Report 6 n /0, 00
November 30, 2010 zryivid.4
MIpAqtg
City of Tigard
RE: TENANT IMPROVEMENT
Project Information
Building Permit: BUP2010 -00246 Construction Type: 2 -B
Address: 6600 SW Hampton St. Occupancy Type: B
Area: 43,720 Sq. Ft. Stories: 1
Name: Quest Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2010 edition; 2010 Oregon Fire Code. Please respond to conditions below.
1) Uniform Load required in Table 1607.1 OSSC for light storage is 125 psf.
2) Combustible material is not allowed in Type II construction.
3) Size of joist and beam shall be calculated with a 125 psf uniform load.
4) Please provide breakdown of required restroom facilities as required by Table
29 -A OSSC and accessible stalls as per Chapter 11.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please use a copy of the
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard
in tracking and processing the documents.
Respectfully,
Ban Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.639.4171
TTY Relay: 503.684.2772 • www.tigard or.gov
•
1221 Second Avenue t: 206.381.6000
Suite 200 1: 2.06.441.4981
Seattle. WA 9810! www.perkinswill.com
P E R K I N S
+ W I L L
December 3, 2010
Dan Nelson
Senior Plans Examiner
13125 SW Hall Blvd.
Tigard, OR 97223
Re: Quest Tenant Improvement; Building Permit BUP2010 -00246
Dear Mr. Nelson
This letter is in response to the conditions noted in your review of the permit drawings for the
Quest tenant improvement. The four conditions from your review are itemized below in italics. The
corresponding responses follow in bold font.
1) Uniform Load required in Table 1607.1 OSSC for light storage is 125 psf.
The primary use for the mezzanine is roof access and miscellaneous storage. The use is not
classified as storage warehouse. Signage will be provided at the base of the stairs and at the
entrance to the mezzanine stating a maximum of 40 psf of live load.
2) Combustible material is not allowed in Type II construction.
The project is type III B which does allow combustible material. The error has been corrected on
the revised permit drawing sheet LS -010 provided for your reference.
3) Size of joist and beam shall be calculated with a 125 psf uniform load.
See response to item 1) above.
4) Please provide breakdown of required restroom facilities as required by 29 -A OSSC and
accessible stalls as per Chapter 11
The breakdown of required restroom facilities as required by 29 -A OSSC and accessible stalls are
noted on the revised permit drawing sheet LS -010 provided for your reference. The existing
conditions comply with these code requirements.
Sincerely,
•
Devin Kleiner
Perkins +Will
P: \Seattle \161019.000 QuestDiagnostics \DOCS \05.0- AgencyCorrepondence \05.01 - LocalAgency \5.1.2 -
LocalBldgCorresp \Permit Revisions Cover Letter.docx