Loading...
Plans February 23, 1999 CITY OF TIGARD Nicoll Engineering OREGON PO Box 23784 Tigard, OR 97281 Attn: Jim Andrews RE: Duncan Building Site Plan Review 16135 SW 74th Avenue PC #: 2 -34c SIT #: 99 -0006 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1998 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: \D∎fl sITE wORK14 ,t 1 1 Prov a liquefaction potential and soil strength loss report (OSSC, Section 1804. . and 1804.5). 2. eview of the approved 1982 (LID 21) street improvement plan and profile for SW 72 Avenue indicates fill has been placed over this site. We are unable to 0 / determine if the fill was placed in accordance with Appendix Chapter 3. A. FiII placed on the property which is to support the foundation of a building shall be placed in accordance with accepted engineering practice. Submit a soils investigation report and a report from an approved testing agency C of satisfactory placement of fill [OSSC, Section 3301.1]. Complete the enclosed Soils Special Inspection form designating an D Approved Testing Laboratory [Line B] and signed by the owner of the project [Line D]. i. The completed form must be returned to this office before a Site permit can be issued. ii. Copies of all special inspection reports shall be filed with this office continually during construction [OSSC, Section 3305]. iii. A final signed report must be on file before an occupancy rn certificate will be issued [OSSC, Section 3318]. V . Catch basins shall be trapped by using the inverted one - quarter bend or welded baffle. Provide catch basins constructed to OPSC, Section 1108 specifications. Submit revised plans with details and specifications for the Lynch -type catch basin. The design shall be in accordance with OPSC, Section 1108 �/ _ requirements. . The pipe size from the new catch basin is not adequate to handle volume /area. Provide not less than a 6 inch pipe at a 1 percent slope. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 r. Duncan Building Site Plan Review PC #: 2 -34c SIT #: 99 -0006 Page . The pipe size from the junction of the catch basin lateral is not adequate to handle the volume of the parking lot and roof drainage. • Provide not Tess than an 8 inch pipe at a 1 percent slope. 6. �rm drain piping size and slope continuing down stream of the junction of all new roof drains shall be no less than an 8 inch diameter with a 1 percent slope. Plans show an existing 6 inch storm drain receiving flow from this project. There is some confusion as the sanitary sewer line is shown as 8•inches along the line. 7. What is the direction of flow at the connection of the sani -sewer to existing. Reverse flow? / Correct detail reference shown on Sheet C1.5. f IB SILI� �yt as � y , `t°� a Ij/'� a.� .,e ,/ � �,,,� :� ., .� «�v�,. ,., �..•° � u.. ?'".„ � �. ._ ...'� �. .!,,,� ice. � igns placed at accessible parking shall be mounted 7 feet 0 inches from the ottom of the sign to finish grade. A. Provide current literature on signs, The second exterior stairway exit from the 2 floor shall be connected to an accessible route leading to the public way (OSSC, Section 1106.2.4). =FIRE AND�LIFgirk ETY ' �, � , l ` K ell �'... �a.�.,�.5 . � +i',<.� N;.�� :< ,,� .,.r;,a n ., x ; %,,,ur w k*, .: .. ..'�,.'.. �.,r,. /a, ,,......,.. �,� -i '�^ v„ s,.,,, ,�,t�s,�d`Jd2l 1. No building . shall be constructed, altered, enlarged, moved or repaired in a manner that by reason of size, type of construction, number of stories, occupancy or any combination thereof, creates a need for a fire flow in excess of 3,000 gallons per minute at 20 psi residual or exceeds the available fire flow at the site of the structure [UFC, Section 903.3]. A. Provide Fire Flow Testing pursuant to NFPA 291 using the enclosed "Hydrant Flow Test Report Form." B. Complete the enclosed "Fire Flow Work Sheet" and return to the City of Tigard, attention Plans Examiner. - Note: These documents shall be on file before a building permit will be issued. Please submit three copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 =4171 if you have any questions. Sincerely, A Jim Funk PLANS EXAMINER m aprm sysldocumentls it99_00.06\pc234c. doc Revised November 12 1997 REQUIRED FIRE FLOW WORK SHEET (TO BE USED WITH FIRE FLOW CALCULATION INSTRUCTIONS) GENERAL INFORMATION Fire Dept. Use Only 1) BUILDING NAME: FMZ / 2) BUILDING ADDRESS: CITY /CO 3) TYPE OF STRUCTURE: (Check 1'Box) ❑ IFR,II FR Cl II One Hour, III One Hour ❑ IV Heavy Timber, V -One Hour ❑ II -N, III -N ❑ V - N 4) TOTAL BUILDING AREA: .Sq Ft 5) TOTAL FIRE AREA (Flow Instruction Section 4) : Sq Ft Use the largest aggregate floor area of all floors including mezzanines as defined by UBC Section 407 floor area. Use the three largest successive floor areas for Types I and II FR construction. 6) Building Fire Flow (Flow Instructions Sec. 6): GPM 7) DESCRIBE FIRE AREA :* * If there is more than one fire area in the structure, include (attach) a diagram on 8 -1/2 X 11 or 11 X 17 paper indicating areas. CALCULATING REQUIRED FIRE FLOW Complete line A if the building has only a single occupancy hazard. Skip to line B if the building has multiple occupancy hazards. Round off calculations to nearest whole number. NOTE: THE REQUIRED FIRE FLOW IN LINE A, B OR C MUST BE AT LEAST 1,500 GPM AND CANNOT EXCEED LINE D OR 3,000 GPM. CORRECTIONS WILL HAVE TO BE MADE IF THE CALCULATED FLOW EXCEEDS LINE D OR 3,000 GPM (See Fire Flow Calculation Instruction Section 5 for explanation) A) SINGLE OCCUPANCY HAZARD: Describe Type of Occupancy X = Building Fire Flow Occupancy Factor Required Fire Flow (Line 6 Above) (Instructions Sec 7) (gpm) • B) MULTIPLE OCCUPANCY HAZARD Use the following when a single fire flow area contains multiple occupancy hazards. Each occupancy will be broken down as a percent of the total fire floor area they occupy. The fire flow for each occupancy will be calculated by multiplying the occupancy factor, fire flow and the percent of the area that the occupancy occupies. Add the fire flow of all occupancies together to obtain the required fire flow for the building. Determine % Building Area Occupancy Fire Area % of Building (sq ft) Fire Area 1. Light Hazard Occupancy 2. Ordinary Hazard (Group 1) _ 3. Ordinary Hazard (Group 2) 4. Extra Hazard (Group 1) _ 5. Extra Hazard (Group 2) _ TOTAL 100% Calculate Fire Flow Building Occupancy Factor % Building Fire :Flow Fire Flow (Instructions Sec 7) Area (Line 6 (gpm) Front of Page) 1. Light Hazard 1.00 X % X _ gpm = 2. Ordinary Hazard (1) 1.20 X % X gpm = 3. Ordinary Hazard (2) 1.30 X % X gpm = 4. Extra Hazard (1) 1.40 X % X gpm = 5. Extra Hazard (2) 1.50 X % X gpm = REQUIRED FIRE FLOW = C) REDUCTION OF FIRE FLOW (Fire Flow Instructions 5.13.3) The fire flow from calculations A or B may be reduced by using only one of the following formulas. The formulas are the reciprocal of instructions from Section. 5(B)(3). Please circle the appropriate formula a. Multiply Line A or B by 75% for full fire alarm or b. Multiply Line A or B by 50% for automatic sprinkler protection or c. Multiply Line A or B by 25% for central station supervised automatic sprinkler protection X =_ Calculated Fire Flow Reduction Factor Total Required Fire Flow (From A or B above) (Listed Above) D) AVAILABLE FIRE FLOW TO THE BUILDING: Please provide actual flow test results used in engineering calculations for estimating flows. CITY OF TIGARD, OREGON :..,.: Hydrant Flow Test Report Location: Date Test Conducted By: Time Representative of: Witness: State purpose of test: - Consumption rate during test: Pumps used in test Yes ( ) No ( ) How many? Hydrant Flows: A/1 A/2 A/3 A/4 Nozzle Size: Pitot Reading: Discharge Coefficient: gpm Static: B psi Residual: B psi Projected results 20 psi residual gpm or ® psi Residual gpm Remarks: Location map: Show line sizes and distance to aert cross connected line, Show valves and hydrant branch size, Indicate ( NORTH), show flowing hydrants - Labels A/1 - A/2 - A/3 A/4, show ration of static and residual - Label "B^ Submit this form to the City of Tigard Building Department. "ATTN" Plan Review. 13125 SW Hall Blvd.. Tigard. Oregon 97223 - (503) 639 -4471 CITY OF TIGARD A Program for Inspection Services and/or Material Testing Date: 2- - ,19 City of Tigard: Plan Ck. No. 2 - y C Bup No. Sit No. 79 - 7 ,i Project Title: j] n ( 1) 1 Address / Z / 3 S r hv, 4- ✓., Architect of Record Ph. address: ll Structural Engineer of Record: 72( cU /I C t Ph. address: F v v� ' 237p r/ c r. Geo- Technical Engineer of Record: Ph. address: Provide the following information for the testing agency chosen to provide inspection services and/or testing. Testing Agency: Ph. Fax. address Geo - Technical Agency: Ph. Fax. - address The owner certifies that the above noted Agency has been employed to conduct the special inspections or observations required herein. Signature of Owner Phone No. Date Print name Company name The following is a list of special inspection and/or services required by the 1996 Oregon Structural Specialty Code and Tigard's Municipal Code 14.06.010 through 14.06.040. The special inspections and/or testing services required for this project to be provided by the Testing Agency, Structural Engineer or Geo - Technical Engineer of Record are as follows: • Special Inspectors for the Testing Agency shall be qualified, to the satisfaction of the Building Official, for inspections of the particular type of construction or operation. • Special inspectors shall observe the work assigned herein for conformance with the approved plans and specifications and, submit copies of all inspection reports and, a final signed report in accordance with OSSC, Section 1701.3 to the building official. • Categ41ry 11:1• #aBy P Ye s TNo 1. Footings adjacent to slopes steeper than 33 -1/3 % OSSC, Section 1806.4 a. Confirm building footings are properly set back from descending slope b. • 2. Grading OSSC, Section 3309 a. Regular grading [less than 5,000 cu. yds. but considered unusual] * * Requirements for engineered grading apply. b. Engineered grading [exceeds 5,000 cu. yds.] \ / Submit: 1. Geo-technical engineers report and, 2. a engineering geology report. 3. an as -built grading plan and, 4. a final report prepared by the soils engineer and, 5. the final report prepared by the geologist. �( C. �1 j v << ��� c e J �s� e 1 I /." .' \ 3. Fills OSSC, Section 3313 a. Preparation of ground. for fill on slopes exceeding 1 to 5 (20 %) Includes benching and proper termination at the toe of the slope • b. Acceptance of fill materials C. Compaction of fill material to minimum 90% of maximum density. • • 13125 SW Hall Blvd., Tigard, OR 97223 [503] 639 -4172 FAX [503] 684 -7297 I:\IlLDG\SPLINSP I.DOC SITE PLAN REVIEW COMMENTS CITY OFTIGARD Community Development S(rapingA Better Community • Date: Stmt Person Commenting: ` j cD f g ¢/4 /o J< Department: / 4w PhoneNumher /Extension: 'V07/ • Project Name: /�v�� �, lAkr<. A2ze/ociir_ a cic/ a Site Permit No Land Use Case File NMI: SAIQ 5'R- 002 THE PROPOSED PLANS SUBMITTED ' FOR A SITE PERMIT HAVEBEEN REVIEWED : BY OUR DEPARTMENT AND.WEHAVE THEFOLLOWING COMMENTS ❑ Plans are approved. All land use conditions related to this department have been satisfactorily met. EK Plans are generally consistent with the land use approval, but there are still land use conditions that must be met prior to release of the site and /or building permit, or prior to a final buildinp inspection. Specifically, 054" �U6;- ✓�,1`1d 6 %4/,',^/ fr�N' ��r'IY'/J�;7 C� iv,l;� 1d,4$3 ❑ Plans are NOT consistent with the land use approval and must be revised. Specifically, ❑ Revised plans are approved. NOTE: IF THE PERMIT APPLICANT HAS ANY QUESTIONS WITH REGARD TO THE COMMENTS ABOVE, THEY MUST CONTACT THE STAFF PERSON SPECIFIED AT THE TOP OF THE PAGE. is \brianr \masters\si teplan.frm 10:• right 1 Si. a C 3 +7S t> ' MH I Elevation 14O.S1 (OM Oat".) : :d�:;� !31.37 Morn A i� . r ' , • It*S. "Lt. af d • 1ta 2 �dl..fa) V' Mti''1 sf , I 4464. f1 Mom A C 9c /ocarc fence bCYween aPprdX. b ti p desrynated , � , . . : . 0.437IMain A . ; 0 o f g Std 9.eZ /1) u J fit. 6.7 fo 7.00 as 5-::1 ;. ]Yee (f) yp. ' U by the envatecr / r ... ele9:n COw. T rrct r/ ( / 1 '� 117 \ - ' . N ',- av , /��‘i�/‘"v'iu"'•% \\1r,r'" Fonno Crack (43. 63'Lt. of Q Sty -11.32) 17 m • 4 1 . k I3r • / 4 o 46'. 4 0 /d • 41 i r-IQ000// O., �C} {,• T D� : � /�/�������� 42 /. MarnA a y+ • 3+535 O u . :.., . J" 1 /4.71.52 d . S'C O +, /QO II I)Q. • i• r I 1 9s it!' • .- - � , 6 •s3.9 7 - , 7+/ M441.57 Sa/U 3doneek . T. 6.6 Durham Rd. l /� . . ' � 0 g •. - -- 1� � - 1:% �:� ® 011;3 H i 3 �/ I 42'Cbne. . �>r�s io.IN/ : • { 7 .. S Rip fbp � _- I Du i $ I fia F es "' _ ' ,< Ossn T.zo.4/) T( Ol /) •r A' 5?).e X21✓ ., I I _ -r l' , i 6 ' � (17 ; 0.42.72 cf. o Ex/sr. pv/nY '� o ` "" T ; i ' , ( a - �` , d "' R; a7v' V IA _ • : 4:� ^ : sa 6.9410 /� 1 r - „'' PLAN • •,.ti. 4.;., Tapir TO match ,(4,0.60 SMC 1/ppriGm•.asFrrzy Iii.. 1 / ` 4,- O //eh ro cui0 C reey . ex t' . pv rs'r O.,0a Access Rd EatA /i O.el.81 9 fr 6.40'35 ,r_ 1 / 0.9426 % / R.70 ` Consi ox. 90' of rove/ d /. -'y • . /5. 18.0E \ % % /6' wale orppro'7SS fn matcgh tarty. drrrarny p / 1 / ,% N• 4� of /f 0 Crushed rock an , ■ I > PLAN % Ca ms rruc tad sect a - - SCALE,'" gp' i (L orne rt e' r s ., t .� a a ^ p 6.02'2' �� tE' •_ 1 r � e �1'COnC. R' M q + A• /10' 1.. 1 - doze_ r I 0 �,c1 •., , a T • 1 70 C. la 2 v 3 i �, k Ni ` R p Rap not /t ss than / Cu. ff. v 0 O ' i la 01 , / . Ar arch ex/st s /ops 0 4 is .3 'T _ C j 0 k i d N q r V C h �n.,,�1.. /� ' -� /• 3 Y , � .. r V s p h - 1 0 O -� c. r Grare/ dame way " grade /50 � _ / b= f N 0 m oo " 4 I 4 T r b a 4 o �j n n o o c h I i go° 6 '' N, C 't 11 1 o n o ° N a h 11 c : Z t ' 5 5 0 • 1 A 4 , N Top of Curb Al ' P ROFI L E $ l' w e ; a °o -a ' + I I I Future curb Hs • • :a !; 42 CONC. PIPE SPECIAL RIP RAP DETAIL i w h • %;.1 ,•o ° • $' ° o / "T T Cur b z ': SCALE. I "•6' 3 / s 000s /40 ti• I I EY r st. 9 r ound C , 1 1 O HO • X N �� " . ' MI �.1•'.:Sr. Tfin /38. SO MOrn .'',. •, ' 135 � C - � _ ` J � 1 Exist. 9raund 1 _ i MAIN A r , r • • , C 17 E ic p t I l - IF IF �n rs40° Let A-! _ _ /!S /. 1 16(IirrMyflo II f C -16• o � /f,� V • y ; /sw I I 11' G} a O 1 r� 8 1- I. T A J r g : .+- 130 ^ q / / ' _ - ,••• ! d ' 1 p a a 41 41 _ arable, driveway grade _ISO _ aj = Y I Verity sArr. 1 s v 41 n N ., h 5 I i ` - `' I Zi /n /tilde IT /A /1'G.00 CC • * r • r z ,, ,. , 115 - .. 1 . .. R 1 - ZE4ut /17,80 �Cput /1700 0 r ' T o p of curb -p `g o N Fie 7 curb HS J- i • C' i1 Si1Z149 _ I I 5•x01 To of curb 3, 1 I ( C s•o.005 p q„';t /20 C -16. u•3 _ ' /40 , ` 2 ,.0. , SE in 122.170 . P t i +•,t, Z6 Oat /11.30 L o %.+r %t f jockedprfao 4r Cas /ny i • /,!•.arty of Anna sun bid /tent - RAILROAD (INDERCROSS/NC Exist. 9ro� _ , I ZE //e.00 I MAIN A &, (3ss der,a //s 1Awf >!r /!4 j no' [ y cgs to - . a r pa w a : 11 r ``#! a.00 /.00 s.00 l.ao i.oa sao PROFILE ti edam. ,. SCALErHaiz. "• g01 a c ! .A=; I Vert I'•5 4t 1 0,44- ? ` � t ii' 60 55 ' 4+00 500 .. 6+00 7.00 II %A V' ' ` / 44 44 ; i 1 - . • ,, ' I � ' 0 1.0 2.00 PLAN REDUCED TO • • . � .• ONE-HALF ORIGtNAL SCALE • 4'.? '4-, omarl® krrgov® ® 1. 81NAAS ASSOCIAT 1. INC. STREET P ROFILE S W 72nd AVENUE AREA PLAN j iN4� CONSULTING ENGI i SURVEYORS DURHAM RD. C500 to C 7418.81 I5 Arrcce