Report me c Div - 0v CL73
R ACCURATE BALANCING AGENCY INC
Commercial & Industrial • Air & Ilydronic, Testing Adiusling a Balancing
ESB #: 3866 • NEBB Certified • CCB #: 64815
CERTIFIED
TEST, ADJUST, BALANCE REPORT
FOR
Project: Express @ Washington Square
Location: Tigard, Oregon
Engineer: Shremshock Engineering
HVAC Contractor: Pace Heating
� 4
� ;�, �� -,��• fi x- � y g
1 � t `Y� Pia
rpfg' h
NEBB Cert #3177
P.O. Boo 653 • Beaverton, OR 97075 • ABA@ABAinc.US • (5031297 -6594 • (5031292 -4825 fax
�k x t ��
A 8 �►
Table of Contents
Project - Location: Express @ Washington Square - Tigard, Oregon
Page #
Table of Contents 1
Certification 2
Terms and Abbreviations 3
Instrument Calibration 4
General Remarks and Summaries 5
Terminal Unit Test Report 6
Air Outlet Test Reports 7
Fan Test Report 11
Indexed Floor Plan
Accurate Balancing Agency, Inc. Page 1 of 11 Supervisor: Edward M. May Jr.
t �
A Certification
Project - Location: Express @ Washington Square - Tigard, Oregon
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the NEBB
Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems.
Any variances from design quantities, which exceed NEBB tolerances, are noted in the
Test - Adjust - Balance Report Project Summary.
Significant or noteworthy remarks are noted on the General Remarks or on individual
test reports.
Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this
report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any
descrepancies, ambiguities, or omissions found in this report will be retested, adjusted,
or balanced as needed. A written notification will be required.
Submitted and Certified by
NEBB TAB Firm: Accurate Balancing Agency, Inc.
Certification: 3177
Expiration Date: March 31, 2011
Certification Date: December 8, 2010
Signed and Sealed by
NEBB Supervisor: Edward M. May Jr.
1 ,
>t•r
Accurate Balancing Agency, Inc. Page 2 of 11 Supervisor: Edward M. May Jr.
l l Terms and Abbreviations
Project - Location: Express @ Washington Square - Tigard, Oregon
AC Air Conditioning Unit
AH Air Handler
AHU Air Handling Unit
BHP Brake Horsepower
BMS Building Management System
BTUH British Thermal Units per Hour
CEF Ceiling Exhaust Fan
CFM Cubic Feet per Minute
CRU Computer Room Unit
DB Dry Bulb
DDC Direct Digital Control
EAT Entering Air Temperature
EWT Entering Water Temperature
EF Exhaust Fan
EG Exhaust Grille (Shown as Triangled number on indexed plans)
ERU Energy Recovery Unit
FPB Fan Powered Box (Terminal Unit which incorporates a fan)
FSD Fire / Smoke Damper
GPM Gallons per Minute
Head Pressure Difference across the entering and leaving side of a pump
HRU Heat Recovery Unit
HVAC Heating Ventilation and Air Conditioning
HZ Hertz
Inches( ") Inches of water gauge
K Correction factor to the free area needed to calculate CFM
LAT Leaving Air Temperature
LWT Leaving Water Temperature
N/A Not Applicable
N/L Note Listed
OBD Opposed Blade Damper
OAD Outside Air Damper
OD Outside Diameter
OSA Outside Air Damper
PSI Pounds per Square Inch
RA Return Air
RG Return Grille (Shown as a Circled number on indexed plans)
RPM Revolutions Per Minute
RTU Roof Top Unit
SA Supply Air
SG Supply Grille (Shown as a Standard number on indexed plans)
SFA Service Factor Amperage
TAB Test; Adjust; and Balance
VAV Variable Air Volume (Terminal Unit which regulates airflow)
VEL Velocity
WB Web Bulb
Accurate Balancing Agency, Inc. Page 3 of 11 Supervisor: Edward M. May Jr.
A" B A Instrument Calibration Report
Project - Location: Express @ Washington Square - Tigard, Oregon
Instrument Manufacturer I Model # 1 Serial # I Calibrated I Cal. Due I
Type
Tachometer UEI I DPM5 I L420478 I 10/14/2010 I 10/14/2011 I
Rotation
Thermometer UEI I 550B I 021109675 1 10/14/2010 I 10/14/2011
Immersion
Thermometer UEI I 550B I 090502268 I 10/14/2010 I 10/14/2011 I
Air Temp
Electrical UEI I DL389 I 90501731 I 10/14/2010 I 10/14/2011 I
Multimeter
' Manometer Shortridge I ADM -860 I M03371 I 10/13/2010 I 10/13/2011 I
Air Pressure
Hygro - Thermometer Extech I RH490 I 10052806 I 9/30/2010 I 9/30/2011 I
Humidity
Anemometer UEI I DAFM2 I 900501731 I 10/14/2010 I 10/14/2011
Air Velocity
Flowhood Shortridge I ADM -860 I M03371 I 10/13/2010 I 10/13/2011 I
Air Volume
Thermometer UEI I ATT47 probe I 90501731 I 10/14/2010 I 10/14/2011 I
Contact
Hydrometer Alnor / TSI I HM680 I 70552165 I 11/9/2010 I 11/9/2011
Differential Pressure
1 1 1 1
Accurate Balancing Agency, Inc. Page 4 of 11 Supervisor: Edward M. May Jr.
A Et z. General Remarks and Summary
Project - Location: Express @ Washington Square - Tigard, Oregon
1) See specific remarks on forms within.
Accurate Balancing Agency, Inc. Page 5 of 11 Supervisor: Edward M. May Jr.
A Fan Powered Terminal Test Report
(Pressure Independent)
Project Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 12/8/10
Submittal Test Data
VAV Terminal Type Size DDC Address Cal. Factor Fan Speed
VAV -1 Parallel 14 "R 04- DB -13 -83 1.02 Potentiometer
VAV -2 Parallel 14 "R 04- 4B -13 -83 0.90 Potentiometer
VAV -3 Parallel 14 "R 04- 49 -04 -92 1.17 Potentiometer
VAV-4 Parallel 14 "R 04 -6C -19-41 1.03 Potentiometer
•
Remarks: I See related Air Outlet Test Reports for additional air flow data.
VAV -1 and VAV -2 heating fans did not run when overridden into heating mode.
Accurate Balancing Agency, Inc. Page 6 of 11 Supervisor: Edward M. May Jr.
ABA Air Outlet Test Report
Project - Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 12/2/2010
System / Unit Design Preliminary Final Test
Area Served # Size Type AK VEL CFM VEL CFM VEL CFM
VAV -1 Maximum
Mens Area 1 10 "R SG 1.00 350 350 295 295 295 295 84%
Did Not Exist 2 10 "R SG 1.00 0 0 0 0
Mens Area 3 10 "R SG 1.00 350 350 355 355 355 355 101%
Mens Area 4 10 "R SG 1.00 350 350 380 380 380 380 109%
Mens Area 5 10 "R SG 1.00 350 350 365 365 365 365 104%
Mens Area 6 10 "R SG 1.00 350 350 365 365 365 365 104%
Mens Area 7 10 "R SG 1.00 355 355 330 330 330 330 93%
Mens Area 8 10"R SG 1.00 350 350 355 355 355 355 101%
Total 2455 - 2445 2445 100%
VAV -1 1 Total -- 1.00 645 645 680 680 680 680 105%
Minimum Total 645 680 680 105%
VAV -1
Fan Did Not Run
Remarks: I
Supply diffuser #2 did not exist; remaining supply grilles were increased to allow for design total airflow.
VAV -1 heating fan did not run when overridden into heating mode.
Accurate Balancing Agency, Inc. Page 7 of 11 Supervisor: Edward M. May Jr.
ABA " �
': li Air Outlet Test Report
Project - Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 12/2/2010
System / Unit Design Preliminary Final Test
Area Served # Size Type AK VEL CFM VEL CFM VEL CFM
VAV -2 Maximum
Cashwrap Room 1 10 "R SG 1.00 295 295 190 190 285 285 97%
Cashwrap Room 2 10 "R SG 1.00 295 295 255 255 300 300 102%
Denim Room 3 10 "R SG 1.00 295 295 295 295 295 295 100%
Denim Room 4 10"R SG 1.00 295 295 285 285 295 295 100%
Fitting Room 5 12"R SG 1.00 380 380 270 270 375 375 99%
Denim Room 6 10"R SG 1.00 295 295 325 325 290 290 98%
Denim Room 7 10 "R SG 1.00 295 295 285 285 290 290 98%
Denim Room 8 10 "R SG 1.00 295 295 290 290 300 300 102%
Total 2445 2195 2430 99%
VAV -2 1 Total - -- 1.00 645 645 670 670 670 670 104%
Minimum Total 645 670 670 104%
VAV -2
Fan Did Not Run
, Remarks:
VAV - heating fan did not run when overridden into heating mode.
Accurate Balancing Agency, Inc. Page 8 of 11 Supervisor: Edward M. May Jr.
A E3 A Air Outlet Test Report
Project - Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 11/30/2010
System / Unit Design Preliminary Final Test
Area Served # Size Type AK VEL CFM VEL CFM VEL CFM
VAV -3 Maximum
Did Not Exist 1 10 "R SG 1.00 0 0 0 0
Womens Area 2 10 "R SG 1.00 350 350 375 375 350 350 100%
Womens Area 3 10"R SG 1.00 350 350 380 380 350 350 100%
Womens Area 4 10 "R SG 1.00 350 350 350 350 340 340 97%
Womens Area 5 10"R SG 1.00 350 350 430 430 355 355 101%
Womens Area 6 10"R SG 1.00 355 355 395 395 355 355 100%
Womens Area 7 10 "R SG 1.00 350 350 370 370 355 355 101%
Womens Area 8 10 "R SG 1.00 350 350 475 475 335 335 96%
Total 2455 2775 2440 99%
VAV -3 1 Total - -- 1.00 645 645 655 655 655 655 102%
Minimum Total 645 655 655 102%
VAV -3 1 Total - -- 1.00 750 750 746 746 746 746 99%
Fan I Total 750 746 746 99%
Remarks: I
Supply diffuser #1 did not exist; remaining supply grilles were increased to allow for design total airflow.
Accurate Balancing Agency, Inc. Page 9 of 11 Supervisor: Edward M. May Jr.
• ABA Air Outlet Test Report
Project - Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 11/12/2010
System / Unit Design Preliminary Final Test
Area Served # Size Type . AK VEL CFM VEL CFM VEL CFM %
VAV-4 Maximum
Managers Office 1 8"R SG 1.00 150 150 300 300 - 140 140 93%
Non Sales 2 8"R SG 1.00 200 200 170 170 200 200 100%
Non Sales 3 8 "R SG 1.00 200 200 155 155 175 175 88%
Non Sales 4 8 "R SG 1.00 200 200 230 230 200 200 100%
Non Sales 5 8 "R SG 1.00 200 200 165 165 180 180 90%
Non Sales 6 8 "R SG 1.00 200 200 180 180 200 200 100%
Non Sales 7 8 "R SG 1.00 200 200 140 140 160 160 80%
Non Sales 8 8"R SG 1.00 150 150 215 215 250 250 167%
Non Sales 9 8 "R SG 1.00 150 150 160 160 155 155 103%
Total •1650 1715 1660 101%
VAV-4 1 Total - -- 1.00 270 270 300 300 300 300 111%
Minimum Total 270 300 300 111%
VAV-4 1 Total - -- 1.00 710 710 740 740 740 - 740 104%
Fan Total 710 740 740 104%
Remarks:
Accurate Balancing Agency, Inc. Page 10 of 11 Supervisor: Edward M. May Jr.
ABA Fan Test Report
(Direct Drive < 1 /6HP)
Project - Location: Express @ Washington Square - Tigard, Oregon
Technician: TT Test Date: 11/12/2010
Submittal Data I
Unit Designation EF -
Service Restroom
Manufacturer Loren Cook
Model Number Gemini 160
Test Data 1
Item Design Actual
Total Airflow (CFM Design / Outlet) 75 / 75 160
Submittal:Data 1
Unit Designation
Service
Manufacturer
Model Number
'rest Data 1
Item Design Actual
Total Airflow (CFM Design / Outlet)
Submittal Data I
Unit Designation
Service
Manufacturer
Model Number
Test Data 1
Item Design Actual
Total Airflow (CFM Design / Outlet)
.. Remarks: I
EF -1 is a single speed direct drive fan reported as tested.
Accurate Balancing Agency, Inc. Page 11 of 11 Supervisor: Edward M. May Jr.