Correspondence ei6 March 29, 1996 O'TY OF OREG Johansen Electric, Inc. Attn: Carl K. Johansen 1130 NE 174th Gresham, OR 97230 Project: TUFCOAT, INC. I4 x`00 SW 72nd Tigard, OR 97224 Subject: Electrical Plan Review (ELC96 -0152) The plans submitted were reviewed for conformity with the 1993 National Electrical Code (NEC) and the State of Oregon Electrical Specialty Code. The following was noted: 1. The 1993 NEC is the minimum electrical requirement. 2. Electrical equipment approval notes: A. Listed equipment with U.L., ETL or factory Mutual Labels is approved. B. Equipment without listing: 1. Requires electrical inspection by Michael Rudd, Electrical Inspector, prior to connection. 2. Classified equipment may require field testing by an approved testing laboratory. a. Underwriters Laboratories Inc. (U.L.) of Camas, WA. Telephone: (360)817 -5613, contact: Scott A. Varner. b. Inchcape Testing Services (ETL) of Beaverton, OR. Telephone: (503)626 -6694, contact: Jim Pierce. 3. The "Powder Booth" will have openings for a conveyor to pass through. These locations will be Class II, Division 2 areas, for a distance of 3 feet from the opening. NEC 516- 2(b)(3). 4. The permit does not indicate any control, branch circuits or feeders to equipment. 13125 SW Had BMd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Johansen Electric, Inc. March 29, 1996 pg. 2 5. The electrical installations involving industrial machinery will meet the minimum standards of NFPA 70 (NEC) 1993, the State of Oregon Electrical Specialty Code and NFPA 79 (1991). Please contact Michael Rudd at (503)639 -4171, ext. 356, to discuss the electrical notes. Thank you for your coo.eration. l/ . 'chael Rud Electrical Inspector e1c96- 0152 \tufcoat.doc F . ti. = �s • cl Cc - (vs?, March 29, 1996 CITY OF TIGARD OREGON Johansen Electric, Inc. Attn: Carl K. Johansen 1130 NE 174th Gresham, OR 97230 Project: TUFCOAT, INC. 1(0300 - 16-200 SW 72nd Tigard, OR 97224 Subject: Electrical Plan Review (ELC96 -0152) The plans submitted were reviewed for conformity with the 1993 National Electrical Code (NEC) and the State of Oregon Electrical Specialty Code. The following was noted: 1. The 1993 NEC is the minimum electrical requirement. 2. Electrical equipment approval notes: A. Listed equipment with U.L., ETL or factory Mutual Labels is approved. B. Equipment without listing: 1. Requires electrical inspection by Michael Rudd, Electrical Inspector, prior to connection. 2. Classified equipment may require field testing by an approved testing laboratory. a. Underwriters Laboratories Inc. (U.L.) of Camas, WA. Telephone: (360)817 -5613, contact: Scott A. Varner. b. Inchcape Testing Services (ETL) of Beaverton, OR. Telephone: (503)626 -6694, contact: Jim Pierce. 3. The "Powder Booth" will have openings for a conveyor to pass through. These locations will be Class II Division 2 areas, for a distance of 3 feet from the opening. NEC 516- 2(b)(3). 4. The permit does not indicate any control, branch circuits or feeders to equipment. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 - Johansen Electric, Inc. March 29, 1996 pg. 2 5. The electrical installations involving industrial machinery will meet the minimum standards of NFPA 70 (NEC) 1993, the State of Oregon Electrical Specialty Code and NFPA 79 (1991). Please contact Michael Rudd at (503)639 -4171, ext. 356, to discuss the electrical notes. Thank you for your coo.eration. f J.LUIO chael Rudd Electrical Inspector e1c96- 0152 \tufcoat.doc • 1 , {