Correspondence August 29, 2000 *Al ;,,,,
ii
CITY OF TI G-/ s
Climate Control OREGON
16500 SW 74
Portland, Oregon 97224
RE: Cognex
15865 SW 74th Mechanical Permit # 2000 -00340
Your plans have been reviewed for compliance; the following items require your attention.
1. Provide Oregon Non - Residential Energy Code forms 4a through 4j.
2. Provide outside air calculations based on table 12, OSSC Chapter 12. Show on plans
placement of grills and CFM capability.
3. When using the economizer for outside air requirements, you must shown how the
economizer will close when the building is not occupied.
Provide two (2) sets of revised drawings.
If you have questions, please call me at 639 -4171 X 392.
Sincerely,
'-‘
Ro.ert Poskin, CB()
Senior Plans Examiner
EXPIRED