FIELD INSPECTION REPORT
BY:
DATES COVERED: March 22, 2000
PROJECT: Duncan Building
ADDRESS: 16135 SW 74th, Tigard, OR
INSPECTOR: G. Seamster ICBO #5006921 -85
03- 22 -00: CTI representative was onsite and the following was noted.
1. Observed the placement of (16) 5/8" x 5" long epoxy dowels into exterior CMU wall for
south and east wall balcony landings ([8] at each landing). Dowels achieved a 4"
embedment, and were cleaned with a brush and compressed air. Epoxy used was Hilti
Hit Hy 150 batch #100501 and expires 7/00. Epoxy was applied in accordance with
ICBO and manufacturer's recommendations.