REPORT OF 4 X 8 CONCRETE TEST SPECIMENS
Test Methods: ASTM C31/ C172 /C192/C39/C1064/C231/C143/C1231
Date Molded: 02/11/2009 Job Number: T0807926.A
Permit #: BUP2008 -00004
Client: PFAFFLE OFFICE LLC & PCCC LLC — ROGER STALICK
Project: PACIFIC CROSSROADS CORPORATE CENTER — BUILDING A
Address: 8020 SW PFAFFLE STREET TIGARD OR Jurisdiction: TIGARD
Contractor: COMMERCIAL CONTRACTORS INC — ERIC MONEY
Subcontractor: SHARP Cast By: J. BLACK
Concrete Supplier: GLACIER NORTHWEST
Truck #: 7355 Load #: 1 Ticket #: 208257
Weather: OVERCAST Test Time:. 11:05 Air Temp. at Sampling Time: 45
Cylinders were cast for the following locations:
SAME AS BELOW
Total Concrete Placement Location:
CURB AND GUTTER ON SOUTH SIDE OF PFAFFLE ST ADJECENT BUILDING A —B FROM 15' TO
150' WEST OF EAST END REPLACES PORTION OF CURB AND GUTTER PLACED ON 1/20/09
Strength Requirement: 3000 psi f c@ 28 Days Slump: 2.750" % Air: 5.80%
Mix Number: 08805 (3.3K) Conc. Temp: 56 Cement Type: I /II Max Agg: 3/4
Admix/Amt: 80 OZ /YD CALCIUM CHLORIDE 7.5
Cubic Yards:
Register Number: 0089678 Lab Location: TIGARD
Set Test @ Date Test Total Area Unit Type Of Cap Tested
No. Days Rec'd Date Load PSI Fracture Type By
I 7 02/12/2009 02/18/2009 46385 12.60 3680 2 PAD 60 BR
28 02/12/2009 03/11/2009 61180 12.62 4850 2 PAD 60 WR
28 02/12/2009 03/11/2009 60993 12.62 4830 3 PAD 60 WR
28 02/12/2009 03/11/2009 65264 12.62 5170 2 PAD 60 WR
❑ Distribute attachments. Average f @ 28 days - 4950
Please see reverse side for additional information.
Job Number: T0807926.A Register Number: 0 089678 Date Molded: 02/11/2009
Project: PACIFIC CROSSROADS CORPORATE CENTER — BUILDING A
< 1 in. [25 mm]
.)\\. l�I
Type 1 Type 2 Type 3
Reasonable well- formed Well- Formed cone on one Columnar vertical cracking
cones on both ends. less end, vertical cracks running through both ends, no
than 1 in. [25 mm] of through caps, no well - defined well - formed cones
cracking through caps cone on other end
rr
Type 4 Type 5 Type 6
Diagonal fracture with Side fractures at top or Similar to Type 5 but
no cracking through bottom (occur commonly end of cylinder is pointed
ends; tap with hammer to with unbonded caps)
distinguish from Type 1
Asterisked ( *) average unit PSI test results did not meet listed acceptance criteria.
Remarks:
PFAFFLE OFFICE LLC & PCCC LLC - ROGER STALICK STALICKCO @COMCAST.NET
TO: CITY OF TIGARD BUILDING DIVISION
AFGHAN ASSOCIATES INC - CRAIG HARRIS CRAIGH @AAIENG.COM
MILDREN DESIGN GROUP - BETTY SHEPPARD BETTY @MDGPC.COM
COMMERCIAL CONTRACTORS INC - ERIC MONEY ERIC @CCIGC.COM
Project Manager: STEVEN W. LEACH
Reviewed By: Ty Toller On 03/13/2009
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced, except in full,
without prior authorization from this office. Under all circumstances, the information contained in this report is provided
subject to all terms and conditions of CTI's General Conditions in effect at the time this report is prepared. No party other than
those to whom CTI has distributed this report shall be entitled to use or rely upon the information contained in this document.