February 20, 2007
ENGINEERS
Mr. Brad Miller
Legacy Homes
17825 S Fieldstone Ln
Oregon City, Oregon 97045
Subject: House Plan 2387 -2L
Lot #5, Prospect Meadows, Tigard, OR
• MCE Project Number: 060870
Building Permit #: MST2007 - 00016
Dear Mr. Miller:
The following is a response to the plan check that was dated February 13, 2007 from the
City of Tigard.
1.) All text on the plan should be no smaller than a size 10 font for the purpose of
clarity, and to enable the plan to remain in a readable state on the jobsite.
Smaller than size 10 font cannot be put on microfiche. Please revise plan pages
with this minimum font size requirement for sheets 2,3,4, and 5.
MCE Response: This is not part of our scope of services and is by others.
2.) The foundation plan on sheet 5 has information superimposed over other
information at the front and rear of the garage, this information is not clear.
MCE Response: This is not part of our scope of services and is by others.
3.) Sheet 3 is missing BP nailing requirements. Page 4 is missing ABP nailing
requirements.
MCE Response: This is not part of our scope of services and is by others.
4.) Please designate which brace panel method is being utilized , and provide nailing
information on floor plans.
MCE Response: This is not part of our scope of services and is by others.
9570 SW Barbur Blvd., Suite 100 Portland, Oregon 97219-5412
Phone (503) 246 -1250 Fax (503) 246 -1395 www.mlllerengrs.com
gh
American Consulting WO Engineers Council
House Plan 2387 -2L
Lot #5, Prospect Meadows, Tigard, OR
Project Number: 060870
February 20, 2007
Page 2 of 3
5.) Provide shearwall calculations for bay window area .1 floor and second story
above, pages 2 and 3.
MCE Response: The lateral requirements of the entire front wall on the 1 floor
have been taken out in the Simpson Shearwall that is specified at R3. CS 16 strap is
located on the framing plan to distribute the load from the bay window area into the
Simpson Shearwall. The upper floor has ABPs called out and are by others. There is
no requirement for additional shearwalls at the bay window area.
6.) Revise floor framing on sheet 6 to show double joists under IBP per R602.10.9.
MCE Response: This is not part of our scope of services and is by others.
7.) The R3 designation to the left of the front door on page 3 isn't clarified on this
plan.
MCE Response: This is not part of our scope of services and is by others.
If you have any questions, please feel free to contact our office.
Respectfully,
Miller Consulting Engineers, Inc.