' From: Dale Krueger [dale.krueger @comcast.net]
Sent: Friday, November 19, 2010 8:56 AM
To: Dan Nelson
Subject: FW: SOLAR JOB 10677 Lady Marion Drive
Attachments: wang drawings.pdf
Hi Dan:
Thanks for your time on the phone this morning.
As I mentioned, the clamps and rails are all one component. The Unirac engineering report rates maximum uplift for this
component at 96.6mph (bottom of Page 2 of engineers report attached and sent earlier). I hope this is the spec you were
looking for.
The other answers are below.
Time is crucial on these Solar jobs since tax incentives are a big part of the financing package, and the end of the year is
approaching fast. Thanks for your help. Please let me know if you need anything else.
Regards,
Dale
Dale Krueger
503 - 539 -7772
Original Message
From: Dale Krueger j mailto :dale.krueger @comcast.neti
Sent: Wednesday, November 17, 2010 9:24 AM
To: 'dann @tigard or.gov'
Subject: SOLAR JOB 10677 Lady Marion Drive
Hi Dan:
I failed to get your direct line number.
The load is <3.5 psf as indicated in on the installation detail form which is page 2 in the site drawing attachment sent
earlier (I have attached here for quick reference). Look at column 3 on the right side of page. The paragraph above this
refers to the requirement of any attachment within 36" of roof edge need to be 24" OC which indicates we are aware of the
requirement and will comply.
I need to know if this answers those two questions.
I will have to find the info on the clamp spec >75lbs. uplift.
Thanks for your help with the process. I can be reached at the number below. CITY OF TIGARD
Approved L c
Regards, Conditionally Approved 1 1
Dale See Letter to: Follow 1
Att.che•
Dale Krueger Permit Number: ~.
Prostat Electric Add -. • 46 : . ip
503 -539 -7772 By: 4I' Date: ' wri . .
OFFICE COPY
1
105.2.5 Building and Site Plan
_
1 : _
Job:
1 I
• . ti N
Site:
: 1 )
4... , -1' z,,z2 4,-
r ,r r
...+ 1
1 i
I 1 .
i k 4,- •i•""; ' ;
, .,•
/ ' ' 50, c 4-• .3 t"444 . ii - •-1 i ! i
7.
)
..., ., i
i 7_6- ''' '>•.,,
1 . i
(,,,,,,,,,,,
1 / :, - ,
\ : „
i , 1
1 .
1 ,
1 i 1
„.
i '!'
. ,..
I ; ,
, .
1 i '
1
! I
• t- it 1.,,,4 ,„,„:, ,%,4 ;,
1
\ 4 1
i b 'ii-7 re% ! ;,•,-• : i
--, e. -,,,, .•,,,,,,,,,, -,, ,
•3 .
1 .
i ,..,,,........,-- ,
1 ,
, •
•
1 I RECEIVE 1
It-
1 NOV 9 2 010
, _.._.......,.......,...,..,..„ ....
.(,-,
. , CITY OF TIGARD
BUILDING DIVISION
,
i 1
'. .- --r
1 i
I i
1
2 .., ' ' 1
1,
i 1
1 ,
• „/ 1 N i
- , :• I .:, ,,,
1 \ \
i \
i q I i
4
. i
„. .
--
______ _______ ___ _ ______ ._______________�_�
__ _________�__�______________ __ --_--------'---- --- --- i
---�--�------ -- 305.2 Module Attachment- 0��E �U5 4'� Kuo[K1uiotJ� |
� 104.3 � ou - � / |
! |. Installation of grid tied solar 1 | |NcLUD[L | X}{X)
photovoltaic system. 11 1Shake
i ----'-----------------' |
2. Location: ^ ]05.3.) All punciro\ion`vi|| bo|losheJ. | L on shinele <3 layers
-___--_'
/�^«�I � \ � �r�� � ��- On metal roofs, uUxchmen|yshall be
� l � OP� ������� UuJx|vi(h$u/xbnjn�cm|n^)6o�hoo| \ 305.4-3 Loading- |'Vnnodo|yundrucAo�
^ �-�� -� | nrin�|uUcdixu�cunJuoc�wiih]U5.4-3 �,eip|8less than 4.5 pounds per square
/------ --------' ------- --- \ boo. Attachments }0�
( / `� � � 4-
4 V hmn��
. u| uu � /--- --------�--�-- 7([)/\nyuku�hmuV�*�|h\n�6^o�«/*�
-------------' | 3V5 3 � hnh||ubm� wiU�omp|yvv/(h / � �
' � | cdc�hh�o'vcor ridge shall be 24"0C
| Siruciu/uSoppnUundxi�chmcm<per | �_��_�������--_-________�
/ 105 .^.ou/vu/u"''"``"=" " | code and /nunx�uUuresiosbUutimn
--- INCLUDED instructions. ' Electrical Components':
^---------- ------' -------------- Mo]okyiztxprox4U"x65"
3U4�h Array will cover plumbing vent(s) ----------- ---' ----�----- ----1 m �vci�h| �� j PS!�
| 305.4-1 Prescriptive |ny� uU�Uonx� | �
| but U\ allow k`r the required minimum � ~ ^��� VV
� will ��oJu|cYVuMz��
) clearances [|h pipe's inside diameter. \ Tog\ >40Ju}*��
/ - -������-----��--- | | |�o�h�ccrin�ioc|ud�d \ �---��-----
^ ' | System size: 1 ^ 3 ^(.) kVV
304.7 PV xyxumymn be °"" |� � � /\n�y
� np| n.nnco�/n�uno��
not less than x 30'' c|uuruucc urou»d \r\ '-- ' Refer inc)cc|hcm| d\ ran� for { � ios0/Undnv�/|\�h| framed wood information. "�
| ov�ohumc | |
u c,osovc|\on | `_-- ___--__ -_--------- |
| - trusses 24"()C and complies with
.K PV modules at least 6 " | uUowxl* spans onTuh|c305'4] height b»
| point of U | | | roof surface /o�
|' ��� -- -----------' | � --------------' -
1 | l Exempt hnnoen�iocehng- Array
1-11 ~~ ''.9 . |6oncradPuihvmyKequionnocois 1 installed over roof framing incompliance 1
----------------_�-��'��-' |
| / with allowable spans nn Table 305.4.1 Solar Photovoltaic Grid Tied
rnpt 1.A. |2"u � \o�ridge Rafter size x 8L | | Building Permit /�����om�x0x
1 - l - xcnnp\ 1.8. i2" along ridge anJ36^ "[XC Form for Single Family Dwelling,s
unobstructed pathway over | |
| supported area I | 1 Array install d over roof fixming,
| | l�xe/npbun2 Non-occupied 1 wit]) the addition (ORSC Fig kg02-1 0 �� @��
with .
'| n k
h a/7 separation I' purlins to reduce spans to comply with
��. � r��
| | Alternate inaNUudouroqoc�cdunder h|espans ,0 Table 3Uil.\ | \ S; �y
�04 !0 | size � &
'
L� �
� _--------- ------------� , ��---' ------ (
! ()[ |
| �=== . -------- '---^
| .)04...).4 A ' - shall be provide to | �@m�rm �� mwmc�r��
L and, around smoke and heat vents. _ L____ ___~~' COPIED --
`---'---- ---' ----- ----- --��
- Roof Mount Estimator - Engineerim! Report rage 1 ot ...)
Success
. This info n mati has bee c sent ,.);afrli&nationatsoiaruszs,Com
tVIL RO0i Mount Estimator - l'i,ngillceri rig Report
Customer Information Project Information
Company national solar Name wang
Contact First Address 10677 Lady marion lane
jamie
Name City, State, Zip tigard, or 97224
Contact Last Solution
abitz Roof Mount
Name Category
Contact Email jamie@nationatsolarusa.com Racking Type Solar Mount
Phone 5035089799
Engineering Variables
Description Variable Value Units
Building Height h 25 ft
- Roof Angle > 27 to 45 degrees
Wind Exposure B
Importance Factor 1
Wind Speed V 100 mph
Effective Wind Area 100 ft
Roof Zone 1
Design Wind Load Calculation
Description Variable Value Units
Net Design Wind Pressure (Uplift) P net30 (Uplift) -14.9 psf
Net Design Wind Pressure (Downforce) 14.9 psf
(Downforce) Pnet30
Adjustment Factor for Height and A
1
Exposure Category
Importance Factor I 1
Design Wind Load (Uplift) net (Uplift) -14.9 psf
Design Wind Load (Downforce)
net (Downforce) 14.9 psf
• Load Combinations Calculations
htmliwww.unirac.comlestimatorlpartiestimatoridetaillsolar/8/ I 0/27/20 1 0
- Roof Mount Estimator - Engineering Report ra■,,../e
Description Variable Downforce Uplift Units
Dead Load D 5 5 psf
- Total. Design Wind Load Pnet 14.9 -14.9 psf
Snow Load S 30
Total Load Combination 1 D + 0.75Pnet + 0.75S 38.675 psf
Total Load Combination 2 D + Pnet 19.9 psf
Total. Load Combination 3 D + S 35 psf
Total Load Combination 4 0.6D + Pnet -11.9 psf
Max Absolute Value Load 38.675 psf
Distributed Load Calculation
Description Variable Value Units
Maximum Absolute Value of Load
P 38.675 psf
Combinations
Modute Length Perpendicular to B 5.41 ft
Rails
Distributed Load (Uplift) w -32.21 plf
Distributed Load (Downforce) w 104.68 ptf
Rail Span Information
Description Variable Vatue Units
• Racking Attachment Type Single L
Racking Attachment L-Foot
Rail preference
Revised Rail Span L 4 ft
Allowable Spans
Single L Foot SML 3 ft
Single L Foot SM 4.5 ft
Single L Foot SMHD 6.5 ft
Doubte L Foot SML 3 ft
Double L Foot SM 4.5 ft
Double L Foot SMHD 7.5 ft
Point Load Calculations (per Code, these are based on maximum allowable spans as
shown in chart above)
- Description Variable Downforce Uplift Units
Single SML Point Load Force R 314.0 -96.6 tbs
hitryllwww.unirac.comlestimatoripart/estimator/detaillsolar/81 10/27/2010
- Roof Mount Estimator - Engineering Report rage _, o 1 3
Single SM Point Load Force R 471.1 -144.9 lbs
Single SMHD Point Load Force R 680.4 -209.4 lbs
Point Load Calculations for your span are:
Rail preference
Revised Rail Span L 4 ft
Sotar Mount Point Load Force R 418.7 -128.8 lbs
This engineering report is to be evaluated to Unirac SotarMount Code Compliant
Installation Manual 227 which references international Building Code 2003, International
Building Code 2006, and ASCE 7-05, ASCE 7-02 and Catifornia Building Code 2007. The
installation of products related to this engineering report is subject requirements in the
above mentioned installation manual.
•
linp://www.unirac.comiestimatorlpartlestimatorldetailisolar/8/ 10/27/2010
James A. Marx, Jr.
North Winds Center
High Mountain Road
Ringwood, NJ 07456
Tel. No. 973- 557 -6080
Fax No. 973 -835 -5924
mail:
jamlight@bellatlantic.net
March 14, 2008
Unirac, lnc.
1411 Broadway Blvd. NE
Albuquerque, NM 87102
To: Building Department or Others:
RE: Engineer's Notice of Evaluation for UniRac SolarMountrM
• Universal PV Module Mounting System Certification Letter
Dear Sir:
1 have reviewed Unirac SolarlvlountrM "Code- C:'onlpliant Installation lwlanual 227 ",
copyright February 2008 and.certiiy that the information and results are accurate. To
determine the design level forces, the appropriate wind speed shall be determined as
•
prescribed by local jurisdiction requirements and applied in accordance to the 2007
Oregon Structural Specialty Code (OSSC) which is based upon the 2006 International
Building Code (IBC) as amended by the State of Oregon. The IBC requires that wind
loading be determined based upon ASCE 7 -05 and Unirac's Manual 227 utilizes the
ASCE 7 -05 using Method 1, that which is dependent upon conditions of spatial form,
height and other structure parameters that are specified in the code provisions for
determining the applied wind loading pressures imposed onto the Unirac SolarMountTm
rails supporting solar panels_ The SolarMountTM railing and anchorage requirements for
the installation are properly represented in the Installation Manual 227.
For other conditions not covered by Method 1, the deterrnination of wind pressures needs
to be determined by the aforementioned OSS(', IBC and ASCE 7 procedures by a
licensed professional.
•
James A. Marx, Jr. P12 Certification Letter
Page 2 of 2
'I'lae design verification is based on:
I. ASCE7 -05 - -- ASCE Standard
I1. "Steel Construction .Manual," 13th Ed., American Institute of Steed
Construction, Chicago, IL, 2005.
111. "Aluminum Design Manual ", 'l'he .Aluminum Association, W ashington D.C.,
2005.
IV. Mechanical Properties and Static Load Testing of Unirac extruded rails and
related components obtained from Dr. Walter Cierstle, PE, Department of
Civil Engineering, University of New Mexico, Albuquerque, NM
Use:
Unirac SolarMountTM is evaluated for use in locations where wind pressure requirements
do not exceed 50 psi'. For loading in excess of 50 psf, Unirac or a licensed professional
should he contacted for suitability of installation. For buildings more than 4 stories or
more than 45 feet above average ground level, or other specialty buildings defined in the
OSSC, a licensed Structural Engineer should be contacted for evaluation and certification
of the Unirac SolarMounf'M and solar system.
By this letter, 1 certify that the Unirac SolarMountTM assembly, when installed in
accordance with the Installation Manual 227 will meet the .requirements of the building
codes adopted by Oregon. Others should evaluate the structure to which the Unirac
SolarMountTM system is to be connected on a case -by -case basis, per Part i Installer's
Responsibilities of the installation Manual, to ensure its adequacy to accept attachments
and to support all applied loadings per the building code.
Please call me if you have any questions or concerns.
Sincerely,
James A. Marx, Jr. PF?,
•
Professional Engineer .
l0 I ligh Mountain Road
Ringwood, NJ 07456 ,7 .' __.....
Oregon Lie. No 50037PE
cc: Aaron Dixon, llnirac, Inc.
STAND ARD
(S
1
L FOOT
■
•
J
3/8 -16 X 3/4
HEX HEAD BOLT
3/8 -16
FLANGE NUT ji ui u 48
000 A
00 Installation Detail
SolarMount Rail
1411 BROADWAY BLVD NE
ALBUQUERQUE, NM 87102 USA L, -Foot Connection
• PHONE 505.242.6411
UNIRAC.COM
URASSY -0002
PANEL
s ,
SOLAR COLLECTOR — DIMENSION
VARIES 1
PANEL. (4.5 PSF. MAX.)
1
1 ,
1 - ,
1 I
/
1 . 1
PANEL ,.;'.::.:',::::.:,::::.:::N:f.::',.:::/.::,-:::.-... ;: ' .
..,!!!!:>,,;,!;x::,,,-;2
1 !,-:....,,,..,....!;.> ..,!..:,...!...;:..,,,/,.!...!,!!!!,.....,!!!,.!,..:.::!,.:•!...,.. -- :-
DIMENSION
1 '-' l ' 1
:.,.:‘,!.s.!!:,!!...:!!..!:,, , !'.''',..!•.,
SECTION A 1 >,..?;:y.:;:j..;::.::.:.\<:-::;.--...:.::;:;,::,',::::-"7.,:2.i
"'..- '::::::',;-. ::; :•`6: :::.:.:: , ''
;t:::::? .:-.:,,,-,,,:).:::,-;L.:.:::..:-/Is:.\•:,;?,...:.-?,,,,.'-:::-.:::7,7:,,,,,..'
''
\ I ::
" ',,,±.....4:2, R, 777 : , :::;: . ".7-r::'-'' i ,'''[.:,:•: , I
SECflON
• , i'' 7 :;:::',.-::::. .N' )•.'',;:.. --77
" -4.:: :,,,,,.... ::,,,,:„. „ :„.„ ,:i.,.., , :•.,„,. , •
CONNECT SOLAR PANEL TO 1 x,,.,.s:.;;,,,,,,;.,,,,. !?0,::::,,;!..:,;!.!!!..,!..k;; "!c t
, '2,, , : ;: ; " 1
RAILS WITI 1 CONNECTOR
'.!1/ ..:!..,!!;,,,'..,,.::!!',', ,,,,.!:!..!›,,• ..... ! I
FOR EACH 8 SQ. FT. OR ,!!".-2:<!.. '"X‘-!!!",!>!?..,-,,-,g4 ,..\;,..--,-- 11
LESS OF PANEL SURFACE :.!:,.:,..../2;.;:. - : :, < !,:! :: : : , A' !,,- !!...!.! ; ,,,..; 1 ;I
.!,,,../...;,.!; 1 :1 i
CORROSION RESISTANT 1 , ! ! !.! , 1:-'i.; -.;!!!..,,..!?!,..;!:;;;,. /V.1.',X 1
METAL RAIL. ANCHOR s ' 7 :.'' . ''':' ''''.` 1 :',;::<:: I I 11
TO ALTERNATE .'::. ;:q:,',..,-::::::-;;;:?V:',
! TERNATE ROOF
FRAMING 4'-0" NIAX. ON . • .
. ,
CENTER .,.
.. ,,,.. ,. r , , , • . , , . ,..,.
11
TYPICAL, PROVIDE A , 11 i !1 ;
MINIMUM OF 2 RAIL,, c _LI ___,
1
PER PANEL
1
1
i
PLAN VIEW
_i__ . ; c FR N AI ': r .,,. 0 1\1 -1 G T:p ‘ —
PANEL
....,
MIN. 2 X 4' JOIST ,„!, _ C R ° AYL T A 1 N 9 1 O
--, -..! ,.
OR TRUSS CHORD ,..., .7 1,
•., ...,..
N, '1•
(1.D 2' MAX. ON CENTER . MA
N N I G U I F E A C T U RAIL
1i R-
EACH END OP RAIL
--,
MIN. 5/16' LAG SCREW. EMBEDDED 2" MIN.''-...
CENTER ON ROOF FRAMING.
• SEAL AT ROOF PENETRATION
'... ..1
_ '________
�a2. pull-out (wid`Vmxqlsmacihco(}h& in tvpical lumber:
Specific /ou Boil Specifications m�shall
Gravity Per 3' Per l' '-
thread depth thread depth
o"";/�Fi, 'w 705 235
Hem, Fir .43 ma zo
n km. Fir ^~^w .46 705 235
5/16" Nut-,
Block i �N N
pivots �mko(
with ���U N } )/|V nm �omm '
' " —' i��o�
5/16" NM Rubber Wnsher-„� - Er � not included '-`
� Gl6"Nu� ~�� tie '~
5/16" �o �� '`
Sealing Washer-,.. \�
```/. �
Bloc k ``„ `` " -
`~~ � u�� ) 1/4" Illo
6" |
8l6'!8x Hanger Both, /
' ��
```^ . |
�~~ |
, i IIII
}2 :�
�e�-- --- ' - [��
~ i --� /41 ��— —�
�� Li. ( � ^
i \ l/ " " l'2'' 00 or/ °
�"7 1.--i ^ � ƒ Mvwood
\ T7 � � ` ....1
� ---- ' ' r1 / '�
, � Bailey
JlW^ i ' l ' � Im�l'2
3" �
..,:‹2---F ---- --------
/ . '
V_ _- _-
1 TITLE: | | � 6
| � _� '
Scale 1:5 -------'
»*/F 80 � U^��K~ Mount ����
.• REV|S|ON ' ' u�I*��� Mount � �
_--------- — You Solution in m x nv,/uru i
� | »o • �rar, as�s�� ' \ onA�N BY -���K� ! s*" • 11,0 ' (:,,,,,,..it • /nwC ' c"*"~
�-___-_-_____-_ -- _-__-_---_ -_-.� _' _-__- __- . _-__ -
' ---'— -- -
.. .~ .. - '.^.
•
|