Correspondence (3) February 1, 2005���`
CITY OF TIGARD
OREGON
Architecture Northwest PC
Peter Kappertz
11930 SE Zion Hill DR
Gresham, OR 97080
RE: SHELL STATION
Project Information
Site Permit: STT2004 -00032 Construction Type: II -A
Tenant Name: SHELL STATION Occupancy Type: M
Address: 15900 SW 72nd Occupant Load: NA
Area: 2436 Stories: Canopy
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
2004 edition; and the Tualatin Valley Fire & Rescue Ordinance 99-01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
EROSION
1. Erosion control measures shall be in place prior to excavation or grading.
FIRE
2. Contact Tualatin Valley Fire and Rescue, Eric T. McMullen 503 -612 -7010, for permits
required for Motor fuel dispensing facilities.
3. The private fire service main shall be at least 30 inches below grade.
4. The private fire service main shall be flushed thoroughly before connection to the
system riser in order to remove foreign materials that might have entered the main
during the course the installation. The flow rate shall not be less than the water demand
rate of the system.
5. All piping shall be inspected prior to backfill.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
FIRE DEPARTMENT ACCESS
6. The driveway is considered a fire department access roadway. The driveway, to the
point of the "Hammer Head" turnaround, shall be capable of supporting a 12,500 pound
wheel point load and a gross vehicle weight of 50,000 pounds.
ACCESSIBILITY
7. Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in 20
units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50 units
horizontal (2% slope).
8. Accessible parking spaces and access aisles shall be located on a surface with a slope
not to exceed 1 unit vertical in 50 units horizontal in all directions. 1104.4.3 OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road fronting
the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectful ,
al Henze G �� ��
Senior Plans Examiner