Correspondence CITY OF TIGARD
August 29, 2001 OREGON
John Romish
15350 SW Sequoia Parkway, Suite 300
Portland, OR 97224
Re: Plan Review
Project Information
Address: 16112 SW 72 B -18 Sprinklered: Yes
Occupancy: B Firewalls: 1 -Hour Corridor
Construction Type: VN Occupant Load: 79
The plans for the above referenced project have been reviewed by the Building
Division and are approved subject to the following items. This review was
performed under the provisions of the State of Oregon Structural Specialty Code,
1998 edition.
1. Plumbing, mechanical and electrical permits are required for this project.
2. A minimum 40 -B fire extinguisher shall be located within 30 feet of the kitchen
cooking equipment in accordance with UFC standard 10 -1. UFC 1006.2.7.
3. Minimum 2A:10BC fire extinguishers shall be located so that the travel
distance to them does not exceed 75 feet. UFC Standard 10 -1.
4. A copy of the approved plans shall be kept on -site during construction for
inspection purposes. OSSC 106.4.2.
5. A final inspection and certificate of occupancy is required prior to occupancy
for the intended use of the structure. OSSC 109.1.
Sincerely,
Gary Lampella
Building Official