Plans City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
June 7, 2007 • q
•
RE: FIRE SPRINKLER TENANT IMPROVEMENT
Project Information T I GARD
Building Permit: BUP2007 -00267 Construction Type: 3B
Tenant Name: Service Master Occupancy Type: B /S -2
Address: 16570 SW 72n St. Occupant Load: 75
Area: 7500 Sq. Ft. Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
2007 edition; National Fire Protection Association, Standard 13 (NFPA 13)2002 edition and the
State of Oregon Fire Code (OFC) 2007 edition. The submitted plans are approved subject to the
following.
GENERAL
1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so
that any sprinklers that have operated or been damaged in any way can be promptly
replaced. These sprinklers shall correspond to the types and temperature ratings of the
sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2 NFPA 13.
2. The spare sprinklers shall be kept in a cabinet located where temperatures will not
exceed 100 degrees "F" at any time. A special sprinkler wrench shall be provided and
kept in the sprinkler cabinet to be used in the removal and installation of sprinklers.
Sections 6.2.9.3 & 6.2.9.6 NFPA 13.
3. The clearance between the deflector and the top of storage shall be 18 inches or greater.
Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop
sprinkler heads. Section 8.11.6 NFPA 13
4. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less than 6
feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13.
• 5. Clearances shall be provided around all piping extending through platforms,
foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the
penetrating pipe for pipe sizes 1 inch through 3 '/z inches. The diameter of the hole shall
be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger. Sections
9.3.4.1 & 9.3.4.2 NFPA 13.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
•
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
' espectfully,
/WTI
A
•
Dan Nelson,
Senior Plans Examiner
. - - 6v, 2W1'�'G26, 7
'
AUTOMATIC SPRIN - •-t " ti w a r tr
� �
• FIRE PROTECTION PRODUCTS r ,.
\ /
V27, K5.6
Models V2703, V2704, V2707 and V2708
High Pressure Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 high The die cast frame is more ture rises causing the liquid
A >����: � °: . v2707 pressure standard spray streamlined and attractive in the bulb to expand.
ci: „ - .a,f- v2708 sprinklers are designed to than traditional sand cast When the ambient temper
produce a hemispherical frames. It is cast with a ature reaches the rated
.- spray pattern for standard hex - shaped wrench boss to temperature of the sprin-
commercial applications up allow easy tightening from !der, the bulb shatters. As a
4. to ordinary hazard, exclud- many angles, reducing result, the waterway is
• Recessed ing storage applications. assembly effort. This sprin- cleared of all sealing parts
Pendent They have a rated working kler is available in various and water is discharged
M ressure of up to 250 psi temperature ratings (see towards the deflector. The
P P s P P g
�'� 0® ` ' (1725 kPa) and are available chart on page 2) and fin- deflector is designed to dis-
•- . ,," with either standard or ashes to meet many design tribute the water in a pat -
yryr,. -' r••,i v2707
s V2708 quick response bulbs. The requirements. tern that is most effective
e design incorporates a state- Sprinkler Operat in controlling the fire.
1. e'Q ,, o f-the-art, heat responsive, The operating mechanism Coverage
g glass g is a frangible glass bulb For coverage area and
Al frangible lass bulb design
V' t (standard or quick which contains a heat sprinkler placement, refer
,, response) for prompt, p re- responsive liquid. Duran a to NFPA 13 standards.
. ,44..,::; : P q g
*;
vise operation.
Pendent fire, the ambient tempera-
. V2703 -(:
V2704 '_- r
m' ':
Upright
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707, MATERIAL ACCESSORIES
V2708 SPECIFICATIONS Installation Wrench:
0 Style: Pendent, Upright or Upright Deflector: ❑ Open End: V27
Recessed Pendent Bronze per UNS C22000 ❑ Recessed: V38, V38 -3
• Nominal Orifice Size: Pendent Deflector ❑ Socket: V27
0 1/2" (13 mm) Bronze per UNS C51000 Finishes:
K-Factor: 5.61mp. (8,1 5.1. ^) Bulb: Glass with glycerin solu- ❑ Plain brass
Nominal Thread Size: Uon ❑ Chrome plated
t /2" NPT (15 mm) Bulb Nominal Diameter: ❑ White painted **
igz, ❑ Standard: 5,0 mm ❑ Flat black painted **
Max. Working Pressure:
'li i 250 psi (1725 kPa) ❑ Quick Response: 3,0 rnm
0 painted **
Factory Hydrostatic Test: • Load Screw: Bronze per UNS ❑ Lead **
^ � `
J 100% @ 600 psi (4140 kPa) C65100 155, 200, 286SR Only
Min. Operating Pressure: Pip Cap: Bronze per UNS ❑ Wes**
7 psi (48 kPa) C65100 0 Wax aver lead **
UN Temperature Rating: See Spring: Beryllium nickel For cabinets and other accesso-
IMP
chart on page 2. Seal: Teflon* tape ries refer to separate sheet
Frame: Die cast brass 65 -30 NOTE: weather resistant escutcheons
available upon request.
Lodgement Spring: * For K -Factor when pressure is mca-
Stainless steel per UNS S30200 surcd in Bar, multiply S,l. units by
Exaggerated for clarity 10,0.
• Teflon is a registered trademark of
Dupont Co.
"" UL Listed for corrosion resistance in
all configurations.
VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1- 800 -742 -5842) Phone: 905 -884 -7444 Phone: 32 -9 -381 -1500 Phone: 610 -559 -3300 Phone: 65 -6235 -3035
Fax: 610 -250 -8817 Fax: 905 -884 -9774 Fax: 32 -9 -380 -4438 Fax: 610 -559 -3608 Fax: 65-6235-0535
e- mail:pickvic@victaulic.wm e-mail: viccanada@victaulic.com e-mail: viceuro@victaulic.be e-mail: vical@victaulic.com e-mail: vicap @victaulic.com
2599 Rev.D 5/03 ® Registered Trademark of Victaulic a Copyright 2003 Victaulic Primed In U.S.A.
C
DISTRIBUTION PATTERNS
MODELS V2707, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10'
8' , _
2,4 m
1 7 psi - -- ---
\ 48 kPa
1,8 m
\ 15 psi
103 kPa
4' . \ �
1,2 m "\
30 psi
\ 207 kPa
2' \ -
0,6 m \
\ `
0
2' 4' 6' 8' 10 ' 12' 14' •
0.6 m 1,2 m 1,8 m 2,4 m 3,0 m 3.7 m 4,3 m
• MODELS V2703, V2704
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
10 ��_
3,0 m 5
2.4m \ \ `` -\-
\ 7 psi -- —
48 kPa
6' \
1,8 m \
. 15 psi
\ 103 kPa
4 , \
1,2 m `\
30 psi
\ . 207 kPa
2' \
0,6 m
2' 4' 6' 8' 10' 12' 14' 16'
0.6 m 1,2 m 1.8 m 2,4 m 3.0 m 3,7 m 4,3 m 4,8 m
NOTES: .
1. Data shown is approximate and can vary due to differences in installation.
2. These graphs illustrate approximate trajectories, floor - wetting, and wall - wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
3. All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaufc Installation/assembly instructions.
Vlctaulic reserves the right to change product specifications, designs and standard equipment without notice and without Incurring obligations.
40.13 -4
•
on
O
' tve—v ) - ri, - . ----- ,-,_ 0-5
MI DI
u I co
1 (1
1 ` + • A'E10 A /POS /od
• ' : ��111�`�AI . � - - ,. o Nec<1 dot A�tl �� ?b M�Cl�1
1
1
IA I° ti F 7. —; • �■ II _ ;
-4
IEEE I '. Et ►ir/1ci : '
Hill. . , . . ... .
1..._ _k _ .
Immo ...I �m Xel ;
•
-----... .. .
I
,..,
.___,,) . •.. •..
- -n a � --1 — '_--. -� / 'u
_. - -'
r '
liell11111111Paalli
1111V1111111 IIIM
UII1011 ■UI _ ► ► 6 _ I -7
I I
INSTAL NEW P AIDARD2X2 NBTALLIEWPACTRUST STANDARD 2X2 EOM PACTRUSTSTAIDARD2X2
OBIS GRID AT AF AREA CBJNGORDATSAFF. THIS AREA. CIMING GRID ATWAFF. THIS AREA
/45/c, l 456 Co /6.542
PHASE 3 CONSTRUCTION . PHASE 2 CONSTRUCTION PHASE 1 CONSTRUCTION
1 REFLECTED CEILING PLAN Oz ( .
A -3 SCALE 1/8" =1' -0" do SWIpI KCC1 MoDEF/C,
Attee01 /Ar M41 1
BUILDING LOCATION
INT ERSTATE 5 G
1 §ER V l CE / 4 5 TEE. 61 l '\. . 6
11 AL
�� II 2 I l 11 S
111 1! JIIPI __ I ' � 1 -- p i i ri PABKI C
l' - p °•, _,� 1:__� . _.
LOCATION MAP F1 RE5 T o P Co.
z TIGARD , DR. # 5 7/157
NOT TO SCALE
i CITY OF TIGARD
- Approved .-. .tf [
FP11,- -- Conditionally Approved.. ».N [ ]
� j `` See Letter to: Follow.N...N [ ]
At� e�d....... [( ]
� FR / c- Permit Nuntbe 31 ZC 7 - 0,?
t ` Ad, • 1 . Z 87
By ■A Date: , ,dr
OFFICE COPY