Correspondence Musil Perkowitz Ruth
1� iC (0-01q c
An Architectural Professional Corp.
Architecture • Planning
August 9, 1996
i' i 1 ,,
Mr. Jim Funk, Plans Examiner
City of Tigard
13125 S.W. Hall Bo - ..
Tigard, OR 97
g � p Principals:
�o $ 7 a l/` "' M. Lawrence Musil, AIA
RE: Borders Shell Simon Perkowitz, AIA, PE
• Bingham Development Steven J. Ruth, alA
Plan Check NMEC #96 -0199, PC #6 -104c Senior Associates:
Brankc Prcbanda
MFR Job # 95- 947 -25 Gary Clements
Ken Gunther
\ Marios Savopoulos
Dear- im: Brian Wolfe
Ted Yoshizaki
In response + our corrections, pleas - : =- attached. I have included a stamped Associates:
calculations for atta 1 - - : . • r conditioning unit to the roof structure. All Casanova
John Bost
, I am sending a mechanical plan showing the location of all the air
Jonathan Gray
Secondly, g P g Michael Heinrich
conditioning units, the indication for labeling and an equipment schedule. David Littman
Peter Paszterko
Mike Salmon
Lastly, the electrical receptacles are being provided under the T.I. contract.
I trust this will meet with your approval.
If you have any questions, please call me.
Sincerely,
MUSI PERKOWITZ RUTH
•
a
/
Ed Craker
EC:dks
cc: File
Enclosure •
9150 S.W. Pioneer Court CC 6eauee MimelL
Suite T
Wilsonville, Oregon 97070
(503) 685-7350
FAX (503) 682-3348
Long Beach, CA Newport Beach, CA Sacramento. CA Denver, CO Washington, DC. Wilsonville. OR
July 31, 1996
CITY OF TIGARD
Temp Control I
4800 N Channel OREGON
Portland, OR 97211
RE: Tigard Center "Bldg C" Mechanical Plan Review
16920 SW 72nd Ave
PC #: 6-104c MEC #: 96-0199
Submittal documents for the above • referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted: •
� w MIE Cl�'ANIC C '" I_ �??��,, ��, .. T'r4 t GS, W latt 43v {yrP.,�y /} t
1. Submit three (3) sets of mechanical plans for review.
A. The attachment of permanent equipment (HVAC) supported by the
building's structural components shall be designed to resist the total
design seismic forces prescribed in Section 1603.2 of the Structural
• Specialty Code. Provide an engineer's design specifying attachment
requirements [SSC Section 160.3.2 and OMSC, Section 304.4].
B. Each individual roof - mounted HVAC shall be permanently labeled as to
the areas it serves [OMSC, Section 304.5]. In addition, each unit shall be
equipped with a power disconnect and a 120 -volt receptacle shall be
located within 25' of each unit [UMC, Section 309.1].
2. The plan shall include an equipment schedule illustrating:
A. Size of units, btu's of cooling/heating.
B. Unit weight.
C. Economizers.
Please submit three copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.