Correspondence C 54 TD FedA HI-We— 2 - Z - b5 ) (y` P HA 3,4NCs) Lice • 4 40 6 CITY OF TIGARD OREGON • February 2, 2005 John Barnes Frahler Electric 11860 SW Greenburg Rd. Tigard, OR Dear John, Here are the deficiencies in the revised plans for the Meyer Sign service changes (permit No. ELC2005- 00032): 6. The plans still don't show a complete grounding detail. It needs to show the bonding of all electrodes available on the premises, per NEC 250.50 and 250.52. It needs to show the grounding electrode conductor as run continuous per NEC 250.64 or per OAR 918 - 305 -0160. Simply making a note, "grounding per NEC" is not sufficient for plan review. Questions: * What are the electrodes available on the premises? Show each one and its bond wire. * Are you using the copper bar system that Oregon allows for the grounding electrode bonds? If so, show it. If not, show each G.E. bonding wire. 7. On page El- are keyed notes 1 & 2 a part of this permit? If so, they are not shown in the fees paid. If not, please remove them from the drawings. Please resubmit two sets of revised drawings. Sincerely yours, Kim Appleberry 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 4 1,110 N CITY OF TIGARD OREGON January 24, 2005 • John Barnes Frahler Electric 11860 SW Greenburg Rd. Tigard, OR • Dear John, Here are some comments on the plans for the Meyer Sign service changes (permit No. ELC2005- 00032): Go /{- 1. New service equipment shall meet the access and working space requirements of NEC 110.26 and shall not cause the existing equipment to fail to meet these same requirements. 2. New service shall comply with NEC 250.24 (grounding). eo q 3. The equipment labeled "Thermoformer" and "controller /aux. equipment" will need to be certified (per ORS 479.610 [Electrical Safety Law]) unless it qualifies as exempt industrial electrical equipment under ORS 479.530(14) and 479.540(13)(a). 4. The plans will need to show the number and size of the service entrance conductors and service entrance.conduit(s). 5. The service entrance conductors must include a grounded conductor per NEC 250.24(B). 6. The plans will need to have a complete grounding detail showing (1) the bonding of all available electrodes per NEC 250.50 and (2) the grounding electrode conductor as run continuous per NEC 250.64 or OAR 918 - 305 -0160. Please resubmit two sets of revised drawings. Sincerely yours, Kim Appleberry 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 i y A February 7, 2005 CITY OF TIGARD Frahler Electric OREGON 11860 SW Greenburg Rd. Tigard, OR Electrical Permit: ELC2005 -00032 Property Owner: Meyer Sign Address: 15205 SW 74 Ave. Plans Dated: January 7, 2005, Revised February 4, 2005 The plan review was performed under the Oregon Electrical Specialty Code(OESC) 2002 edition which includes the 2002 edition of the National Electrical Code (NEC). The submitted plans are approved subject to the following conditions: 1. New service equipment shall meet the access and working space requirements of NEC 110.26 and shall not cause the existing equipment to fail to meet these same requirements. 2. Equipment must comply with NEC 110.9 (...interrupting rating sufficient for the available fault current...). You are reporting the available fault current to be 47,395 amps. 3. Grounding electrode bonding jumpers and common copper ground bar to be installed per OAR 918- 305 -0160 (Oregon Electrical Specialty Code). 4. The equipment labeled "Thermoformer" and "controller /aux. equipment" will need to be certified (per ORS 479.610 [Electrical Safety Law]) unless it qualifies as exempt industrial electrical equipment under ORS 479.530(14) and 479.540(13)(a). 5. Approved Plans: One set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. Sincerely yours, Kim Appleberry 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772