- CONNECTEEr DIVERSITY al LOAD TYPE KW , FACTOR , r
■
LIGHTING 14.1 _ 0.9
RECEPTACLES 36.1 0.1
3- PHASE TRANSFORMER PAD - 1 WATER HEATING 2.5 0.2
CONDUIT CONFIGURATION ELECTRIC HEAT 0.75 .
(TOP VIEW) 6'4' REFRIGERATION / AC 9.0 0.75
TRANSFORMER PAD MOTORS - 52.0 KW -
Air''''''''' MSC MISC 10.0 KW . -
OPENING IN PAD .,- -
TOTAL FST. OEM AND , - 124.30
4" PRIMARY
• CONDUIT ." -----
• - 1 - - Tsr'aaa. - -.- - --
,_____ - CALL BEFORE YOU DIG: OREGON LAW REQUIR
` 48 HOURS PRIOR TO EXCAVATION. FOR LOCATES
SI/ � / ���
II CENTER AT 503 -246 -6699 OR 1 -800- 332 - 2344.
MISTS CONTACT GENERAL FOREMAN 7 TO 10 WO ' DA
CONDUIT INSPECTION REQUIRED PRIOR TO L., „IRA
TO OUTSIDE
PGE WILL NOT INSTALL WIRE UNTIL TRENCH IS 100
OF COMM FRONT OF PAD RICK BEEKS EXCAVA
GENERAL FOREMAN CONTAC
—,- 2' MIN. BETWEEN .— PHONE: (503) 570 -4431 CELU 572 -7318 PHONE
NEAREST PRI & SEC CONDUIT STREETLIGHT SPECIALIST : .JEFF STEIGLEDER SER'
PHONE: (503) 510 -4404 CELL: 849 -6548
02/07/2005 16:17 FRAHLER ELECTRIC COMPANY 4 95036243681 NO.720 P02
COMMERCIAL LEGEND
PAO *00056 NEW PaLACILITIES TO BE INSTALLED
LL 7200Y : (UNLESS OTHERWISE SPECIFIED)
% 75 30
6'x6' TRANSFORMER PAD, INSTALLED BY CUSTOMER
Q FAULT INDICATOR - 450 AMP
Ili INSTALL CUTOUT
SIZE FUSING AS NOTED
INSTALL 4" POLE CONDUIT UNIT
WITH 12" BRACKETS, INSTALL E3 - AL JKT PRIMARY IN 4" PVC CONDUIT
3 -142 C/O FIOT PROVIDED & INSTALLED BY CUSTOMER
& LIGHTNING ARRESTER INSTALL I-W350 AL-OX SECONDARY IN 2 OF 3-4" PVC
COMM' PROVIDED A INSTALLED BY CUSTOMER a SPARE/
CONSTRUCTION NOTES: COM
CUSTOMER IS RESPONSIBLE FOR ALL TRENCH, CONDUIT, VAULTS. PADS AND
ROAD CROSSINGS.
2. ALL CONDUIT TO BE INSTALLED 36 INCHES 1491) BELOW FINAL GRADE.
3, ALL PGE CONDUCTORS TO BE INSTALLED IN GRAY, SCHEDULE 40. ELECTRICAL
GRADE, PVC CONDUIT WITH NYLON PULL STRINGS BAEN. 500 LBS. TEST).
PGE TO DETERMINE THE SIZE AND NUMBER OF CONDUITS .READ,
MAINTAIN 12 VERTICAL INCHES AND 24 HORIZONTAL BICCES CLEARANCE BETWEEN
GAS AND OTHER UTILITIES. ALL ELBOWS TO BE 36 INCH 000 RADIUS.
ALL BENDS MUST E FACTORY MADE. CONDUIT RUNS LONGER THAN I50 FEET
OR WITH MORE THAN 270 DECREES OF RENDS MUST USE RIGID STEEL ELBOWS
AND MUST BE APPROVED BY PGE PRIOR To INSTALLATION BY CUSTOMER.
WR CHECKLIST 4. ALL
ANDD FEET�NMIHFROM HYDRANT Arm Mils •
ITEM NO YES BE WITHIN 15 FEET OF A DRIVEABLE AREA. ALWAYS MAINTAIN 10 FEET CLEARANCE
BV FRONT OF 'ALL TRANSFORMERS.
,HOLEDIGGER X 5. TRANSFORMER PADS ARE TO BE SET S0 THAT THE TOP IS 2 INCHES ABOVE
4ATED BOOM X FINAL GRADE. CONDUIT IS TO BE INSTALLED IN PAD AS INDICATED IN DETAIL
IAND GAMMM x AND TO EXTEND I INCH ABOVE THE PAD.
PGE TRH x 6. STEEL BARRIER POSTS ARE REQUIRED AROUND TRANSFORMERS THAT ARE EXPOSED
LOCATES % TO VEHICLES,
STAKING g T. PGE TO BE NOTIFIED AND INSPECT ALL CONDUIT, VAULT AND PAD INSTALLATIONS
BEFORE BACKFILL.
— FLAGGING x
TREEttli x B. REFER TO LETTER OF RESPONSIBILITY FOR FURTHER DETAILS AND THE OREGON
ELECTRIC SERVICE REQUIREMENTS BOOKLET FOR SPECIFIC REQUIREMENTS.
EASEJIENT g
PERMITS % E9, DESIGN IS BASED ON STANDARD UNDERGROUND EOIPIIENT. NON- STANDARD
UNDERGROUND EQUIPMENT 15 AN OPTION AT AN ADDITIONAL COST TO THE CUSTOMER.
CIJTSHEET x
www.PortIQndGeneral.com www.TownPcrtnor.com www.EarthAdvontage.com
—�— JOB NO. DATE SECTORS) SCALE
YOU TO REHIUEST UTILITY LOCATION. 255052 9/16/2002 1 C21 -120 1' =80`
LL THE OREGON UTILITY NOTIFICATION
/44444.4\ DURHAM — BONITA SrcE 11x17
s ' R TO EXCAVATION. MEY SIGN Co -
BA LF.Q. LOCATION •��'•�
15205 SW 74TH AVE, TIGARD
iN COr DEsCRIPT1oN 'sI1EET
N►tLSONVILLE _ INSTALL UG SERVICE TO COMM BLDG
LINE CREW CENTER DEGN BY PHONE 15031 DRAWN BY 1 OF 1
E INSPECTOR: 9480 SW BOECKIIAN RO MICHAEL STRUBELL 570 -4409 R. CAMPBELL _
WI SONVILLE. OR 07010 ID PORTLAND GENERAL ELECTRIC CO. - ALL RIGHTS RESERVED