Loading...
Plans Yi I?--qi /� ' t TUALATIN VALLEY FIRE & RESCUE 1v °eta �y AND BEAVERTON FIRE DEPARTMENT s 4 �`' } 475 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, OR 97076 • • FAX 526 -2538 & •, •,/ (503) 52b -2s169 ti RF &R E S G., ` August 1 1994 Nicoli Engineering P.O. Box 23784 Tigard, Oregon 97223 Re: Skourtes Warehouse 14975 S.W. 74th Avenue 6190B- 170 -000 Gentlemen: This is a Fire and Life Safety Plan Review and is based on the 1991 editions of the Uniform Fire Code (UFC) and those sections of the Uniform Building Code (UBC) and Uniform Mechanical Code (UMC) specifically referencing the fire department, and other local ordinances and regulations. Plans for the above noted building cannot be approved at this time. Please revise the following and resubmit for review and approval. 1. Hydrants were not noted on submitted plans. Hydrants shall be located so that no portion of the building is greater than 250 feet from a hydrant measured around the outside of the building and along access roadways. If building is provided with automatic sprinkler protection, then the hydrant may be extended to as much as 500 feet provided the Fire Chief believes adequate protection is being provided measured in the same method as above. Fire hydrant will be required within 70 feet of a fire department connection if the building is provided with automatic sprinklers. 2. This building exceeds the allowable 3,000 gpm fire flow for Type V -N Ordinary Hazard Group 3 (Spec Warehouse) application. Building either needs to be divided with area separation wall in accordance with Uniform Building Code, upgraded type of construction or provided with automatic sprinkler protection. "Working" Smoke Detectors Save Lives PP Nicoli Engineering August 10, 1994 Page 2 3. Approved numbers or addresses shall be placed on all premises in such a position as to be plainly visible and legible from the right -of -way. The numbers on the premise shall contrast with their background and be a minimum of four (4) inches in height. In addition, if the premise is not visible from the right -of -way due to distance or obstacles, the driveway(s) servicing the premise shall be identified by a sign at the driveway(s) and where the driveway(s) enters the public right -of -way. The sign(s) shall be white reflective numbers four (4) inches in height mounted on green background. Sign(s) shall be on the right side of the driveway four (4) feet to six (6) feet high within twenty five (25) feet of the right -of -way and any intersection of the driveway leading to the premises. 4. Not less than one (1) approved fire extinguisher(s) with a rating of not less than ( *) shall be provided for each ( * *) square foot of floor area or fraction thereof. The travel distance to an extinguisher from any portion of the building shall not exceed 75 feet. UFC Sec. 10.505 ( *) 2A10B:C, - Light and Ordinary Hazard 4A10B:C - Extra Hazard ( * *) 3 000 - Light Hazard 1,500 - Ordinary Hazard 1,000 - Extra Hazard Note: Where flammable or combustible liquids are used, "B" ratings of extinguishers may need to be higher and travel distances shorter. See requirements in National Fire Protection Association Standard 10 -1. If I can be of any further assistance to you, please feel free to contact me at 526 -2502. Sincerely, -5A(7.—d_ ill! Gene Birchill, DFM Plans Examiner GB : kw cc: City of Tigard Building Department