Correspondence d
. - ♦ 60 fr 4 . , _ _ 'J `.
Musil Perkowitz Ruth
An Architectural Professional Corp.
Architecture a Planning
April 23, 1996
Mr. Jim Funk - !' vED
Plans Examiner
City of Tigard APB 4 199&
13125 SW Tigard, ORH972223 Blvd. COMMUNITY uEVE(OpME
RE: Bingham Development M. Lawrence P M. Lawrence Musil, AIA
16920 SW 72nd Building C Simon Perkowitz, AIA, PE
PC2 -62C BUP96 -0089 Steven J. Ruth. AIA
Tigard Center Associates:
ar
Ti d, OR Gary Clements
Tigard, Kenneth P. Gunther
MPR Job #95- 947 -25 Michael J. Leberman
Branko Prebanda
Brian Wolfe
Ted Yoshizaki
Dear Jim:
We hereby resubmit for your approval the following corrections:
. Deleted the ramp at the Handicap stalls and changed the curb height to be flushed
with the asphalt, (See attached Partial Civil Plan).
2� Revised the Parking Sign on Detail 7/ SA -2.
Enetiv
1. -Form 2A completed.
Foundation to slab insulation, (See Detail 16/A -4).
Fir vLife Safety
,V Note 31 on the Title Sheet is intended to comply with the Fire Extinguisher
Requirements.
The Exit Signs will be provided by the Tenant Improvement Permit. Our intent is
to turn over a secure structure to the Interiors Contractor, who will take over the
construction when the shell is complete. That date is approximately August 1,
1996. No occupancy will occur until the Interior Contract is complete.
,Door No.1 will be the door indicated as the "Main Exit" in note No.18 on the
/ Title Sheet.
3=a. Hardware Group No.1 is correct as shown, Group No.2 is not Exit Door
Group No.3 is changed to touch bar exit devices with alarm, Hardware
Group No.4 has been added for Door No. 2 and will have an exit device.
Auto -Flush bolts are no longer required.
Commerce Center South
9150 S.W. Pioneer Court
Suite T
Wilsonville, Oregon 97070
503-685-7350 FAX 503/682-3348 Long Beach, CA Newport Beach, CA Sacramento, CA Honolulu, HI
Jim Funk
City of Tigard
April 22, 1996
Page 2
St uctura1
The Wall Section references have been revised on Sheet A -1.
2. The Wall Section references have been revised on Sheet A -1.
3. The Wall Section references have been revised on Sheet A -1.
4. Revised Footing Schedule per request.
5. Added Detail 23/ST2
6. See attached Soils Report
7. See calculations for awning labeled "M-1".
8. See attached Special Inspection Form, indicating Carlson Testing, Inc. as the
Engineer.
Plumbing
1. The roof drain has been changed to 6" (See Detail 5/A -2).
I believe this completes the corrections. Please call if you have any problems, as the
owner would like to start construction as soon as the Pad is ready.
Sincerely,
MU P • WITZ RUTH
Ed Craker
cc: Stuart Bingham Jr./Bingham Development
Karl Korach/Mackinzie Engineering
Jim Heitert/MPR
File
EC:aw
Attachments
Musil Perkowitz Ruth
Avitomze
41-4,..zok,
April 3, 1996 art OF TIGARD
OREGON
MPR Architects
9150 SW Pioneer Ct. "T"
Wilsonville, OR 97070
Re: BINGHAM DEVELOPMENT
16920 SW 72nd, Bldg. "C"
PC2 -62C BUP96 -0089
The plans and specifications have been reviewed for conformity to
applicable codes. Please submit three (3) sets of revised plans and
specifications incorporating the following requirements:
cessibility
. No ramp or obstacle may extend into the parking space or access
aisle [OSSC, Section 3104(a), ORS 447.233(3)]. Correct Detail
11 /SA -2.
. Accessible parking stall signage shall be in accordance with minimum
standards adopted by the Oregon Transportation Commission. Correct
Detail 7 /SA -2.
Energy
0) Submit a completed Form 2a (Summary sheet) from an Energy Code
Compliance Manual (Revised January 1993). Include relevant
compliance forms and documentation.
1. For slab -on -grade floors, the perimeter of the floor shall be
insulated with a thermal resistant material, no less than R -4. The
insulation shall extend downward form the top to the bottom of the
thickened slab (footing) [Section 5303 (d) 4] .
Fire and Life Safety
i 7. Provide Type 2 -A fire extinguishers throughout so that the travel
ice distance to a unit is not more than 75' [NFPA 10- 3 -2.1].
Ae4I 2. Clearly indicate all required exits, except the main entrance, with
illuminated exit signs. Provide secondary power to one lamp in each
fixture [Section 3314] .
lilk Only the main exit is permitted the exception for use of a key lock
[OSSC, Section 3304(c). Correct General Note #18.
A. Hardware Groups 1, 2, and 3 shall list latching hardware
other than cylinder locks and bolts.
. Provide manufacturer's literature for the auto -
flush bolts listed in Hardware Group 3.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
ige
,
r
MPR Architects
April 3, 1996
pg. 2
Structural
k Provide Sheet A4.1 reference on Sheet A -1 or provide correct
��/ references on Sheet A -1.
Gam. Provide Sheet A1.3 and Detail 4/A1.3.
./! What is the correct detail for Wall Line 1 and Grid Line E? Detail
referenced (20/A4.1) shows windows.
4 : Correct Footing Schedule. Sheet 2 /S -1, Line 3 should include #5 at
12" o.c. transverse, not Line 2.
Provide schedule for bolts and plate steel referenced in Detail
20 /ST2.
i O (, ' Provide a geotechnical report stating the soil classification and
design bearing capacity.
'6
� 7.' Provide the engineer's design and calculations for the awning shown
0 in Detail 2/A -2.
( 1 Complete the enclosed Special Inspection form and return to this
office prior to our issuance of the building permit. Copies of all
special inspection reports shall be filed with this office
continually during construction. A final signed report must be on
file before occupancy will be permitted [OSSC, Section 306(c)].
P1 ing
The roof drain and piping shall be not less than 5" diameter with
a slope of 1/4" per foot [OPSC, Table 14.1]. Submit a revised
Detail 5/A -2.
If you wish to discuss any of these items, please give me a call.
Sincerely,
J ames Funk G --
Plans Examiner
bup96- 0089 \pc2 -62c
Enclosure
•
Plan Review # /11. — pv�
Date CITY OF TIGARD
OREGON
Structural Special Inspections
The owner or architect or engineer of record shall complete Parts B & D of this form and then return it to the Building Division
for approval p to issuance of a building permit. (Please note that a separate soils special inspection form may be required
and additional special inspections may be required for contractor design items.)
Project Address: Project Name: R / t/ 6 j ,., n P c e l
Architect of Record (Firm): Phone No:
Engineer of Record (Firm): Phone No:
The following special inspections and structural observations shall be performed according to the State Building Code and the
City of Tigard's Municipal Code Chapter 14.06.010 - 14.06.040 unless a schedule of inspections is submitted by the Engineer
of Record and approved by the Building Division.
•
A. G: Reinforced Concrete ❑ Prestressed Concrete
E} Structural Steel ❑ Structural Masonry, f'm
a Field Welding ❑ Fireproofing
❑ Shop Fabrication 14 Other e.)-40 u f i 7 (,,,, l Y i - z r°
B. Indicate the special inspector or approved testing agency to perform the special inspections noted in Part A above,
including addresses and phone numbers. Submit names, qualifications and certifications of the special inspectors
assigned to the project. The special inspector or inspection agency shall submit a final signed report to the Building
Division stating that all items requiring special inspection and testing were fulfilled and reported and, to the best of his/her
knowledge, in conformance with the approved design drawings, specifications, approved change orders and the
applicable workmanship provisions of the U.B.C. (see U.B.C. 7015 for soils special inspection final report requirements).
Items not in conformance, unresolved items or any discrepancies in inspection coverage (i.e., missed inspections,
periodic inspections when continuous was required, etc.) shall be specifically itemized in this report.
C. ❑ Structural Site Observation by Engineer cf Record
D. The owner hereby agrees to employ the special inspector, approved testing agency and/or engineer for the above -noted
special inspections and /or structural observation.
Signature of Owner
Print Name Phone No.
Firm Date
Structural Plans Examiner signature sirs+.da
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
�11`1 A\ DevE't OPA4 T
c,j c12- CITY OF TIGARD
gI50 5VU piotJEW Cr, ''T
W ILSOMVIlA/E, OP- x7070 OREGON
Dear Applicant:
The Development Services Team recently received building plans for your commercial
project without a sitework permit application. To expedite the plan review process, please
forward a sitework plan (one copy), permit application and payment as soon as possible.
After the sitework plan is received the Plans Examiner will be able to address:
1. Handicap Accessibility
2. Storm and Sanitary Sewers (building laterals)
3. Fire Line, Water Line, Private Water Mains, Water Meter Location and Size
4. Site Erosion
5. Site Detention (grading, retaining structures)
6. Utility Location
7. Private Streets
8. Landscaping (per conditions of land use resolution)
Overall, the sitework plan determines many of your development's features. Before the
building plans are approved the sitework plan is distributed to Tualatin Valley Fire and
Rescue, United Sewerage Agency, and the City's Water, Engineering, Planning and
Building Departments for comments and corrections. This preliminary coordination takes
extra effort, but will result in fewer revisions and quicker final approvals.
Thanks for your cooperation. If you have any questions or concerns, please feel free to
contact me at 503 - 639 -4171, extension 322. If you reach my voice mail, please leave a
message or transfer to the Development Services Team at extension 304.
Sincerely,
Jill Aldrich, Customer Service Manager
Community Development
PROJECT: ADDRESS: PLAN CHECK NO: NOTICE:
E11JC& ice/. "rz fob /Puz.NAM zJ&zc [ ] first
- rI &A DATE: 2431q6 z3 /gb [ 14 second
COMMENTS: sl Wpp - r0 W Ct.-U M - DC&S - 5uBU1 it A5
P4A5e - o e set Ol= PLANS OI- Fog NOW ! `/
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
_. 60PC CO <<
., DATE: 1 PLANS CHECX NO.:
' CS-0/--q& oz -6 C
PROJECT TITLE:
COUNTYWIDE , CS .---,4,.._ \' be've ror..--e____77
TRAFFIC IMPACT FEE APPLIT:
WORKSHEET
MAIUNG ADDRESS:
(FOR NON - SINGLE FAMILY USES) 759 - 5 N i.1 4 S K
CITY/Z1P /P NE
RATE PER I'or il
a. -c( c rK 9 zio
LAND USE CATEGORY TRIP TAX MAP NO.:
RESIDENTIAL 5159.00 0 c 1) 3./ ( - o 1 :f-o - n
BUSINESS AND COMMERCIAL , S40.00 Smis NO. ADDRESS: _
OFFICE 5146.00 , / (sS Fc' - ` ��
INDUSTRIAL 5153.00
-
INSTITUTIONAL 566.00
PAYMENT METHOD:
(:ASH i t -4FCi<
CREDIT var; of - 7q, 9vs i it S P')"J riD,, INSTTTiJTIONAL
BANCROFT (PROMISSORY NOTE LAND usE CATEGORY DESCRIPTION OF USE NEEXCAY AVG. TRIP RATE WEEKEND AVE TRIP RATE
DEFER TO OCCUPANCY I S e.r-r .. c I/5 / T ^ P'
nn q C
BASIS: j i _ /
�
(r i s c a_ -I rro k a
,,,S ( pet �57 o it SAC ��.
lI . !cf'�
ii
car c,(- z 4-1 1115 4 �t` ° .4q ( 91,: e - ,
r .
CALCULI► T IONS: �7 / c {- i .L /Tr.'� ' / S (c cF-_. I (�,
PROJECT TRIP DENERATION:
zr4
FEE: 1gS $ .2, CI
ADDITIONAL NOTES: FOR.AGC;,UNTING PURPOSES ONLY:
r _ M 1 = C . ! rr� n j f + — �. � _ ' ROAD AMT.:
l . ff
b r Al-- T .
_ r c ,
T— r - ,
„ - � TRANSIT MST.:
/ _ 0 0 &'. 07.3 RRE?AAED 3Y: --,
i
CC. WASHINGTON COUNTY
T1F 4OTE3OCK CfTT1
May 2, 1996 ,,,, , lu I \*
MPR Architects CITY OF TIG�RD
ATTN: Ed Craker
9150 SW Pioneer Court "T" OREGON
Wilsonville OR 97070 FAX: 682 -3348
TRAFFIC IMPACT FEE FOR Bingham Development
16920 SW 72nd Bldg C
Enclosed with this letter you will find a calculation sheet showing the
computation that has been performed to determine the amount of the
Traffic Impact Fee (TIF) to be paid for the project noted above. The amount
of the TIF is $85,862.00.
You have three payment options available to you. The first is to pay the TIF
at the time you are issued a building permit. The second is to arrange for
payment over time by signing a promissory note (if you wish to exercise
this second option please contact me for additional details). The third
option is to defer payment until occupancy. Traffic impact fees are subject
to an annual increase of up to 6% if not paid or financed prior to July 1st
of each year.
Please note that you may appeal the discretionary decisions made in
determining the appropriate category and the amount of the fee based on
that category. A notice of appeal must be received by the City Recorder no
later than 5:00 p.m. on May 16, 1996 and must be accompanied by the
$625.00 appeal fee required by Washington County. Although filed with
the City Recorder, an appeal would be heard by the Washington County
Hearings Officer.
If you have any questions, or if I can be of further service, please contact
me at 639-4171.
James S. Duckett, Development Services Technician
c: TIF file
Building file
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
•
COUNTYWIDE CITY OF TIGARD
TRAFFIC IMPACT FEE OREGON
PAYMENT OPTION FORM
co )Lodi
Date Site Address
t �P
70().— c
Project Name Plan Check #
I realize that I must make a decision on payment of the Traffic Impact Fee (TIF) at this time. Therefore,
I request the following (choose whichever option or options are applicable):
❑ Cash or Check
❑ Credit Voucher
❑ Bancroft or Installment Payments
and/or
❑ The Ordinance allows for deferral of payment of the TIF until issuance of the occupancy permit
if the TIF is greater than $5,000. If the TIF meets this requirement, I also request this option.
I understand the TIF must be paid prior to issuance of an occupancy permit. I also understand
that the TIF will be recalculated based on the prevailing rates at the time of payment. Please
be advised that TIF rates may increase up to six percent each July 1st. This rate increase is not
subject to appeal.