Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
,...., , , ,!\i1cc 91A r 0034 (t° :,,-„,... A as ACCURATE BALANCINGI4EN . B 't'!'1•'' Commercial & Industrial Q Air & Hydronic, Test Adjust ESB #: 3866 • NEBB Certified • CCB #: 64875 CERTIFIED TEST, ADJUST, BALANCE REPORT FOR Project: LCCS1@ Washington Square Location: Tigard, Oregon Engineer: Not Listed HVAC Contractor: A- Absolute Comfort Heating Me-C zv)o -- Od fit/ i me. e NEBB Cert #3177 P.O. Box 653 • Beaverton, OR 91075 • ABA@ABAinc.US • (503) 297 -6594 • (5031292 -4825 fax ° B Table of Contents Project Location: CCS @ Washington Square - Tigard, Oregon Page # Table of Contents 1 Certification 2 Terms and Abbreviations 3 Instrument Calibration 4 General Remarks and Summaries 5 FPB Test Report 6 Air Outlet Test Report 7 Indexed Floor Plan Accurate Balancing Agency, Inc. Page 1 of 7 Supervisor: Edward M. May Jr. ' B Certification Project Location: CCS @ Washington Square - Tigard, Oregon The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test - Adjust - Balance Report Project Summary. Significant or noteworthy remarks are noted on the General Remarks or on individual test reports. Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent. Warranty is limited to one year from date of this report. Within that time, any descrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required. Submitted and Certified by NEBB TAB Firm: Accurate Balancing Agency, Inc. Certification: 3177 Expiration Date: March 31, 2011 Certification Date: July 20, 2010 Signed and Sealed by NEBB Supervisor: Edward M. May Jr. 9 � ncir� � 6, te e, r . ">07 .,: E ' o DWA�t -AY J" CE 4 HCAT ON , ,. 3177 i f Exp. 339 /{i i i dro rwG., Accurate Balancing Agency, Inc. Page 2 of 7 Supervisor: Edward M. May Jr. Terms and Abbreviations Project Location: CCS @ Washington Square - Tigard, Oregon AC Air Conditioning Unit AH Air Handler AHU Air Handling Unit BHP Brake Horsepower BMS Building Management System BTUH British Thermal Units per Hour CEF Ceiling Exhaust Fan CFM Cubic Feet per Minute CRU Computer Room Unit DB Dry Bulb DDC Direct Digital Control EAT Entering Air Temperature EWT Entering Water Temperature EF Exhaust Fan EG Exhaust Grille (Shown as Triangled number on indexed plans) ERU Energy Recovery Unit FPB Fan Powered Box (Terminal Unit which incorporates a fan) FSD Fire / Smoke Damper GPM Gallons per Minute Head Pressure Difference across the entering and leaving side of a pump HRU Heat Recovery Unit HVAC Heating Ventilation and Air Conditioning HZ Hertz Inches( ") Inches of water gauge K Correction factor to the free area needed to calculate CFM LAT Leaving Air Temperature LWT Leaving Water Temperature N/A Not Applicable N/L Note Listed OBD Opposed Blade Damper OAD Outside Air Damper OD Outside Diameter OSA Outside Air Damper PSI Pounds per Square Inch RA Return Air RG Return Grille (Shown as a Circled number on indexed plans) RPM Revolutions Per Minute RTU Roof Top Unit SA Supply Air SG Supply Grille (Shown as a Standard number on indexed plans) SFA Service Factor Amperage TAB Test; Adjust; and Balance VAV Variable Air Volume (Terminal Unit which regulates airflow) VEL Velocity WB Web Bulb Accurate Balancing Agency, Inc. Page 3 of 7 Supervisor: Edward M. May Jr. B u ' Instrument Calibration Report Project- Location: CCS @ Washington Square - Tigard, Oregon Manufacturer Model #.; Instrument � ' °', � ° s Ser # .�� I T _ alibrate C al . Due Tyne Tachometer UEI DPM5 21109672 I 10/16/2009 10/16/2010 Rotation Thermometer UEI I 550B N/A 10/16/2009 10/16/2010 Immersion Thermometer UEI 550B N/A I 10/16/2009 10/16/2010 Air Temp Electrical UEI I DL389 90501731 I 10/16/2009 I 10/16/2010 Multimeter Manometer Shortridge I ADM -860 M91491 10/14/2009 10/14/2010 Air Pressure Hygro- Thermometer Extech RH490 8089524 I 10/30/2009 10/30/2010 Humidity Anemometer UEI I DAFM2 8810692 I 10/16/2009 I 10/16/2010 Air Velocity Flowhood Shortridge ADM -860 M91491 I 10/14/2009 I 10/14/2010 Air Volume Thermometer UEI ATT47 probe 90501731 I 10/16/2009 I 10/16/2010 Contact Hydrometer Alnor / TS1 HM680 70552168 I 10/22/2009 10/22/2010 Differential Pressure Accurate Balancing Agency, Inc. Page 4 of 7 Supervisor: Edward M. May Jr. B General Remarks and Summary Project- Location: CCS @ Washington Square - Tigard, Oregon 1) See specific remarks on forms within. Accurate Balancing Agency, Inc. Page 5 of 7 Supervisor: Edward M. May Jr. FAN POWERED TERMINAL TEST REPORT Project CCS @ Washington Square - Tigard, Oregon Date 7/19/10 Submittal Test Data FPB Terminal Terminal "Type; a '.FPB Size DDC Address - Cal. Factor Fan Speed VAV - Parallel 14 "R Stand Alone N/A Potentiometer Remarks=, 1 Technician: EMMjr Accurate Balancing Agency, Inc. Page 6 of 7 Supervisor: Edward M. May Jr. !. Air Outlet Test Report Project Location: CCS @ Washington Square - Tigard, Oregon Technician: EMMjr Test Date: 7/19/2010 System / Unit;;a Design preliminary Final Test Area Served # Size Type AK VEL CFM VEL CFM VEL' CFM 0 70 VAV -1 Maximum Sales Floor 1 24x24 SG 1.00 460 460 400 400 365 365 79% Sales Floor 2 24x24 SG 1.00 460 460 335 335 360 360 78% Sales Floor 3 24x24 SG 1.00 460 460 330 330 365 365 79% Sales Floor 4 24x24 SG 1.00 460 460 260 260 360 360 78% Sales Floor 5 24x24 SG 1.00 460 460 180 180 280 280 61% Fitment Room 6 6 "R SG 1.00 80 80 105 105 55 55 69% Fitment Room 7 6 "R SG 1.00 80 80 95 95 55 55 69% Back Room 8 24x24 SG 1.00 255 255 335 335 195 195 76% Back Room 9 24x24 SG 1.00 255 255 375 375 190 190 75% Upstairs Storage 10 10 "R SG 1.00 N/L 220 220 295 295 Upstairs Storage 11 6 "R SG 1.00 N/L 55 55 75 75 Upstairs Storage 12 6 "R SG 1.00 N/L 60 60 80 80 Upstairs Storage 13 6 "R SG 1.00 N/L 50 50 70 70 Total ,., 2970 �� 2800 ' 2745 P. 92 %o VAV -1 1 Total - -- 1.00 750 750 885 885 885 885 118% Fan Total 750 885 885 118% EF -1 1 Total CEF 1.00 N/L 65 65 65 65 Exisiting RR Total 0 65 65 Remarks : .I Upstairs storage area was not shown on plans and supply diffusers located there are not equipped with volume dampers. Main level was balanced as proportionally as possible without further reducing total airflow. VAV is pressure dependent and primary air modulates between full open position in cooling mode to fully closed in heating mode. Integral heating fan is minimum obtainable adjusted to lowest potentiometer setting. Accurate Balancing Agency, Inc. Page 7 of 7 Supervisor: Edward M. May Jr. Z 1 R � I i R g 51 o . �a�� N Q r w our- , par /KO ;u 1 r r 22 2 x Z i�_XX --, ao,V2 Il fi 0 tol": E i4: ! . ° 8 ! ON QOD IL { j I 7 1A — E O o -- -- -- — - -- - -- 1 1 u :i " 1 i h ;i j A Q y� E / P •< - i $ F r , i w i w 141 q Al DI liv ill ,61 'F' i/ iii 1 g ii k. gi: T 0 Q T w o 332 a I t t,R10: iitimairdmr:i. 5 LI i 1: �" 11,1:.1 1 H - a I - 51 k 1w 1111111ROR INE X1.1 p 0, 4 aagz pi � i n: umn ■ice■ �s: q � 1 11�1i '�;��.: ■�... Z11111 1111 ., r , 1, ul ► di � A � i 13 ? 2 i . 1:r11 111IC111111�11ret11I. e ilidil " P nnun=cu��t n 33 0 � � J ■ - toriiminiiiiiiktfie.:1 1 i t L i - M MI 4 IIIIIII��II Q;4 !9 1i�1 ! q R 1 2 giiIuI' . I �r11U1l_ i$ - 1 v " qi 1 Oil 1 ! 1�II�Ii�■�:',1 •—_. - � � a X 1 ll l, 1 1 „--- IIIIIIMMIlltillmet"..411111 N lid lei: gel 0 1 i q i ° r i I. 1N• ' ' .. - l _ f lll!p1111►J�'111AJ iiiii 1111 ` 1 ■11 li�b��,u. !,IIIIII ■��111r'1 illii till > i t - 6 ®- : _ iird 1 li pU1111l ..111x' .._.. --,,� � . R P < p 11: 11EN 111 to milt 'll 73 w pl. l R r �� l'il i hli liii ghl q x ./ o R k ILL'1,o1��11111 ura. � ailm, ._ ,1 , o� i _ 4,1g{to _ ,-.r y . r 1 1 Na1 i I1 i�ii1•!ii•Ili11 11 Ig 7- . g II = a,1 - ° o' n_o 0 r t i p '4; 11 INI 111I11111111l011�111'11 / Ili i t �� 8 w Obi Y trIU • 1�19�rI O :� � � 1,11 01 § ■f •1•k31 \I�rik�71.1�lC 4 iy p } EQ�nt. o rb 7 I I N•lllllilUkklI•ll' � I d ii 1 ®-- _ 1 ; r cra i 0 1 s g r . fil i ..P q • O Iii i T Q •- Y < ($ illiii t i i S ..::::____ c. `� r it it • J• a L �~ -i, 2 Z ,; i 0� s i IC ____ ____ i ��+ � r 11 I � I 1 _ Eye - ; E L 4 ; � : 1 TO $ 1 i it fig. 50 -- x g 11 rev% qiim ; _ , ay.: .1 g 'tip * le p 'E isi - ---- g iN 4 .. 1 1 ,I2 -E- _ ' -- i , ....-7:—..--- + g Iiiiiiiiilli m. ' itt "). ®-- ' '- --7- F t ,� .- : .1 . . r , n 1 , , I „ .]I! R 0§ il - __ j < il 4 h 1 1 g th 01', 1 9 --> \ — 71: L 1 g r- ! i ! g f 0 11 1 ggi ill il I I 1, - .: 09 1 , i. i i / ! • 1100 ! i i ii l l " i r . 1 "1 ' ii ... _Imo, 1_ F r 1!I 6 6 i o IfOil'l $ m i iii P 1 g r 1 1 Z r� n 'e t - 1 1 2 5 1 o q • y d 6 t 2 1 ii 4 �'ilrg. 51 Q R r " N Q NI " il , _ ti ti " " ill qi d IR ii !„. ❑ ❑ EJ T O — e• ' ♦ n 0 r E � /vW W vW amU Icmr MAW 'I SUMO AA ax, MO - 1» -. ' Cp., FOOT LOCKER, NC. 9 ' - � I J llyl'/ // II 11 1 MUM ,u NOTE. �i / / l `I►\ DlFRISER LOCATIONS AND RovnNS of RETURN AIRr Evnc NOTE. ` Os STORE PLANNING DEPT • DUCTWORK IN SALES AREA MST BE I THE LAIIDLORD5 CENTRAL AIR GONDI11ONIN6 SYSTEM REQUIRES A ).�, O / 112 WEST 34TH STREET r w = • , - , :/,.. `ar°x°xa COORDINATED D FEATURES. AlZ a l l I EG T O u R I A � I ,L � �� F RETURN AIR AL SPACE ABOVE TENANTS BE SPGEILINS� _ �� / V /O NEW YORK, NY 10120 THE TENANTS CEILING SHALL BE S P INSTALLED ABOVE NITS CEI sl Pp I��J - a .. • °W' - -" -" (3.-0' T TENANTS CONTRACTOR S IN SHALL FURNISH INDICATED INSTALL RETURN AIR ) Lb�N C 0 � � R D Mt . L To E RE FLECTED CE ILING PLAN. (TYPICAL) NOM R O P E .s � 01L1 m ° I 6RILLFS AS INDICATED IN HIGH DEICING FOR FREE FLOW OF RETURN AIR ARCHITECT. IRON me Cr URIC m•RNL T. IC MVO WOO, MOM O r e C O RO N wimU c�=MOD /�' 03, WORE OW i C COni SODA CT Sa"M WO EXI TINE. PRIMARY z o J �`Y JAMES M. HAMILL • REMOVED. REPAIR LLCS ADJACENT TENANT 580 DECKER DRIVE RD FAN POW R 0 T RUINAL BOX DETAIL 5/A TRUNK DUCT A5 REOD G ( NOT IN CONTRACT ) SUITE 170 P).S ST MOVE, TO Q ® ® ® IRVING, TX 75062 1472.1.111e MOVE, OI VAV-1 MOOD EVAN �I LL PRIMARY SUPPLY AIR RI:I,AIN REPLACE IDSTDG I • App. ROOM EXIST VAV 42 0 12' 7' OFF. A TRIM( DUCT O 2 • • AFF. - - - - - - -I - O AeaVe OAK W SRAM ,r r , . 1 - ' / 1 , - - - I •• ii - zi_i '' o TO ��.IryIry1��� BLC• BV PP I - • �1. ■ ■ ■� — �, ■ ■. ■ ■. ■ ■ ■� .� •_. �.. • ® • D Am SMOKE A I I -- I - F- '-- ___1 —__ I ��NGH�Ke Mt /SKTT MAW 1 • g ' T'S R raaoPprrx. .two ,u_,.S -O �I -- r■11■H■ ■■� ■I■ _ ■ ■Ii■ =-- - r.,-- rs�l i 1 a fi 11 1 1 = =-= li . 1.0570.1 /0 ■ r . eb x n RIA -7 OPMS N- 1 — 1 I •"P --- -- i c` A9MGHA9P099E1L N =� � ��.� �_ M 1 1 ■ _ i i s■ i � ■������■� ■�C 0 e.xnHA- zBAYXroB ,�- 1 Ir a I ©I r PHEW IQ ; ° .�. . _ I I � _ � _ � _ € � � _ �� __ �� _ alaE: �I� ! �' 3 _ I,�I p �� �� s i�l��. MALL COMMON � AREA SEAL 255 GFp.c --411111111 • �. u11s: - ICOMMEIMEI�■II•MII � I 1 ■M11�1�1IIIMMI MEM=MIKIM TI RID' -0'APP ;r 0 > � . - ■ EXISTIIL56•DIA TOILET EXHAUST _ _ 11�■ l�i�iill��llliil .�■li�'I ■Ifi� - DUCT TO L A N D L O R D S CENTRAL I ' / . 11L� =uMMlM 4 D� "1 1a ■��I��� II_. 5M1NE DETECTOR TOILET EXHAUST SYST@4 = = _ �` P bDIA �' S - IN6 - ' I3' -• V 7 C I�1 • wo -o R' APP. .P •� U °_ � , ■. ■�� ( � I � 13 ' -1 -.. ��„I\ \ \u 1. � ■136El.1■lli�11 11 '' MALL PPS MG / TIG r � C = =i i I 1 NON- SALES __1 — 1 = =� =MMIIlaNWIE`1ii1MMILIIMM ∎M�!■1R uiu 11. CITY OF�V' 1 s.� - - -- � 2• W. I p i c c3° PO fa!�1 -4�gq� I 1 ►� _ . • e = ! ISIONS ft 5D �' EL ■■ ■ ■ w7 1e !)!%ivevF HIRED ■ ■M �I7FY = \n ■ ■ ■ ■ =1 ..,6% I i , � � ` � " .1 �' : BD �'' Ill =1112l7t: l l�_i iif:+iilG� 111.11 Ii . 1IJNN1MEN I - nd Aped D =._�RIP„oN DATE SERVICE -- - '/'°1O CORRIDOR — I See N- • ° IIMTIC . Coe Arne , ,,,m sPR.•iHt MAIN • 274 1 A PP II j I I Letter to: Follow: ca+ems SPRDC. We RAIL FRONT TO REAR • 14 APP. FIXTURES, METAL PANELS, t � © EasrN ram ROOM ADJACENT TENANT O YAY1_ • I3' -0• AFF. TRACK LIGHTING o p2' -0• AFF A H N: 1 N �/j f� 1 aI 1 SEE '!!}T NF2 FOR Q 2470 CFM (W��O DOS LLORD PRIMARY SUPPLY AIR �{ �p�• , - 201 O K/ ►jli w AieB 5 BIT5 ( NOT IN CONTRACT ) N EM VAV TERMINAL UNIT TO REPLACE PRIORY `SIA DUCT remit r � r N • +��• +• TRUNK DUCT • 22' -0• AFF 01 E)U5TWi - VERIFY EXALT LOCATION ( Fi SUE ARID RMDR - CO . �1� , , � � T�y. • _1 \ CONNECT To DOWNS IYD1A PRIMARY PROM LANDLORDS CBImAL / ..�,�I � / / psi. = may. SUPPLY AIR DUCT AS RT�IIR ®. Ad - QI NOTE PER LANDLORD PLAN PRIMARY SLPRY AR s YSTBI : M REVIEW COMMENTS. B�Ir /sy. I : _ • in! Eta • PROVIDE MINIMUM 5' -0' LINED C4345116 WALLS TO TERKNATE EE OI PECK ABODE SUPPLY AIR DUCT ON DI TO Al1D1 FREE FLOW OF REIUI AR TO LNOLCDS • • SIDE OF VAV TERMINAL REFER COMMON REDID! AIR NET VERIFY ALL MSTNS WOMB DATE. 4/01/10 TO LANDLORDS STANDARD NV REMMER5 MTH THE MALL OPERATIONS MASER TERMINAL BOX DETAIL TO BB•R CO1vLIANCE PITH LANDLORD =saw SCALE: AS NOTED PROVIDE SEC RITY MEN AS DIRECTED BY TIE TBANTS NOTE, - EXISTING DUCTWORK TO REMAIN ''t R�$rIATNE ISCHM I/2' KW 1454. DUCTYHORY AND DIFFUSERS IN SALES VERIFY EXACT SIZE AND LOCATION GROSS AREA 2,548 SD. FT • AREA SHALL BE CLEANED, PREPPED, - _ AT THE JOB 517E. SALES AREA. 1,660 SO. FT ' AND PAINTED PER THE TENANT'S REVISED HEAT GAIN / L.055 CALCULATIONS PER LANDLORD S$R FINISH SPECIFICATIONS. R TO -- EXISTING DUCTWORK TO BE REMOVED PROJECT p . 5.857.0210 71� CONTRACTOR MUST VERIFY ALL EXISTING SERVICES PLAN REVIEW COFD'ENTS, ARC W ZE ARCHITECTURAL DRAN8S. VERIFY EXACT SI AND LOCATION DRAWN BY D.H. AND CONDITIONS AT E JOB SITE. - - AT THE JOB SITE. THE RECALCULATE SUPPLY AIR CFM BASED ON IS degree delta 7 - (75d F - bOd F) BASED ON ROOM SENSIBLE 41,9•8 am NEW DUCTWORK TO BE RRRNI� TIME TENANT'S AND NVAC SYSTEM SHALL BE FURNISHED A = 2,961 CFM SUPPLY AIR • I Ib CFM / SOFT. (2548 SOFT) AND INSTALLED BY TIE CONTRACTOR INSTALLED IN STRICT ACCORDANCE WITH THE LANDLORD'S DES16N E AND CONSTRUCTION CRITIA CO TO EX vriN H REQUIRED . Pant AND ALL APPLICABLE STATE ARID LOCAL CODES. COOORDIRDI NATE ROoUTING WITH EXRISnNb CONDITIONS. 71E MOST 57RIN6ENf REQUIREMENTS SHALL GOVERN. OFFICE COPY i O SPRINKLER (MEAD NOTE: ALL ROOFING WORK SHALL BE PERFORMED BY TIE LJJDLOROS BY MECHANICAL CONTRACTOR, WITH NEW DUCTWORK (R EN (REFERENCED LOCATION) CERTIFIED AIR BALANCE REPORT TO BE CONTRACTOR AT THE TENANT CONTRACTOR'S EXPENSE. IN ORDER HVAG SYSTEM IS TO BE NEW ❑ SUBMITTED TO THE LANDLORD FOR APPROVAL TO MAINTAIN THE WARRANTY AND INTEGRITY OF THE ROOF SYSTEM. P. A FAIL 1.10019 FM El SYSTEM IS TO BE NEW, BY LANDLORDS MECHANICAL CONTRACTOR DUCTWORK BY THIS CONTRACTOR ID UPON COMPLETION OF TFg PROJECT. irlk . 1.131.01.9 Mr1•749. ❑ FIN/AC mMb* �Km ecc LANDLORD APPROVED AIR BALANCING CONTRACTOR RPM ALL CTOR IS THIS CONTRACTOR SHALL ENSURE THAT ALL EGUIPI•ENT, PIPING AND SYSTEM 15 EXISTING TO REMAIN, MECHANICAL CONTRACTOR TO PROVIDE NEW DUCTWORK .v POW MOM InneGren oum REQUIRED VERIFY LANDLORD AIR BALANCING REQUIREMENTS SHOWN � a c WITH MALL OPERATIONS PRIOR TO BID (I E, VAV REMEN BOX(S). DUCTWORK, NOT SHO TO REMMIN IS FULLY Y REMOVED AND NOT ALL InSIT. &MTN 010■11 On .1411' CA= HVAG SYSTEM IS EXISTING TO REMAIN, MECHANICAL CONTRACTOR TO REPLACE AND /OR MODIFY EXISTING DUCTWORK ra ao c•:o• no ,. COM 1.03•0C1011 o. m m � 0177M110.. Mad ,m. SMOKE EXHAUST, TOILET IXHAUST,) ABANDONED .-. REPLACE EXISTING VAV TERMINAL FEZ LANDLORD SPECIFICATION I ® MECHANICAL PLAN I SCALE: I/4' I' -O" Nsime I CONICAL BEI_LMOUTH F11711166 NTH MANAL BALANCING DAMPER TO O TIE rEcHo N F I N M CONTRACTOR SHALL REPLACE EXIST HEAT/COOL T-STAT B EXISTING TOILET FJDW.ST FM AND DSCHAR6E D1 RK TO REUSED AS SYMBOL DESCRIPTION SYMBOL DI CW PTION $ USED FOR ALL RCSD BRANCH TAPS ABODE ACCESSIBLE LAY-IN ( ABOVE FINISHED FLOORIADN AS PER LAtOLO D FICATION. INDICATED ON TIE DRAI'D1GS. TIE CONTRACTOR SHALL HALL PROVIDE SERVICE AS DAMPERS TO DE USED FOR ALL ROOD BRANCH TAPS ABOVE VERIFY / COORDINATE ALL TEPBiATURE CONTROL REQUIREMENTS AND (EXIST) HO TO ENSURE PROPER OPERATION IF RBLADIENT ° EE REQUIRED, PROJECT TITTLE BRIMS CONICAL BEIJROVfH FITTIN65 WITHOUT MANIAC INTERLOCKS H THE MALL OPERATIONS 3M ONS MANAGER. (RD•7EC.') 1 • TIE 11€ FOL ED ENS LOWING SHALL BE PROVIDED AND NSTALLID, ® SUPPLY AIR DIFFUSER I " i ED - M ML?N MECHANICAL ECUIPT INACCESSIBLE DRYWALL CEtSE MTN BALANG THERMOSTAT NS REWIRED MTNN 2 COORDINATE LOCATION OF THOSTAT WITH TENANT HADI NT FINIS. I SMEARS, DBROTC-5 BLANK -OFF A -/ L AS NOT FT. of DIFFUSER 14114 RI14114 PIASTER FRAME- (RBX N PIE EXISTING T5TAT5 PITH LSIrtSTAT MODEL 7MELV5' AS PER TOILET E)O4ALI T FAN (L]OV,1 PH, 60 HO COMPLETE WITH INTEGRAL BAG DRAFT WASHINGTON SQUARE DA ER AND ON-OFF SNITCH UNIT SHALL BE FURNISHED BY TBIANT (NITH LKHTIN6 TENANT SFECIFI ATION IF COMPATIBLE NTH EXISTING EQUIPMENT. VERIFY \ ) i BROAI MODa•6M COMBINATION 9585 SW WASHINGTON S0. 2 ROIL D R/60 Y AIR DUCTS SHALL BE EXTERNALLY INSILATED POLKA6E. EXHAI TICAPACTY SHALL BE 75 CFM. EXTEND DSCIARGE DUCT TO O DUCT MOUNTED DIFFUSER WITH I• THICK, 15 L26. DIMITY FOIL FACED REER6LA.S II£ILATION f 'MAIL OPERATIC/1G MANAGER. PROVIDED CENTRAL TOILET EXHAUST SYSTEM DUCTWIRK AND PROVIDE f (\ LIGHT/ TOILET EXHAUST FAN PORTLAND, OR 97223 Q VAV -1, COELT1ON PEN LAIOLONS? CRITERIA 8 THERMOSTAT CS-MOTES MEOW SPACE #D08 3 FLEX COIEGTIONb TO DIPFUSEFL.+ ARE NSUATED FLEX NTH A E ISTNS VAV TERMINAL UNIT AND ASSOCIATED CONTROLS TO EE REPLACED MAUMLM LBGTH OF 5 FT PBR LLORD REQUIREFENTf TIE TENANT'S CONTRACTOR SHALL VERIFY ALL O MOT USED) . • Z RETURN AIR GRILLE OR DUCT EXISTIB C IOI1IONG AND VERIFY COIPLWNGE NTH TIE LNDLORDS CURRENT 47257 - 4 MECHANICAL CONTRACTOR SHALL HALL EE REEP0NLraIBLE FOR COORDINATION DE:OIEH GRIT�IA O (71 07 ��) - ii TURNING VANES STORE NO. OF ALL TRADES, LANDLORD RECUIR EFE N1S, CEILING HENRIES MD VAV -I. / - SUPPLY AIR T RISE TV EDSTINS STRUCTURAL CONDMONS PRIOR TO FABRICATION OF ANT 8MR0 -TFZ' Mil DUCT SIM ILAR FOR RETURN AIR DUCTWORK OR ORDERDRS OF ANT EGLIFNeRT. SERIES WHENMI © FJOSSTI e S O DETECTO ITERLUCKED NTH LANDLORDS CENTRAL E .ILO IFEISAFETY 17� ,t - • 5 MECRIANC EN CINS BOX AL CONTRACTOR TO PROVIDE TENANT NTH AS -B11LT Fµ 8 9FLIRIC HEATING COILS I T$ THE CONTRACTOR STALL VERIFY PROPER OPERATION AND TIO PROVIDE SERVICE AS SITE ' I I/ \ 1 DUCT 7RANSInONS SHEET TITTLE SUPPLY AIR DUCT DROP 1I— t. DRANNSS, ALL EQUIPMENT SHOP DRAKIN S,1IFRWATION ON SEE EaIBr RMr SCIEnJJ;, SHEET M-2 FOR CAPACITIES REWIRED. COORDINATE ALL SERVICE WORK NTH HE MALL °PIRAT1ONG MANAGER THERMOSTATS CONTROL WIRING DIAGRAMS AND OTHER FSRITNEIT VERIFY ALL EXISTING CONDITIONS S 7 6Et AL CCITRACTC R TO OVER CUT DOOR 1 FOR NR PASSAGE WAY. 'SIMILAR FOR RETURN AIR ERM INFORMATION AT COIFLFTION OF PRO.EGT• I STRICT ASH HIGH SSIDE WALL BRANCH DUCT MECHANICAL VERIFY CONTROLS PACKAGE (DIG CONTROLS) AND INTERLOCKS WITH b M E CHHANICAL CONTR S TO PROV AND INSTALL FIRE DA)PB25 E 'S - BER SY MANAGEMENT SYSTEM. O PITH _ _ _ _ _ LANDLORD f.RITTRIA VILIFY Nl EXISn GOND1710H5 A TIE .100 5 ACCORDANCE 'SPIN -IN RIMS AND VOLUME DAJ•PBR PLAN V2, ' LSW LOW SIDE WALL - IN ANY EXISTING OR NEW =WORK THAT F9tITRATES A FIFE RATED © VAV -2. PARTITION AS RE BY CODE O MG. MECHANICAL AL CONTRACTOR _ EXISTING VAV TBO•DNAL UNIT AND ASSOCIATED CONTROLS, DUC7Yl7RK 9 SUPPLY AIR PICTS TO VAV TERMINAL UU7 FULL SITE OF RUT CONFLTIOH EEG. TO REMOVED PER LLORD RiL11RB•BNi. THE TENANT'S COMRTR 7 NO FIBERGLASS OR FIBERBOARD DUCT ' ALLOYED. - •'- - SHEET NO. EC. ELECTRICAL CONTRACTOR SMOKE DUCT SMO DETECTOR � 1 MUST VERIFY ALL EXISTING COMMONS AT THE .NOB SITE /� a - L .. . 1.; _ ,• ' - ' - • . 1 V /A 1 1 .0 © MECHANICAL GENERAL NOTES © MECHANICAL CODED NOTES I pD SYMBOL SCHEDULE CCS PROTO RELEASE 1.1- 03/2010 � ka. f S / d ) .54 / `? /7 5/ 7 f'7I 0 ') .77 17x5 Cam/ -pky 7s —'47,9 %s .� / 1A,7/f< Ley, ``r4 f Jo y's P /pi ca