Correspondence 6() 1-6C)C-1-002.4r A„, June 17, 2004 CITY OF TIGARD OREGON Delta Fire 14795 SW 72 Avenue Portland, OR 97224 RE: MODIFICATION TO FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2004 -00248 Construction Type: VN Tenant Name: Baggallini Occupancy Type: B Address: 16650 SW 72 Avenue, #B -12 Occupant Load: NA Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so'that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 2. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 3. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. Standard 9 -1, section 4 -4.1.6 OSSC 4. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 %2 inches shall be not less than 1 inch. Standard 9 -1, section 4- 5.4.3.4 • Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772