 1
• 1 -7 Documentation 43
lation wiring has been checked. Part 3 shall be completed The Record of Completion was previously referred to
'after the operational acceptance tests have been completed. as the Certificate of Completion. This document is very
A preliminary copy of the record of completion shall be given important to the owner, maintainer and the authority
to the system owner and, where•requested, to other authori having jurisdiction because it provides information nec-
1/ '\' ties having jurisdiction after completion of the installation wir- essary to maintain, repair and modify the •system. A
ing tests, and a final copy shall be provided after completion record of completion is required for all installed fire
of the operational acceptance tests. Alarm Systems.
/'� Record of Completion
Name of Protected Property: tJ G W 4 !'O s c i e n C �'. S o
Address: /6/60, J ( f e i' C� C)O[) e S ce r r' 'ea( / i /3rGf Gv e
Rep. of Protected Prop. (name/phone): J A T � -
p. p. (name/ hone : C'. �'Gt 5'f" s��J, �, �� 3
� tr�
Authority Having Jurisdiction: T/ Q /9 rC( •
Address /Phone Number:
1. Type(s) of System or Service
NFPA 72, Chapter 3 — Local
If alarm is transmitted to location(s) off premises, list where received:
C e n Sh9 fi0r1 / ;-) n33 50 3 - 1.30- a 89
NFPA 72, Chapter 3 — Emergency Voice /Alarm Service
Quantity of voice /alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker Tones:
Quantity of teiephones or telephone jacks included in system:
NFPA 72, Chapter 4 — Auxiliary
Indicate type of connection:
Local energy: Shunt: Parallel telephone:
Location and telephone number for receipt of signals:
E S /fi C 0191 OR 510.3 - h30- '
NFPA 72, Chapter 4 — Remote Station
Alarm: C e / .Sf/91 /a or) 1 for , ns 5e3- .4,30-,2e96
Supervisory: "
NFPA 72, Chapter 4 — Proprietary
If alarms are retransmitted to public fire service communications center or others, indicate location and telephone number of the organization
receiving alarm:
Centr',I 5' /en en ;7 n 503 -630 -aV46
Indicate how alarm is retransmitted:
NFPA 72, Chapter 4 — Central Station
The Prime Contractor: C �° n ' f /3 I S f/37/on PI_ / 1
Central Station Location: £ S j- ,,C Aa A 0 k
•
Figure 1 -7.2.1 Record of Completion.
•
NATIONAL FIRE ALARM CODE HANDBOOK
•
•
44 Chapter 1: Fundamentals of Fire Alarm Systems
Means of transmission of signals from the protected premises to the central station:
McCulloh Multiplex One -Way Radio
Digital Alarm Communicator Two -Way Radio Others
Means of transmission of alarms to the public fire service communications center:
(a) e e� r� / 5 g o t) Oper/t
(b)
System Location: E-514 C /3 Gt r OR
Q Organization Name /Phone / �0 p /� Representative Name/Phone C L ( I
Installer /?dV/�►nCec( ,SeCUr 4, FI Day ice /�or'/9v Jd3 -5)q- /55
Supplier pp
Service Organization Ad vine e.c( Se.cur i ]� s(1 Fire
Location of Record (As- Built) Drawings:
Acivr4 raced -Secur► F; re ( Ofiric.e
Location of Owners Manuals:
On -s%
Location of Test Reports:
O n - 1-
Acontrc fitted Li- 3 / I , fortest and inspection in accordance with NFPA standard (s)No(s).
dated L' . in effect.
Record of System Installation
(Fill out after installation is complete and wiring checked for opens, shorts, ground faults, and improper branching, but prior to conducting op-
erational acceptance tests.) ,/ n�1
This system has installed in accordance with the NFPA standards as shown below, was inspected by �EJA r`^ e0!'!li°i
on 1 )- .3-- _ includes the devices shown below, and has been in service
since
NFPA 72, Chapters 1 3 4 5 6 7 (circle all that apply)
NFPA 70, National Electrical Code, Article 760
V Manufacturer's Instructions
Ot er (speciff :
Signed: C -r,-Y i C.l� T r ;'J p Date: 7 -
Organization: /9d Yft /) c ecl .J e Cu l+i t�/ F ;Pe
3. Record of System Operation //�� 2
All operational features and functions of this system were tested by -LfVicl /')orAVa k on LJ - J ' f/ , and
found to be operating properly in accordance with the requirements of:
V NFPA 72, Chapters 1 3 4 5 6 7 (circle all that apply)
V NFPA 70, National Electrical Code, Article 760
V Manufacturer's Instructions
Other (specify): 'Y1
Signed: (lr. / [,v LGt c Date: 4 1 "
Organization: /9d v// n cei S cti rl fV 1.3
Figure 1 Continued
NATIONAL FIRE ALARM CODE HANDBOOK
1-7 Documentation 45
4. Alarm- Initiating Devices and Circuits (use blanks to indicate quantity of devices)
MANUAL _
(a) / Manual Stations Noncoded, Activating Transmitters Coded
(b) Combination Manual Fire Alarm and Guard's Tour Coded Stations
AUTOMATIC
Coverage: Complete: Partial:
(a) o � I Smoke Detectors Ion Photo
(b) O ¢- Duct Detectors Ion - Photo
(c) Heat Detectors FT RR FT /RR RC
(d) / Sprinkler Water(low Switches: Transmitters Noncoded, Activating Coded
(e) / Other (list): S/)// d Fr Tip r p
5. Supervisory Signal- Initiating Devices and Circuits (use blanks to indicate quantity of devices)
GUARD'S TOUR
(a) Coded Stations
(b) Noncoded Stations, Activating Transmitters
(c) Compulsory Guard Tour System Comprised of Transmitter Stations and Intermediate Stations
NOTE: Combination devices recorded under 4(b) and 5(a).
SPRINKLER SYSTEM
(a) Coded Valve Supervisory Signaling Attachments
Valve Supervisory Switches, Activating Transmitters
(b) Building Temperature Points
(c) Site Water Temperature Points
(d) Site Water Supply Level Points
Electric Fire Pump:
(e) Fire Pump Power
(I) Fire Pump Running
(g) Phase Reversal
Engine- Driven Fire Pump:
(h) Selector in Auto Position
(i) Engine or Control Panel Trouble
Q) Fire Pump Running
Engine- Driven Generator:
(k) Selector in Auto Position
(I) Control Panel Trouble
(m) Transfer Switches
(n) Engine Running
Other Supervisory Function(s) (specify):
Figure 1 -7.2.1 Continued
NATIONAL FIRE ALARM CODE HANDBOOK
•
46 Chapter 1: Fundamentals of Fire Alarm Systems
6. Alarm Notification Appliances and Circuits
Quantity of indicating appliance circuits connected to the system:
Types and quantities of alarm indicating appliances installed:
(a) Bells Inch
(b) Speakers
(c) Horns
(d) Chimes
(e) Other: �/ L L
(ff / Visual Signals Type: �f //4 /'/1 ` re es
�. �¢ w audible g w/o audible
(g) / Local Annunciator
7. Signaling Line Circuits
Quantity and Style (see NFPA 72, Table 3 -6) of signaling line circuits connected to system:
Quantity: Style: 8
8. System Power Supplies
(a) Primary (Main):Nominal Voltage: A2 6 V Current Rating: L) M p
Overcurrent Protection: Type: Are f9 k e r` Current Rating: c2 Li A /gy p
Location:
(b) Secondary (Standby):
a Storage Battery: Amp -Hour Rating 0'2' 7 "5 x 1 API p
Calculated capacity to drive system, in hours: l 24 60
Engine- driven generator dedicated to fire alarm system:
Location of fuel storage:
(c) Emergency or Standby System used as backup to Primary Power Supply, instead of using a Secondary Power Supply:
Emergency System described in NFPA 70, Article 700
Legally Required Standby System described in NFPA 70, Article 701
Optional Standby System described in NFPA 70, Article 702, which also meets the performance requirements of Article 700
or 701
9. System Software
(a) Operating System Software Revision Level(s):
(b) Application Software Revision Level(s):
(c) Revision Completed by:
(name) (firm)
10. Comments:
pp, side * 1-1 /Jey
(signed) for Central Station or Alarm Service Company (title) (date)
Figure 1 -7.2.1 Continued
NATIONAL FIRE ALARM CODE HANDBOOK
1 -7 Documentation 47
•
-�1
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standards(s): - S � 1
e.cf' re; 11A -f Ccni '9 f _ S f /9 1 en, /9 CI_ u/9071 1`J
•
System deviations from the referenced NFPA standard(s) are: f" /9 - - -- _ - -- — - -_. - -- —
•
PPe s_id e of -- - -- -411,9 q
(signed) for Central Station or Alarm Service Company (title) (date)
Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction):
. .(1A2q1l)
(signed) for Central Station or Alarm Service Company (title) (dale)
Figure 1 -7.2.1
A -1 -7.2.1 The requirements of Chapter 7 should be used 2. Step -by -step instructions detailing the requisite test -
to perform the installation wiring and operational acceptance ing and maintenance procedures. and the intervals at which
tests required when completing the record of completion. these procedures shall be performed. for each type of device
installed,
1-7.2.2 Every system shall include the following documen- 3. A schedule that correlates the testing and mainte-
tation, which shall be delivered to the owner or the owner's Hance procedures recommended by A-1-7.2.2(c)2 with the
listing recommended by A- 1- 7.2.2(c)1.
representative upon final acceptance of the system.
(d) Detailed troubleshooting instructions for each trouble
(a)' An owner's manual and installation instructions cover- condition generated from the monitored field wiring, including
ing all system equipment; and opens, grounds, and loop failures. These instructions should
include a list of all trouble signals annunciated by the system,
(b) Record drawings. a description of the condition(s) that causes such trouble sig-
. nals, and step -by -step instructions describing how to isolate
A- 1- 7.2.2(a) The owner's manual should include: such problems and correct them (or how to call for service, as
appropriate).
(a) A detailed narrative description of the system inputs. (e) A service directory, including a list of names and tele-
evacuation signaling, ancillary functions. annunciation, in- phone numbers of those who provide service for the system.
tended sequence of operations, expansion capability, applica-
tion considerations, and limitations. 1 -7,2,3 Central Station Fire Alarm Systems. It shall be
(b) Operator instructions for basic system operations, conspicuously indicated by the prime contractor (see Chapter
including alarm acknowledgment, system reset. interpreta-
4) that the fire alarm system providing service at a protected
tion of system output (LEDs, CRT display, and printout), oper-
ation of manual evacuation signaling and ancillary function premises complies with all applicable requirements of this
controls, and change of printer paper. code by providing a means of verification as specified in
(c) A detailed description of routine maintenance and test- either 1- 7.2.3.1 or 1- 7.2.3.2.
ing as required and recommended and as would be provided
under a maintenance contract, including testing and mainte- 1-7.2.3.1 The installation shall be certificated.
nance instructions for each type of device installed. This infor-
mation should include the following.
1-7.2.3.1.1 Central station fire alarm systems providing
1. A listing of the individual system components that re service that complies with all requirements of this code shall
quire periodic testing and maintenance: be certificated by the organization that has listed the prime
NATIONAL FIRE ALARM CODE HANDBOOK