RE: Meyer Building Building Plan Review
15205 SW 74 th
PC #: 12 -35c SIT #: 99 -00077
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1998 Oregon Specialty Codes and other applicable
codes and standards.. The follotiving comments are noted:
S IE Qa » ., { Weg �� p �a s
X The storm drainage plan shall adequately address the number of catch basins
required to handle the parking lot and hard surface runoff. The Uniform
Plumbing Specialty Code [UPSC, Section 1108] allows a maximum 6" outlet on
each catch basin, and Table 11 -2 limits the maximum surface area one catch
basin can serve to 7,133 square feet at 1% slope of the horizontal line from the
catch basin. Additional catch basins are required to adequately serve the area.
Sizing of all storm drain piping is determined by OPSC, Table 11 -2. If an
engineered system is to be used in lieu of a table 11 -2, two sets of plans
stamped by an engineer licensed in Oregon and the hydrodynamic calculations
must be submitted for review and approval.
2. Provide details and specifications for erosion control. Include a gravel driveway
approach, storm drainage protection and location of silt fencing. Contact
Washington County Unified Sewerage Agency, at 799 -1639, for their technical
guidelines.
3. Provide details and specifications for erosion control. Include a gravel driveway
approach, storm drainage protection and location of silt fencing. Contact
Washington County Unified Sewerage Agency, at 799 -1639, for their technical
guidelines.
4! The parking stall north of the dumpster impedes fire department access.
Remove.
�- r � as ..✓y -w.r d -_:. � 6 ; t r. j ^ � "�y ", ' "x y " ��'
fACCESSIBILITr1( k zw f, um,,
.oz �+xe.� A .4 :6?' ; G ,x.r,. �7: . ,�- 3t� ' s.. arzYr''�m .^a �` kKA b- � ,a �4' :V: n 'e i� '.s ,F «. -kft i,
1/ Based on the building footprint, two (2) exits will be required. Show how the
second exit will connect to an accessible route to a public way.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Meyer Building Building Plan Review
PC #: 12 -35c BUP #: 99 -00077
Page #2
OE :b TECWHNIC*L INUESTIGATIOIV FtEP ittI W ;p
•
1. Based on the Geo- Technical Report concern for the lateral displacement, we will
require a letter from your Geo - Technical Engineer that he is in agreement with
your structural engineer's foundation system design. This letter shall accompany
your building permit application. OSSC, Section 1804.
.> .
1. An elevator will be required for the second floor. See OSSC, Section 1108.3.1.1.
Exception 1.6.
Please submit three copies of revised submittai documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
c.461
�✓lv -rte
Robert Poskin, CBO
SENIOR PLANS EXAMINER