Series TY-B — 2.8,f and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, itisoro
D escription is recommended that the end user be 4
consulted with respect to the suitability '_
The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro-
K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi
klers described in this data sheet are p
ent temperature, concentration of /
standard response - standard cover- chemicals, and gas /chemical velocity, , `r>
age, decorative 5 mm glass bulb type should be considered, as a minimum, •
spray sprinklers designed for use in along with the corrosive nature of the ; --
light, ordinary, or extra hazard, com- chemical to which the sprinklers will be
mercial occupancies such as banks, exposed. --
hotels, shopping malls, factories, refin-
eries, chemical plants, etc. An intermediate level version of the
Series TY -B Pendent Sprinkler can be
The recessed version of the Series obtained by utilizing the Series TY -B
TY -B Pendent Sprinkler, where appli- Pendent Sprinkler in combination with
cable, is intended for use in areas with the Model S2 Shield. 4 . :? ,
a finished ceiling. It uses a two -piece & p,
Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS ` 0 ' v
inch NPT) Recessed Escutcheon. The The Series TY -B Sprinklers described
Recessed Escutcheon provides 1/2 herein must be installed and main-
inch (12,7 mm) of recessed adjust- tained in compliance with this docu-
ment or up to 3/4 inch (19,1 mm) of m ent, as well as with the a
P ( ) applicable
total adjustment from the flush pen- standards of the National Fire Protec-
dent position. The adjustment pro- tion Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de-
cut. vices.
Corrosion resistant coatings, where The owner is responsible formaintain-
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler
tained when exposed to corrosive at- manufacturer should be contacted
mospheres. Although corrosion resis- with any questions.
tant coated sprinklers have passed the
standard corrosion tests of the appli- Model/Sprinkler
IMPORTANT Identification
Always refer to Technical Data N umbers
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal- TY1151 - Upright 2.8K, 1/2 "NPT
lation of sprinkler systems and com- TY1251 - Pendent 2.8K, 112 "NPT
ponents. Improper handling and in- TY3151 - Upright 5.6K, 1/2 "NPT
stallation can permanently damage TY3251 - Pendent'5:6K; 1°/2 "NtPT
a sprinkler system or its compo- TY4151 - Upright 8.0K, 314 "NPT
nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 3/4 "NPT
to operate in a fire situation or cause •TY4851 - Upright 8.0K, 1/2 "NPT
it to operate prematurely. TY4951 - Pendent 8.0K, 1/2 "NPT
Page 1 of 8 APRIL, 2006 TFP151
Page 2 of 8 TFP151
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 1/7 ** NOMINAL SSU
. SURFACE NPT MAKE -IN DEFLECTOR 7 4.
t ---,---
: 5
�
2-1/4" — 1 2- 3/16" 4
(57,2 mm)
i ALM1' ' (55,6 mm)
2
1- 9/16" WRENCH 0 3
(39,7 mm) FLATS ,4 ti i II
Y' 1
SSP 7
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
t 5
rr 7/16" �'
2- 3/16" 1�'',� ' ( 11 ,1 m m )
(55,6 mm) =1
I rt NOMINAL 4
-
— MAKE -IN
I I
��
1 -1/2" r ��l a l :..: �� 2
(38,1 mm) , I _
i (556 mm) 0
l # WRENCH 3
1 .- "��. -s -• ..AT FLAT
1
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. – --] 1/2" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
TFP151 Page 3 of 8
ESCUTCHEON 1/2" (12,7 mm) STYLE 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
T____ 5
1/2.. 6�s
iii
6
2- 5/16" �� (12,7 mm)
(58,7 mm) n R i "tie NOMINAL 4
- MAKE -IN
1-9/16" _- � 'r 21/4" pa id 2
(39,7 mm) , _ (57,2 mm) 3 g 1 .1..
WRENCH rA r / 1 °__ ° FLATS 1
` 1
SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. 3/4" NPT ** 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 1/2 ** NOMINAL SSU
SURFACE NPT MAKE -IN DEFLECTOR
f ._--,--..
II ,m S
2 -1/4" 2- 3/16"
(57,2 mm) . A (5 5,6 mm) 4
1- 9/16" WRENCH ,L j 4 2
(39,7 mm) FLATS �
1
SSP
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K- FACTOR, 1/2 INCH NPT
Page 4 of 8 TFP757
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE * ** LEAD WAX WAX OVER
LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
2 (TY1251) 1, 2, 3 N/A
1/2" and 175 °F /79 °C Yellow
NPT UPRIGHT 200 °F /93 °C Green
(TY1151)
286F/141°C Blue
360 °F /182 °C Mauve 1, 2
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3251) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 1, 2, 3, 5 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3151)
286 °F /141 °C Blue 1 ** 2 ** 3**, 5 ** r1 ** 2**, 3**, 5 **
1/2" •
NPT 360 °F /182 °C Mauve N/A
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3251)* 175 °F /79 °C Yellow
Figure 4 200 °F /93 °C Green
286 °F /141 °C Blue 1, 2
•
135 °F /57 °C Orange
PENDENT 155F/68°C Red
(TY4251) 1, 2, 5 1, 2, 3, 5 1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
8.0 UPRIGHT 200 °F /93 °C Green
3/4" (TY4151) -
286 °F/141 °C Blue 1 * *,2 * *, 3 * *, 5 ** l 1 * *, 2 * *, 5 **
NPT
360 °F /182 °C Mauve N/A
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4251)* 175 °F /79 °C Yellow
Figure 5 200 °F /93 °C Green
286 °F /141 °C Blue 1, 2
135 °F /57 °C Orange
PENDENT 155F/68°C Red
g p (TY4951)
1/2" and 175 °F /79 °C Yellow 1, 2, 3, 5 N/A
NPT UPRIGHT 200 °F /93 °C Green
(TY4851)
286 °F /141 °C Blue
360 °F /182 °C Mauve
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03).
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05).
8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed, the
sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** 150 °F /66 °C Maximum Ceiling Temperature.
TABLE A, LABORATORY LISTINGS AND APPROVALS
TFP151 Page 5 of 8
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER
BRASS PLATED POLYESTER COATED COATED LEAD COATED
2.8 PENDENT (TY1251)
1/2" and 175 PSI (12,1 BAR) N/A
NPT UPRIGHT (TY1151)
PENDENT (TY3251)
5.6 and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
1/2" UPRIGHT(TY3151) OR
NPT RECESSED PENDENT 175 PSI (12,1 BAR)
(TY3251) (SEE NOTE 1) N/A
8.0 PENDENT (TY4251)
3/4" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4151)
RECESSED PENDENT
(TY4251) 175 PSI (12,1 BAR) N/A
8.0 PENDENT (TY4951)
1/2" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4851)
NOTE:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York.
TABLE B, MAXIMUM WORKING PRESSURE
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, VdS, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A for complete ap- activate and water to flow.
proval information including corrosion
resistant status.) Design
Maximum Working Pressure
Refer to Table B. Criteria
Discharge Coefficient
K = 2.8 GPM /psi (40,3 LPM /bar1 /2) The Series TY -B Pendent and Upright
K = 5.6 GPM /psis / (80,6 LPM /bar1/2) Sprinklers are intended for fire protec-
K = 8.0 GPM /psi / (115,2 LPM /bar1/2) tion systems designed in accordance
with the standard installation rules rec-
Temperature Ratings ognized by the applicable Listing or
Refer to Table A. Approval agency (e.g., UL Listing is
Finishes based on the requirements of NFPA
Sprinkler: Refer to Table A. 13, and FM Approval is based on the
Recessed Escutcheon: White Coated, requirements of FM's Loss Prevention
Chrome Plated, or Brass Plated. Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable, E
Physical Characteristics is to be used for recessed pendent m
Frame Bronze installations. t=
Button Brass /Copper a
Sealing Assembly
Beryllium Nickel w /Teflont
Bulb Glass
Compression Screw Bronze
Deflector Copper 0
Bushing (K =2.8) Bronze
0
Page 6 of 8 TFP151
2 -7/8" DIA. _ e
. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2.1/4" DIA. 1/4" (6,4 mm) WRENCH RECESS
(END "A" USED FOR
FACE OF ( 57,2 mm) MOUNTING • 1/2" NPT MODELS)
SPRINKLER PLATE '�
FITTING
1/8" WRENCH RECESS
�J' (3,2 mm) (END "B" USED FOR
�l�li 3/4" NPT MODELS)
/✓ % FIGURE 7
� W-TYPE 6 SPRINKLER
e WRENCH
MOUNTING
SURFACE - ,;;=- -,
WRENCH
CLOSURE SERIES 1 -1/4" (31,8 mm) RECESS
TY-B 3/4" (19,1 mm)
SF � l
FIGURE 5
SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT U
STYLE 10 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT �"',
PUSH WRENCH
IN TO ENSURE
2 -7/8" DIA. ENGAGEMENT
(73,0 mm) 3/4" (19,1 mm) WITH SPRINKLER
. 5/8±1/4" WRENCHING AREA
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) FIGURE 8
FACE OF MOUNTING W - TYPE 7 RECESSED
SPRINKLER PLATE SPRINKLER WRENCH
FITTING
1/8"
(3,2 mm) Installation
J . . I
' T he Series TY -B Sprinklers must be
installed in accordance with the follow - � 1�' ing instructions:
MOUNTING NOTES
SURFACE �• r Do not install any bulb type sprinkler if
Y yP P
" - - - - - -- the bulb is cracked or there is a loss of
CLOSURE SERIES 1 - 5/16" (33,3 mm) liquid from the bulb. With the sprinkler
TY 13/16" 20,6 mm) held horizontally, a small air bubble
( ) should be present. The diameter of the
air bubble is approximately 1/16 inch
FIGURE 6 (1,6 mm) for the 135 °F /57 °C to 3/32
SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY tech mm) for the 360F/182°C
WITH TWO -PIECE 3M INCH TOTAL ADJUSTMENT temperratat ure ratings.
STYLE 40 RECESSED ESCUTCHEON A leak tight 1/2 inch NPT sprinkler joint
8,0 K- FACTOR, 3/4 INCH NPT should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40, 7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
Tf:P151 Page 7of8
leakage or impairment of the sprinkler. heated rod, in order to prevent the by brushing it with a soft bristle brush.
Do not attempt to make -up for insuffi installer from being burned. Care must be exercised to avoid dam-
' cient adjustment in the escutcheon age to the sprinklers - before, during,
plate by under or over - tightening the The Series TY -B Recessed Pendent and after installation. Sprinklers dam -
sprinkler. Readjust the position of the Sprinklers must be installed in ac- aged by dropping, striking, wrench
sprinkler fitting to suit. cordance with the following instruc- twist/slippage, or the like, must be re-
The Series TY -B Pendent and Up- tions. placed. Also, replace any sprinkler
right Sprinklers must be installed in Step A. After installing the Style 10 or that has a cracked bulb or that has lost
accordance with the following instruc- 40 Mounting Plate, as applicable, over liquid from its bulb. (Ref. Installation
tions. the sprinkler threads and with pipe Section).
Step 1. Pendent sprinklers are to be thread sealant applied to the pipe Frequent visual inspections are rec-
installed in the pendent position, and threads, hand tighten the sprinkler into ommended to be initially performed for
upright sprinklers are to be installed in the sprinkler fitting. corrosion resistant coated sprinklers,
the upright position. Step B. Tighten the sprinkler into the after the installation has been com-
sprinkler fitting using o the W -Type P to verify the integrity of the cor-
Step 2. With pipe thread sealant ap 7 Recessed Sprinkler Wrench (Ref. rosion resistant coating. Thereafter,
plied to the pipe threads, hand tighten annual inspections per NFPA 25
Figure 8). With reference to Figure 3
the sprinkler into the sprinkler fitting. or 4, the W -Type 7 Recessed Sprinkler should suffice; however, instead of in-
Step 3. Tighten the sprinkler into the Wrench is to be applied to the sprinkler specting from the floor level, a random
sampling of close -up visual inspec
sprinkler fitting using only the W -Type wrench flats.
6 Sprinkler Wrench (Ref. Figure 7), tions should be made, so as to better
except that an 8 or 10 inch adjustable Step C. After the ceiling has been in- determine the exact sprinkler condi-
Crescent wrench is to be used for wax stalled or the finish coat has been ap- tion and the long term integrity of the
coated sprinklers. With reference to plied, slide on the Style 10 or 40 Clo- corrosion resistant coating, as it may
Figures 1, 2, 3, and 4 the W -Type 7 sure over the Series TY -B Sprinkler be affected by the corrosive conditions
Sprinkler Wrench or the adjustable and push the Closure over the Mount- present.
Crescent wrench, as applicable is to ing Plate until its flange comes in con -
be applied to the wrench flats. tact with the ceiling. The owner is responsible for the in-
spection, testing, and maintenance of
When installing wax coated sprinklers � their fire protection system and de-
with the adjustable Crescent wrench, Care and vices in compliance with this docu-
additional care needs to be exercised /Y /a�n &enan�se ment, as well as with the applicable
to prevent damage to the wax coating standards of the National Fire Protec-
on the sprinkler wrench flats or frame tion Association (e.g., NFPA 25), in
arms and, consequently, exposure of The Series TY -B Sprinklers must be addition to the standards of any other
bare metal to the corrosive environ- maintained and serviced in accord- authorities having jurisdiction. The in-
ment. The jaws of the wrench should ance with the following instructions: stalling contractor or sprinkler manu-
be opened sufficiently wide to pass NOTES facturer should be contacted relative
over the wrench flats without damag- to any questions.
ing the wax coating. Before wrench Before closing a fire protection system
tightening the sprinkler, the jaws of the main control valve for maintenance It is recommended that automatic
wrench are to be adjusted to just con- work on the fire protection system that sprinkler systems be inspected,
tact the sprinkler wrench flats. After it controls, permission to shutdown the tested, and maintained by a qualified
wrench tightening the sprinkler, loosen affected fire protection system must be Inspection Service in accordance with
the wrench jaws before removing the obtained from the proper authorities local requirements and /or national
wrench. and all personnel who may be affected codes.
by this action must be notified.
After installation, the sprinkler wrench
flats and frame arms must be in The owner must assure that the sprin-
spected and the wax coating re k/ers are not used for hanging of any
touched (repaired) whenever the coat objects; otherwise, non - operation in
ing has been damaged and bare metal the event ofa fire or inadvertent opera -
is exposed. The wax coating on the tion may result,
wrench flats can be retouched by gen- Absence of an escutcheon, which is
. tly applying a heated 1/8 inch diameter used to cover a clearance hole, may
steel rod to the areas of wax that have delay the time to sprinkler operation in
been damaged, to smooth it back over a fire situation.
areas where bare metal is exposed.
. Sprinklers that are found to be leaking
NOTES or exhibiting visible signs of corrosion
Only retouching of the wax coating ap- must be replaced.
plied to the wrench flats and frame Automatic sprinklers must never be
arms is permitted, and the retouching painted, plated, coated or otherwise
is to be performed only at the time of altered after leaving the factory. Modi-
the initial sprinkler installation. fied sprinklers must be replaced.
The steel rod should be heated only to Sprinklers that have been exposed to
the point at which it can begin to melt corrosive products of combustion, but
the wax, and appropriate precautions have not operated, should be replaced
need to be taken, when handling the if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
Page 8 of 8 TFP151
TY1251
P/N 57 - XXX - X - XXX
I I
SPRINKLER TEMPERATURE
MODEUSIN RATING
530 2.8K UPRIGHT (1/2 "NPT) TY1151 1 NATURAL BRASS 135 135 °F /57 °C
590 2.8K UPRIGHT (1/2 "NPT) 4 WHITE POLYESTER 155 155 °F /68 °C
570 5.6K UPRIGHT (1/2 "NPT) 3 WHITE (RAL9010) * 175 175 °F /79 °C
571 5.6K PENDENT (1/2 "NPT) 9 CHROME PLATED 200 200F/93°C
590 8.0K UPRIGHT (3/4 "NPT) 7 LEAD COATED 286 286 °F /141 °C
591 8.0K PENDENT (3/4 "NPT) 6 WAX COATED 360 360 °F /182 °C
286 °F /141 °C MAX.
560 8.0K UPRIGHT (1/2 "NPT)
8 WAX OVER LEAD
561 8.0K PENDENT (1/2 "NPT) 286 °F /141 °C MAX.
TABLE C
PART NUMBER SELECTION
SERIES TY -B PENDENT AND UPRIGHT SPRINKLERS
any other legal theory, for incidental, ,,/
Limited indirect, special or consequential dam- Ordering
ages, including but not limited to labor
Warranty YY charges, regardless of whether TFBP Procedure
was informed about the possibility of
Products manufactured by Tyco Fire & such damages, and in no event shall When placing an order, indicate the
Building Products (TFBP) are war- TFBP's liability exceed an amount full product name. Refer to the Price
ranted solely to the original Buyer for equal to the sales price. List for complete listing of Part Num-
ten (10) years against defects in mate- bers.
rial and workmanship when paid for The foregoing warranty is made in lieu
and properly installed and maintained of any and all other warranties. ex- Contact your local distributor for avail -
under normal use and service. This press or implied. including warranties ability.
warranty will expire ten (10) years of merchantability and fitness fora par -
from date of shipment by TFBP. No ticular purpose. Sprinkler Assemblies with NPT
warranty is given for products or com- This limited warranty sets forth the ex- Thread Connc Model/SIN), :
ponents manufactured by companies clusive remedy for claims based on Sppee cify: (Specif (specify K -Stand
as
not affiliated by ownership with TFBP failure of or defect in products, materi- Response, t factor
or for products and components which als or components, whether the claim (specify temperature a ra e rati K g), Series
have been subject to misuse, improper is made in contract, tort, strict liability y g theory. TY-B with Pendent n or Upright)
or
installation, corrosion, or which have or any other legal then Sprinkll er r w with (specify type of finish .
not been installed, maintained, modi- coating), P/N (specify from Table C).
fied or repaired in accordance with ap- This warranty will apply to the full ex-
plicable Standards of the National Fire tent permitted by law. The invalidity, in Recessed Escutcheon:
Protection Association, and /or the whole or part, of any portion of this Specify: Style (specify 10 or 40 ) Re-
standards of any other Authorities warranty will not affect the remainder. cessed Escutcheon with (specify *) fin -
Having Jurisdiction. Materials found ish, P/N (specify*).
by TFBP to be defective shall be either • Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56-850-4-001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under